You need 10-3 PLUS ground for this 220v application. The ground is the only uninsulated wire. If you did it with 10-2, I would suggest re-doing it correctly ASAP. That leaves you without a neutral and potential for supply to go through grounding wire to breaker box (or through a person to ground, causing electrocution).

Clarification: you do not need three current-carrying conductors for all 220 v applications. There is no neutral in 220, so you only need two "hot" leads and a bare safety grounding wire. If the appliance (as here, a dryer) actually needs 110 in addition to 220, then yes, you need 10/3 cable, plus grounding wire.

First of all the word "shield" in electricity refers to blocking magnetic flux. What you meant to say is "insulated" which means to block conductivity. When #?-2 NM w/ Ground wire is used in a 240 volt circiut, there is no neutral conductor. You're connecting the black and white wires hot and the bare wire as equipment ground in the distribution panel. On the dryer a 3 wire cord is connected with the neutral and ground terminals jumpered, so that the ground wire ran to the dryer serves as both ground and neutral. This is how dryers have been wired for many years in most of North America. Electrically this works because ground and neutral have the same electrical potential. Technically, however, it's wrong because a ground wire shouldn't be used as a normally current carrying conductor, and in the case of a dryer, the motor and control circuits are 120 volt, causing a small current flow in the ground conductor with a 3 wire supply.

The real question is: Does a residential dryer require a separate neutral conductor or just a ground conductor? The same question asked differently does a residential dryer require a #10-2 or #10-3 supply cable?

The answer is: If this is an existing dryer supply, a #10-2 cable with a 3 prong cord will work just as well as it has for decades, but if this is a new installation, a #10-3 cable and a 4 prong cord is required to abide with current laws.

User Avatar

Wiki User

12y ago

What else can I help you with?

Continue Learning about Natural Sciences

How do you put on a four prong outlet on a roper electric dryer?

Black & Red are hot, and White is neutral. If it has no place to connect neutral connect neutral to ground.


Why 4 wires for dryer?

A dryer needs four wires for proper operation and safety because it requires two hot wires, one neutral wire, and one ground wire. The ground wire helps protect against electrical shocks and ensures proper functioning of the appliance. It is a standard requirement to have all four wires for dryer installations to meet safety regulations.


Can groundwire be together with neutral wire at the dyer?

Ground and neutral should only be connected at the main electric panel to prevent parallel neutral currents. If it is a new installation, you must provide four wires (two hots, 1 neutral, & 1 ground) and connect to the four separate (appropriate) places on the dryer. If it is an existing installation and it only has three wires (two hots and a neutral) connect the neutral to both the neutral and ground connection of the dryer (the National Electrical Code allows this exception for older homes). Call a qualified electrician to do any electrical work.


What are the NEC requirements if a laundry circuit is to be installed in a basement of a dwelling for a washing machine and the dryer will be connected to a 30A dryer receptacle?

== == The washing machine outlet should be ground fault protected on 12-2 wire. The 30 amp dryer circuit should be on 10-3 wire with a ground. Laundry receptacle outlet for washer, 12/2 with ground yes! GFCI required if receptacle is within 6 feet of sink or duplex receptacle rather than single receptacle [but a GFCI isn't a bad idea anyway...Dryer, 10/3 with ground and 4-wire outlet and cord set connection at dryer location! NO NEUTRAL BONDING LINK!1) NEC requires a disconnecting means [plug and receptacle works] if equipment [dryer] is not within sight of the power source [in this case, if the panel is in the garage]2) You were never allowed to use the ground wire to carry neutral current, so you need an insulated white or grey neutral [this means three wire]3] You are not longer allowed to use the neutral jumper at the terminal in the dryer for a chassis ground [with certain limited exceptions - existing ungrounded three wire cable and new dryer] Ground wire goes to chassis. As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


What is the difference between a 4 prong dryer outlet and a 4 prong stove outlet?

The four blade dryer plug brings a separate ground wire from the machine to the electrical grounding system. The three blade dryer plug depended on the neutral wire of the plug to make this connection.

Related Questions

Can you install a dryer outlet using the bare copper as a neutral wire in an older house?

Technically, yes you can. However, this is one of the most dangerous things you can do in electrical wiring. It's not only against the code, it's a fire waiting to happen. Don't do it! Understand, the neutral wire is a conductor. It carries current. It needs to be an insulated wire. Also, if you use the bare copper (ground) wire for a neutral, you have taken away the earth ground from the circuit, eliminating short circuit protection. If the dryer motor shorts out it will burn up. (fire again) A residential dryer requires a 30 amp 220 volt circuit breaker in your panel and a # 10 gauge wire with three conductors (insulated) and a bare ground. Have a qualified electrician install it.


How can I convert a 4-wire dryer to a 3-wire dryer?

To convert a 4-wire dryer to a 3-wire dryer, you will need to remove the neutral wire and connect the ground wire to the neutral terminal. Make sure to follow safety guidelines and consult a professional if needed.


How do you put on a four prong outlet on a roper electric dryer?

Black & Red are hot, and White is neutral. If it has no place to connect neutral connect neutral to ground.


Why 4 wires for dryer?

A dryer needs four wires for proper operation and safety because it requires two hot wires, one neutral wire, and one ground wire. The ground wire helps protect against electrical shocks and ensures proper functioning of the appliance. It is a standard requirement to have all four wires for dryer installations to meet safety regulations.


Can you plug your washer and dryer into the same socket?

No. They are two different voltage and amperage rated pieces of equipment. Also, a dryer does not use a common (neutral) wire. It uses two separate 110 volt legs, and a ground. The washer uses only one 110 volt leg, a neutral, and a ground.


Can groundwire be together with neutral wire at the dyer?

Ground and neutral should only be connected at the main electric panel to prevent parallel neutral currents. If it is a new installation, you must provide four wires (two hots, 1 neutral, & 1 ground) and connect to the four separate (appropriate) places on the dryer. If it is an existing installation and it only has three wires (two hots and a neutral) connect the neutral to both the neutral and ground connection of the dryer (the National Electrical Code allows this exception for older homes). Call a qualified electrician to do any electrical work.


How can I change a dryer cord from 4 to 3 wires?

To change a dryer cord from 4 wires to 3 wires, you will need to remove the neutral wire and connect the ground wire to the neutral terminal on the dryer. Make sure to follow the manufacturer's instructions and turn off the power before making any changes.


Is a ground fault protection for equipment required even if the neutral will not be used?

Yes, ground fault protection for equipment is requiredeven if the neutral will not be used.However, the question implies that it might not be required if there is a neutral. That is not true. With two exceptions, ground fault protection is always required in the US, and it is probably required in other countries as well.The exceptions are the use of an electric cooking range, and an electric clothes dryer. In those cases, the US NEC allows the neutral conductor to also be the ground fault conductor, except for the case where the range or dryer is in a mobile home. In the case of the mobile home, the ground fault conductor and the neutral conductor must be maintained separate and distinct all the way back to the distribution panel.In every other case, including where local code overrides the US NEC's exceptions, it must be understood that ground fault protection (protective earth ground) is not the same as neutral, even though the neutral conductor is grounded.


Does a 4 wire plug for a dryer can be replaced with a 3 wire plug?

The fourth prong is a ground for the body of the dryer. The dryer will work fine with the 3 main ones. Building code requires the four wire plug now, but you can change it and the dryer will work. If you have a 4 plug outlet and a 3 wire cord, you can just change the cord and not use the second ground or connect to the the frame of the dryer.


How to hook up a 3 prong dryer cord correctly?

To hook up a 3 prong dryer cord correctly, first make sure the dryer is unplugged. Then, connect the neutral wire to the center terminal, the hot wire to the left terminal, and the ground wire to the right terminal. Tighten the screws securely and plug in the dryer to test it.


What do the letters stand for on a 4 prong plug?

On a 240 volt outlet, such as a dryer outlet: G is Ground, W is Neutral, X and Y are the two Hot legs.


What are the NEC requirements if a laundry circuit is to be installed in a basement of a dwelling for a washing machine and the dryer will be connected to a 30A dryer receptacle?

== == The washing machine outlet should be ground fault protected on 12-2 wire. The 30 amp dryer circuit should be on 10-3 wire with a ground. Laundry receptacle outlet for washer, 12/2 with ground yes! GFCI required if receptacle is within 6 feet of sink or duplex receptacle rather than single receptacle [but a GFCI isn't a bad idea anyway...Dryer, 10/3 with ground and 4-wire outlet and cord set connection at dryer location! NO NEUTRAL BONDING LINK!1) NEC requires a disconnecting means [plug and receptacle works] if equipment [dryer] is not within sight of the power source [in this case, if the panel is in the garage]2) You were never allowed to use the ground wire to carry neutral current, so you need an insulated white or grey neutral [this means three wire]3] You are not longer allowed to use the neutral jumper at the terminal in the dryer for a chassis ground [with certain limited exceptions - existing ungrounded three wire cable and new dryer] Ground wire goes to chassis. As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.