Wiki User
∙ 2008-08-11 19:51:07Only if you want to damage it.
"277" Volt 3-phase will usually mean 277 from each phase to neutral, and 480 from phase to phase.
By "230 3-phase", you likely mean 120 phase-to-neutral, and 208 phase-to-phase.
If you really mean 230, then you are probably NOT talking about a three phase motor.
Wiki User
∙ 2008-08-11 19:51:07If they are in different rooms or side by side in the same room, and not connected together mechanically, there should not be a problem.
no. it clearly needs a 415 volt 3 phase motor.
No, the voltage difference is too much. A 570 volt motor falls in the 600 volt range which is separate from the 480 volt range of three phase systems.
You don't, single phase motors that size are wired to 240 volt circuits, to put a 10 hp single phase motor on 440 volt would require a transformer and numerous other components. Use a 3 phase motor they are significantly cheaper to purchase.
If it is a four wire (ie grounded) circuit, and the phase to neutral voltage is indeed 240 volts, then you can.
:
Yes but the connection has to be to the 480 volt windings. Applying 277 volts to the 230 volt windings will damage the motor.
It *can* be, but it won't work.
A volt can not be connected to a circuit.
Yes.
If they are in different rooms or side by side in the same room, and not connected together mechanically, there should not be a problem.
no. it clearly needs a 415 volt 3 phase motor.
Question is incorrect. in a 240 Volt single phase circuit, how can you have A phase and B phase?
The wire can be used for dc or any number of phases provided it's thick enough to take the current you need. <<>> Any two legs of a three phase system can be classed a single phase. As long as the voltage required by the load is supplied by the supply it can be connected. A perfect example of this is on a 120/208 volt supply. This is a three phase supply allowing three phase 208 volt motor to be connected to it and also by using any two legs of the supply, a single phase 208 volt motor can also be connected.
Yes, but the motor's horsepower rating will not be reached.
The voltage drop should not exceed 3% on a feeder or branch circuit.
You can not change it. 440 volt is by design. However you run it with 220 single phase supply, but it would run far lower power.