To enable any gases generated within the transformer to bubble along the pipe towards the expansion tank. The Buchholz relay itself isn't angled; it's the pipe in which its fitted.
The Buchholz relay is installed in an inclined position because of buoyancy. Slightly inclined so the gas bubbles will flow to the cover and then to the Buchholz relay and not stay in a pipe corner.
A Buchholz relay is situated in an inclined pipe between the transformer itself and its expansion tank. It (a) provides an alarm should there be an oil leak or if excessive gas accumulation within the relay and, (b) will disconnect the transformer in the event of a major oil loss or a surge within the oil (caused by a fault within the transformer).
A major cause of decomposition of transformer oil is minor arcing within the transformer. Decomposition results in gas which bubbles towards the top of the transformer and upward into the conservatory tank. Between the transformer and conservator tank is a Buchholz relay, in which this gas collects, causing a mercury switch inside a float to initiate an alarm in the substation. This gas can be collected through a small pipe feeding from the Buchholz relay in order to have it analysed.
An electrical device, typically incorporating an electromagnet, which is activated by a current or signal in one circuit to open or close another circuit.Based on Characteristic the protection relay can be categorized as-Definite time relaysInverse time relays with definite minimum time(IDMT)Instantaneous relays.IDMT with inst.Stepped characteristic.Programmed switches.Voltage restraint over current relay.Based on of logic the protection relay can be categorized as-Differential.Unbalance.Neutral displacement.Directional.Restricted earth fault.Over fluxing.Distance schemes.Bus bar protection.Reverse power relays.Loss of excitation.Negative phase sequence relays etc.Based on actuating parameter the protection relay can be categorized as-Current relays.Voltage relays.Frequency relays.Power relays etc.Based on application the protection relay can be categorized as-Primary relay.Backup relay.Primary relay or primary protection relay is the first line of power system protection whereas backup relay is operated only when primary relay fails to be operated during fault. Hence backup relay is slower in action than primary relay. Any relay may fail to be operated due to any of the following reasons,The protective relay itself is defective.DC Trip voltage supply to the relay is unavailable.Trip lead from relay panel to circuit breaker is disconnected.Trip coil in the circuit breaker is disconnected or defective.Current or voltage signals from CT or PT respectively is unavailable.As because backup relay operates only when primary relay fails, backup protection relay should not have anything common with primary protection relay.Some examples of Mechanical Relay are-Thermal(a) OT trip (Oil Temperature Trip) (b) WT trip (Winding Temperature Trip) (C) Bearing temp trip etc.(a) Buchholz (b) OSR (c) PRV (d) Water level Controls etc.Float typePressure switches.Mechanical interlocks.Pole discrepancy relay.
cdg is circular disk gear relay which is electromagnetic relay
The Buchholz relay is installed in an inclined position because of buoyancy. Slightly inclined so the gas bubbles will flow to the cover and then to the Buchholz relay and not stay in a pipe corner.
To enable any gases generated within the transformer to bubble along the pipe towards the expansion tank. The Buchholz relay itself isn't angled; it's the pipe in which its fitted.
A Buchholz relay is designed to detect a failing oil-filled power transformer. It will automatically disconnect the transformer and produce an alarm signal.
Buchholz Relay is a special type of relay and its only used in transformers, and the main use of this relay is transmission and distribution systemAnswerA Buchholz relay is used between a transformer and its expansion tank. So they are only used (1) where there is an expansion tank and, (2) in substations, where the associated protection relays can be installed.
Buchholz relays are used with oil-filled transformers, and these types of transformerare not normally hermetically sealed, because the oil must be allowed to expand and contract with changes in temperature, and must be able to displace air within the tank. Air vents are provided for any resulting air displacement, and are normally fitted with silica-gel chambers to ensure any air entering the transformer when the oil contracts is dry.Buchholz relays are normally fitted in an inclined pipe between the main tank of the transformer and an elevated expansion tank, so that any gases formed within the tank pass up that tube and are collected within the Buchholz relay's chamber. A Buchholz relay is designed to set off an alarm in the event of a loss of oil or an excessive collection of gas within the relay; a further fall in oil level, or a catastrophic explosion within the tank, will cause the Buchholz relay to disconnect the transformer.