answersLogoWhite

0

You really should be asking what is 'line' and neutral.

In Europe, the secondary winding of a distribution transformer has a pair of terminals. One is connected to earth and, therefore, has a potential of approximately 0 V with respect to earth. This terminal is termed the neutral, and the conductor connected to this terminal is called the neutral conductor. The other terminal is termed the line, and the conductor connected to this terminal is called the line (not 'phase'!) conductor. A distribution transformer's line conductor has a nominal potential of 230 V with respect to the neutral.

In North America, distribution Transformers' secondary windings have three terminals. The centre terminal is grounded, and provides the neutral. Each of the outer terminals acts as a line terminal. The nominal potential difference between each of these two line terminals is 240 V, while the nominal potential between either line terminal and the neutral terminal is 120 V.

User Avatar

Wiki User

13y ago

What else can I help you with?

Related Questions

If in the three phase connection phase to phase voltage is 400v what will be the phase neutral voltage?

The formula to use is, phase voltage /1.73 = phase to neutral (ground) voltage.CommentThere is no such thing as a 'phase to phase', or 'phase to neutral' voltage. The correct terms are 'line to line' and 'line to neutral'. So the above answer should read: line voltage/1.73= line to neutral voltage = phase voltage.


When phase and neutral will short means what will be the voltage in neutral?

If the phase and neutral wires are shorted together, the voltage in the neutral wire will be the same as the phase voltage. This is because the short circuit effectively bypasses any impedance or resistance in the circuit, causing the potential difference between the phase and neutral wires to be equal.


What is the code ruling in the US on 3 phase branch circuits and the neutral?

A three phase system will have 3 phase branch circuits and no neutral.


What happens when phase to phase line is connected?

If there is a voltage differential from phase to phase, and a conductance (inverse of resistance) between them, then current (amperes) flows. This is no different than phase to neutral, i.e. voltage across conductance generates current, (I = EC, or I = E/A) except that neutral current is zero in a true phase to phase connection.Note that phase angle is always relative. In phase to neutral, it is relative to (typically) neutral; while in phase to phase, it is relative to the other phase. By Fourier Analysis, the difference between two phases of the same frequency, but of different phase angles, is still a sine (or cosine) wave. Also, by Kirchoff's Current Law, (implied, and I will (sort of) not repeat it here), current entering from one phase and equally leaving via another phase will not reflect at all in the neutral conductor.The simple answer is that connecting phase to phase is a short circuit, just like connecting phase to neutral.CommentThere is no such thing as 'phase to phase' or 'phase to neutral'. The correct terms are 'line to line' and 'line to neutral'.


How does a phase leg connect to a neutral in an electrical circuit?

A phase leg connects to the neutral through the connected load.


Why neutral is not requied in 3 phase?

As far as I understand, you don't need neutral line for connecting appliances that is 3-phase compilant. You only need the neutral line to connect a single phase appliance, which you connect along with one of the three lines.


What is the voltage for each leg on a 480v 3-phase pannel phase to neutral?

Only one neutral conductor is typically in a 3 phase panel.


What is the power line voltage between phase and earthing?

It is the same as phase to neutral. As the neutral is earthed at the electricity suppliers transformer.


Why the neutral cable takes high current than the phase lines in three phase installation?

In a balanced three-phase system, the current in the neutral wire should ideally be minimal as the three phase conductors carry equal and opposite currents that cancel out in the neutral wire. However, if the loads are unbalanced, the neutral wire may have higher current due to the uneven distribution of power among the phases. This can happen when loads on each phase are different or when single-phase loads are connected between a phase and neutral, leading to increased neutral current.


What would be the effect on the neutral bar of a 3 phase D B if the main incoming neutral is lost?

A three phase delta system does not use a neutral in its operation.


Why neutral is necessary in a single phase operation?

Neutral is a return path.


Do you need a neutral to install 480 volts 3 phase heater?

If the heater is rated as a 3 phase 480 volt heater then a neutral is not needed. If the voltage stated is 277 volts three phase then a neutral is needed.