Your new dryer may be tripping the breaker immediately due to an electrical issue, such as a short circuit or overload. It is recommended to have a professional electrician inspect the dryer to determine the exact cause of the problem.
If there is no room for a new 30 amp breaker, you may need to upgrade your electrical panel to accommodate the additional load. It is recommended to hire a licensed electrician to properly install the new circuit and outlet for the dryer to ensure safety and compliance with local codes.
The dryer plug is probably wired wrong, check where the cord is wired to the dryer first. Unplug the dryer befor starting to remove any screws or panels
To safely install a new wire for your electric dryer, first turn off the power to the dryer at the circuit breaker. Then, remove the old wire and install the new wire following the manufacturer's instructions. Make sure to use the correct gauge wire for your dryer and secure all connections tightly. Finally, turn the power back on and test the dryer to ensure it is working properly.
A circuit breaker will trip if it is faulty or if the connected circuit has a short circuit or a connected device is trying to draw more current than the breaker rating. If you disconnect the output wire from the breaker and it still trips, it is a faulty breaker. If the breaker is tripping immediately when it is turned on then start disconnecting elements of the circuit to see what might be causing the problem. If everything was working and now isn't, it is likely that the wire from the breaker is nicked where it exits the box and is shorting to the feedthru connector.
A circuit breaker is dual function. The only time it will trip is if it senses a fault current that is rated higher than the breaker rating (short circuit). The other trip condition is if the circuit is overloaded and is drawing a current higher than the breaker rating. On breakers that protect motor feeders the breaker has to be rated 250% higher than the motors full load amperage. If the breaker has lots of use and is used for a switch being manually turned off and on will weaken the trip value of the breaker. If you have access to, or know an electrician, a clamp on amp meter on the conductor that the breaker feeds will tell you what is happening. Clamp the line and turn on the load to see exactly what the current is. If, like you say, the breaker is properly rated and the current is within the breaker limits then change out the breaker for a new one.
You can reset a breaker. Fuses are a one time use device. Once they trip or burn out due to a short, they are no good anymore and you need to replace it with a new one.
you could have a loose connection causing it to arc enough to trip the breaker -- check all the connections -- maybe you'll need to change out the arc fault you could have a loose connection causing it to arc enough to trip the breaker -- check all the connections -- maybe you'll need to change out the arc fault
More information is needed, maybe a lot more. Depending on its size you may need a new circuit for it. If you trip the breaker then don't use it and get a new circuit installed for it on its own breaker. You are probably talking about a window unit. If it is a simple 5000 BTU unit you can probably plug it into the nearest receptacle. If you trip the breaker then you need to run a new circuit for it. If it is much larger you may need to run a new circuit. If it is a 240 volt unit then you need a new circuit.
A 32 amp fixture can not be fed from a 20 amp breaker as the breaker will trip every time.
Electric dryers typically are 220 volts and need a 30 amp, 2-pole circuit breaker. A 15 amp breaker would quickly trip if overloaded with a dryer. You may need a wiring upgrade (to 10 gauge) and a new 2-pole breaker for 30 Amps. You should also not be using two separate breakers for one 220 volt circuit; they should be either one unit or two that have their handles mechanically connected together. Hire an electrician.
Theoretically yes if you remove the two pole 50 amp breaker and replace it with a 2 pole 15 amp breaker. This has to be done because the new receptacle is only rated at 15 amps and can not be protected by a breaker any larger than 15 amps.Physically this is not going to happen due to the fact that you will not be able to connect the existing #6 conductor, which fed the 50 amp dryer receptacle, under the terminals of the new 2 pole 15 amp breaker.
It is attached to the condenser unit. You will need a hexagon wrench and pliers to remove it. Be very careful to avoid moisture exposure to the new air dryer prior to installing. Remove old dryer first and be prepared to remove new dryer from packaging and install IMMEDIATELY and protecting from any moisture.