In what context? Typically people want to know this because someone referred to a residential service as 'two phase', meaning there are two hot wires and a neutral. Technically, there is no such thing as two phase power. Commercial sites are often wired in three phase power, and residences are actually using a special type of single phase power called 'Split single phase'. This has to do with the way the voltage for the hot leads is created. Residential step-down Transformers on the ground or on poles use a transformer with a center tapped secondary, making each hot wire about 120 volts. The center tap point becomes the neutral wire. A phase to phase measurement gives you about 240 volts. This is technically created with only one phase from the power generation point, as opposed to commercial services which actually use all three phases. A phase to phase measurement in a commercial service yields 208 volts instead of 240.
AnswerA two-phase system is very rare these days, as it pre-dated three-phase systems. It consisted of a generator with two phase windings, physically displaced by an angle of 90 degrees, giving two phase voltages displaced by 90 electrical degrees. The resulting line voltage is 1.414 times the phase voltage.A two-phase system should not be confused with the split-phase system used for North American residential supplies.
In a two-phase connection, the phases are displaced by 90 degrees. Two lines (not 'phases') of a three-phase system will provide a single-phase supply, not a two-phase supply.
From one phase to the next you should see 208 Volts.From any phase to ground you should see 121 Volts.AnswerYou are very unlikely to come across a two-phase machine, as two-phase a.c. systems are archaic. A two-phase system has two phase voltages that are 90 degrees out of phase with each other, and was used many years' ago. These days, you have either single phase or three phase. So it's probably safe to say that there are no two-phase motors about, these days!
It's unlikely you have a two-phase supply. Two-phase systems (two phases, displaced by 90 electrical degrees) are very old, and there are very few two-phase systems around. Assuming you really mean 'two phase', t's unlikely, therefore, that you can use a three-phase energy meter using its standard terminals.
A two-phase system is archaic and you are unlikely to find it in use anywhere these days, so it is mainly of historical interest. A two-phase, three-wire system, consists of two phase voltages, displaced from each other by 90 electrical degrees, and a phase voltage which is 1.414 x phase voltage.A three-phase system consists of three phase voltages which are displaced from each other by 120 electrical degrees. In the case of a three-phase, three-wire, system, the line voltages are numerically equal to the phase voltages; in the case of a three-phase, four-wire, system, the line voltages are 1.732 x phase voltage.
Three phase uses a safety circuit away from the machine, two phases uses you as the safety circuit
There is no such thing as a two phase instrument. There is only single phase and three phase. You can only have: single phase/ one pole single phase/ two pole three phase/ three pole
In a two-phase connection, the phases are displaced by 90 degrees. Two lines (not 'phases') of a three-phase system will provide a single-phase supply, not a two-phase supply.
From one phase to the next you should see 208 Volts.From any phase to ground you should see 121 Volts.AnswerYou are very unlikely to come across a two-phase machine, as two-phase a.c. systems are archaic. A two-phase system has two phase voltages that are 90 degrees out of phase with each other, and was used many years' ago. These days, you have either single phase or three phase. So it's probably safe to say that there are no two-phase motors about, these days!
Most electrical equipment are either designed to work on Single phase (two wires) or Three Phase (three or four wires). Two phase equipment are non existent today. A single phase heater will require a single phase thermostat while a three phase heater will require a three phase thermostat.
A two-phase* system is archaic, and has been completely superceded by three-phase systems, so there is no demand for two-phase induction motors. (*A two-phase generator has two phase windings, displaced from each other by 90 degrees.)
In two phase locking there are two phases. The first phase is known as Expanding Phase and locks are issued in this phase. No lock is released. Then after change all changes are committed and the second phase starts that is the Shrinking Phase in which all the changes are noted and the locks are released. No locks are issued in this phase
It's unlikely you have a two-phase supply. Two-phase systems (two phases, displaced by 90 electrical degrees) are very old, and there are very few two-phase systems around. Assuming you really mean 'two phase', t's unlikely, therefore, that you can use a three-phase energy meter using its standard terminals.
If you have single phase now, you have two options. One, is to install a three phase service or Two, install a roto phase device.
If two phase voltages are the same voltage and the same phase angle, the the resultant voltage will be twice the voltage.
it is the relative velocity of two phase that is gas and liquid.
initial phase follow on phase
Initial phase and follow-on phase