In a three phase that means there are three lines live. Lets name the first line L1, second one L2 and the last L3. If you would connet it to a three phase motor then you require L1, L2 and L3 to be connected either in star or delta connection. Rating of your motor should be 200V, 3 phase , x HP ( star or delta connected). If you have a single motor of 200V then you only need to connect two lines of the three., namely either L1 to L2 , L1 to L3 or L2 to L3.
For a 240-volt single-phase induction motor, a two-pole motor starter is typically required, as it connects to the two live conductors of the single-phase supply. For a 440-volt three-phase induction motor, a three-pole motor starter is needed, as it connects to the three phases of the three-phase supply.
Yes, if the motor is rated 240 volts 3 phase.There is such a thing as 240 volt 3 phase power.However if you are asking if you can use 240 volts single phase on a three phase motor, then the answer is no.
No, a 2 pole breaker is designed for a 240-volt circuit or for two separate 120-volt circuits that are out of phase with each other. For a 120-volt single-phase circuit, you would typically use a single-pole breaker.
If you have a 208Y/120 volt 3 phase system, you can use any one of the three phases (hot or ungrounded conductor) with the neutral for 120 volt load or you can use any two phases of the three phase for a single phase 208 volt load. If you have a 120/240 volt 3 phase system, you can use any two phases of the three phase for a single phase 240 volt load or you can use either the A phase or C phase with the neutral for a 120 volt load. You can not use the B phase with a neutral (you would have 208 Volts!).
The standard units were 220 volt, 3 phase. 220 single phase was a purchase option. There were also conversion kits to convert the machines from 3 phase to single phase. The kits contained a 1 HP 220 volt capacitor start motor and a DC motor brake control assembly. Jerry S greentron@att.net
no
All my experience with rotary phase converters have been in converting 240 volt single phase into 240 volt three phase. They all were hard wired into their respective systems, so my answer is no.
Question is incorrect. in a 240 Volt single phase circuit, how can you have A phase and B phase?
AC voltage conversions are usually done with transformers. Most commonly, a 3 phase 277/480v system is transformed to a 3 phase 120/208v system. You can, however transform to anything you like with the proper transformer. If you are trying to convert 480v single phase to 240v single phase, such as for home use, then ask for that type transformer. It would use only 2 phases of the 3 phase system. Using 2 phases is called single phase and there are reasons for this that are beyond the scope of this answer. 220v and 110v are field measurements of what is considered 240v and 120v when ordering equipment or applying code.
No you need a Roto Phase
Yes it would work pretty well but it might not meet its accuracy specification.
For a 240-volt single-phase induction motor, a two-pole motor starter is typically required, as it connects to the two live conductors of the single-phase supply. For a 440-volt three-phase induction motor, a three-pole motor starter is needed, as it connects to the three phases of the three-phase supply.
120 volt single phase rectifies to about 96 volt DC
220 volt single phase from 480 volt 3 phase that one wire taken one phase and second wire connected in earth point. we get 220 v The above answer is incorrect, one phase from a three phase 480 volt system will give you 277 volts to ground. You must use a transformer to get the voltage you need.
You can not change it. 440 volt is by design. However you run it with 220 single phase supply, but it would run far lower power.
A single phase 600 to 240 Volt transformer using two phases of the three phase primary.
You Don't. 440volt 3-phase is actually 480 volts, taking a single phase gives 277Volts single phase. To get single phase 440 you would use one leg of three phase 440/760 three phase power.