The 220 Volt secondary in a single phase transformer rated 2kVA, should be able to deliver about 2000/220 or 9.1 Amperes, assuming unity power factor.
To calculate the amperage in the secondary side of a transformer, you can use the formula: Amps = kVA / (Volts x Sqrt(3)). For a 250 kVA transformer with a 220-volt secondary, the amperage will be approximately 660.4 Amps.
A transformer does not use, it transforms voltage from one value to another. The output amperage is governed by the connected load. If the load wattage is higher than the wattage rating of the transformer then either the primary or secondary fuse will blow or the transformer will burn up if the fusing is of the wrong sizing. The maximum primary amperage can be found by using the following equation, Amps = Watts/Volts, A = W/E = 600/120 = 5 amps. The same equation is used for the calculating the maximum secondary amperage, A = W/E = 600/12 = 50 amps.
The number of amps a transformer can carry on its secondary side depends on its power rating (in watts or VA) and the voltage of the secondary winding. You can calculate the current (in amps) using the formula: Amps = Watts / Volts. For example, if you have a 1000 VA transformer with a 10V secondary, it can carry 100 amps (1000 VA / 10V = 100A). Always ensure the transformer is rated for the desired load to avoid overheating or damage.
Different controllers have different outputs depending on how many valves are on each zone. In the device there is a control transformer. Look for the VA output of the transformer's secondary side. Mine states 20 VA at 24 volts. To find the amperage use the following equation. I = W/V. Amps = Watts or VA/Volts. Mine can output 20 divided by 24 = .83 amps. This amperage will be the maximum output in amps that the controller can produce to operate the zone valves. To find the current draw of the primary side of the transformer divide the transformers VA by 120 volts.
To determine how many amps are in 115 volts, you need to know the power (in watts) being used. The relationship between volts, amps, and watts is given by the formula: Watts = Volts × Amps. Therefore, to find the amps, you can rearrange the formula: Amps = Watts / Volts. For example, if you have a device that uses 1150 watts, you would have 10 amps at 115 volts (1150 watts ÷ 115 volts = 10 amps).
2.083 amps
Rephrase your question, as it doesn't make any sense. If the primary side of the transformer is 480 volts 3 phase, this transformer can be supplied from a breaker as big as 180 amps. If 480 volts 3 phase is your secondary then you can supply up to 180 amps to your loads.
To calculate the amperage in the secondary side of a transformer, you can use the formula: Amps = kVA / (Volts x Sqrt(3)). For a 250 kVA transformer with a 220-volt secondary, the amperage will be approximately 660.4 Amps.
The formula you are looking for is I = W/E. Amps = Watts/Volts.
A transformer does not use, it transforms voltage from one value to another. The output amperage is governed by the connected load. If the load wattage is higher than the wattage rating of the transformer then either the primary or secondary fuse will blow or the transformer will burn up if the fusing is of the wrong sizing. The maximum primary amperage can be found by using the following equation, Amps = Watts/Volts, A = W/E = 600/120 = 5 amps. The same equation is used for the calculating the maximum secondary amperage, A = W/E = 600/12 = 50 amps.
160 amps at 12v.
160 amps at 12v.
Ohm's law: Volts = Amps * Ohms, or Amps = Volts / Ohms 12 volts / 0.5 ohms = 24 amps
480 volts is probably 3-phase (Line to line) voltage, so: 1500K / (480 x 1.732) = I = 1804Amps
4 volts and how many amps? Watts = amps x volts. It depends on the amount of current (in Amps) flowing at 4 Volts... See Ohms Law: Watts = Volts x Amps If you have 2 Amps flowing at 4 Volts you are dissipating/consuming 8 Watts. If you have 10 Amps flowing at 4 Volts you are dissipating/consuming 40 Watts.
Different controllers have different outputs depending on how many valves are on each zone. In the device there is a control transformer. Look for the VA output of the transformer's secondary side. Mine states 20 VA at 24 volts. To find the amperage use the following equation. I = W/V. Amps = Watts or VA/Volts. Mine can output 20 divided by 24 = .83 amps. This amperage will be the maximum output in amps that the controller can produce to operate the zone valves. To find the current draw of the primary side of the transformer divide the transformers VA by 120 volts.
The formula to calculate the relationship between amps, volts and watts is Volts X Amps = Watts or Volts = Watts / Amps or Amps = Watts / Volts therefore; 200 Watts divided by 1.95 Amps is 102.5641 Volts.