Yes, but you need a power source, for the shunt trip coil voltage, in the circuit.
There are per-engineered shunt trip solutions such as the Littelfuse LPSM that have a transformer that isolates the line voltage from the control voltage. You simply wire the N.O. contact on the float in the shunt trip isolated contacts.
I've never heard of a 50 amp b-e-a-k-e-r. You can put a 50 amp b-r- e-a-k-e-r in a 60 amp panel; but you can only have an additional 10 amp breaker along with it. You may need to consider adding another larger panel or a separate 50 amp breaker box.
Look to see if the 30 amp panel is fed with a two wire or a three wire. If it is a two wire then you are out of luck. If the panel is fed with a three wire then the panel should have the neutral terminated in the panel. It is this neutral that you need for 120 volt connections. You didn't state how many panel slots there are in the panel. If you are able install a 15 amp breaker into the panel and connect the wires going to the load. The black wire will go to the breaker and the white wire will go to the neutral bar in the panel.
Yes, you need to use a mini breaker panel with a 15A circuit breaker to safely connect a 15A receptacle to a 30A line. The breaker panel will protect the receptacle and wiring from the higher current capacity of the 30A line, preventing potential overheating or damage. It's important to match the amperage of the circuit breaker with the rating of the receptacle to ensure safe electrical operation.
Yes, but you need a power source, for the shunt trip coil voltage, in the circuit.
A shunt trip breaker is installed like any other molded case breaker. The only difference is that it has an internal tripping coil that is usually connected to a C.T. The breaker is usually mounted in a MCC cabinet The top of the breaker is bolted to the MCC bus bars and the bottom of the breaker is connected to the load. The load conductors pass through the C.T.'s which induces a current into the circuit to trip the tripping coil in the breaker.
There are per-engineered shunt trip solutions such as the Littelfuse LPSM that have a transformer that isolates the line voltage from the control voltage. You simply wire the N.O. contact on the float in the shunt trip isolated contacts.
A TEE is a transesophageal echo, which is a diagnostic test. A cardiac shunt is a separate thing altogether, as it is surgery. Perhaps they performed a TEE and as a result, felt there was a need to proceed further and explore the need for a shunt?
You would need to take the "input" wire for the shunt trip breaker to an electrical switch (not alarm initiating switch, which are DC voltage rated) within the Automan unit and connect to the "Common" connection and the "return", the wire to the actual shunt circuit of the breaker, from the "Normally Open" connection of the switch. When the unit activates, the switch will be placed into "Closed" position, therefore completing the circuit and activating the shunt coil.
To determine the compatibility of a Square D 125 amp breaker with your electrical panel, you need to check the manufacturer's specifications for your panel to see if it is rated to handle a 125 amp breaker. It is important to ensure that the breaker is compatible with the panel to avoid any safety hazards or damage to the electrical system.
I can only assume that you are attempting to connect 480VAC coil from a elevator to a fire system in order to shunt the elevator. In order to do this you will need a shunt trip breaker rated for this use.
I've never heard of a 50 amp b-e-a-k-e-r. You can put a 50 amp b-r- e-a-k-e-r in a 60 amp panel; but you can only have an additional 10 amp breaker along with it. You may need to consider adding another larger panel or a separate 50 amp breaker box.
The sub-panel need to be fed from the main panel, by way of a circuit breaker connected to one of the breaker locations. Or if your sub-panel has a main breaker installed you can feed from the main panel with a sub-feed lug kit. This looks like a breaker, but is only a point where you can branch off the sub panel.
Look to see if the 30 amp panel is fed with a two wire or a three wire. If it is a two wire then you are out of luck. If the panel is fed with a three wire then the panel should have the neutral terminated in the panel. It is this neutral that you need for 120 volt connections. You didn't state how many panel slots there are in the panel. If you are able install a 15 amp breaker into the panel and connect the wires going to the load. The black wire will go to the breaker and the white wire will go to the neutral bar in the panel.
To install a 50 amp breaker in your electrical panel, you will need to first turn off the power to the panel. Then, remove the panel cover and locate an open slot for the new breaker. Connect the hot wire to the breaker, the neutral wire to the neutral bar, and the ground wire to the ground bar. Secure the breaker in place and replace the panel cover. It is recommended to consult a licensed electrician for assistance to ensure safety and compliance with local codes.
You will need to determine the specific type of breaker required for your electrical panel based on the manufacturer's specifications and the electrical load requirements of your home. It is recommended to consult a licensed electrician for proper guidance and installation.