It depends on the current, not the power. There is insufficient information in the question to answer it. Please restate the question.
To determine the KVA needed for a 200A panel, you can use the formula KVA = (Voltage x Amperage)/1000. Assuming a standard voltage of 120V, the KVA would be 24 KVA (120V x 200A / 1000 = 24 KVA).
Yes, 2.8 kVA is equal to 2800 watts. This is because 1 kVA is equivalent to 1000 watts, so 2.8 kVA would be 2800 watts.
12HP is approximately 10.8 KVA. You would want to use a 15KVA transformer to supply this motor. KW = HP * .75 KVA = KW * 1.2 (These formulas are approximate)
To convert amps to kVA, you use the following formula: Amps = (kVA x 1000 / voltage) / 1.73
To convert 2 kW to kVA in single phase, you need to know the power factor. If we assume a power factor of 0.8 (common for many single-phase loads), the conversion formula is kVA = kW / power factor. Therefore, for 2 kW at a power factor of 0.8, the result would be 2 kVA / 0.8 = 2.5 kVA.
35 KVA generator using for load 100 meter length which cable need to used
To answer this question the voltage of the genset is needed.
16mm2
It depends totally on the voltage used.
A 10 mm cable is most commonly used for a 500 KVA transformer, 240 volt, 3 phrase. The size of the wire that is used in a transformer is based on the voltage.
250 kVA generators come in different voltage settings and this information is needed before a wire size can be given
4core*240mm square..
3r x 300sq.mm Al. ar UG cable <<>> Wiring is sized by the amperage that is used by the load. The formula for amps is I = W/E. Amps = Watts (or VA)/Volts. As you can see an answer can not be given unless a voltage is stated. The lower the primary voltage the larger the amperage will be and likewise the larger the wire size will be.
Yes, a 3 phase 95 millimeter for each phase 150 meters long cable is enough for a 285 KVA genset.
How to compute for the size of wire in the primary side of 2500 kVA transformer 34.5kV
The motor would draw about 24 kVA which is 35 amps. For this you would need 10 mm2 cable.
The capacitor size for a 5 kVA generator typically depends on the power factor and the specific application. A general rule of thumb is to use about 0.5 to 1 microfarad (μF) of capacitance per kVA for power factor correction. Therefore, for a 5 kVA generator, you might consider a capacitor size ranging from 2.5 μF to 5 μF. However, it's essential to consult with a professional or refer to the generator's specifications for precise requirements.