Why does an ac contactor need shading rings?

In a AC contactor, a shaded ring is essential to prevent it from buzzing twice a cycle. Ac contactor takes a input of alternating voltage resulting an alternating current and flux through its windings. So The contactor buzzes each time the magnitude of alternating magnetic field reaches zero. The shaded rings are provided at some part of the core. When the alternating flux cuts them the produce another alternating magnetic field which is out of phase from the main magnetic field. So the resultant magnetic field no more zero at the contacts and which prevents the contact from buzzing.


What is the definition for Magnetic Domain?

A magnetic domain is a region within a material where the magnetic moments of atoms are aligned in the same direction. These domains can change size, shape, and orientation in response to external magnetic fields.


Why is the compressor contactor not sticking in?

A contactor not being energized or closed can be caused by a host of reasons . A shorted or open contactor coil. No control voltage or incorrect voltage present to energize the contactor coil , A safety device opening or breaking the control circuit . A loose or broken control devise or control wire . and possibly more , depending on your a/c units control wiring configuration. Tom H, HVAC proffesional. New Orleans .


In terms of the scientific definition of work magnetic an electric fields can do work?

In the scientific definition of work, magnetic and electric fields can do work on charged particles that are moving through them. The work done is based on the force exerted by the field on the particle and the distance over which the particle is displaced.


What does unmagnetised mean?

"Unmagnetized" refers to a material that does not have a magnetic field or is not magnetized. This means that the material does not exhibit magnetic properties such as attracting or repelling other materials.

Related Questions

What is a magnetic contactor protection device?

Contactors have both power and auxiliary contacts. We use the auxiliary contact to control magnetic system of contactor. When a heater , relay or a key warn the contactor it is energized and by the typical magnetic interaction it opens its closed power contacts.


What are the parts of magnetic contactor?

There are three main parts of a magnetic contactor. These include the power contacts, contact springs, and the auxiliary contacts.


How does magnetic contactor operate?

explain me about the contactor works with examples. if i want to control a motor with contactor. and how i can use contactor in loops with over load and circuit breakers.


Why does an ac contactor need shading rings?

In a AC contactor, a shaded ring is essential to prevent it from buzzing twice a cycle. Ac contactor takes a input of alternating voltage resulting an alternating current and flux through its windings. So The contactor buzzes each time the magnitude of alternating magnetic field reaches zero. The shaded rings are provided at some part of the core. When the alternating flux cuts them the produce another alternating magnetic field which is out of phase from the main magnetic field. So the resultant magnetic field no more zero at the contacts and which prevents the contact from buzzing.


What can you do to provide separate electricity to your shared well?

You can build a control panel that utilizes a reversing magnetic contactor set up. These types of magnetic contactor have a mechanical interlock along with a electrical interlock. Have your separate feed from each house terminate on the top of each magnetic contactor. House one to contactor one, house two to contactor two. Parallel the feeds from the bottom of both contactors to the pump load. Depending on which house calls for water first that contactor will pull in and lock the other one out. Once the pressure tank demand for that house drops out the other contactor will pull in and fill that pressure tank.


Definition of coil in contactor?

The coil in a "Contactor" is essentially an electromagnetic coil that provides the driving force to close the contacts in a Contactor. When the "Coil" is energized by a lower control voltage usually from some type of controller such as a PLC, the Normally-Open contactor will close or in the oposite case, the Normally-Closed contactor will open.


Wiering diagram for contactor?

the uglys book is a good reference ,call the manufacture or go on line to find a manual


What is the function of an electrical coil in a basic circuit?

There are a couple of examples that come to mind where there is a coil in a circuit. One is, the coil is used as a choke to block harmonics from going down the electrical line. Another example of a coil in the line is the coil in a magnetic contactor. When this coil is energized the contacts of the magnetic contactor close.


Shading ring in magnet of electrical contactor?

Best guess? A shading ring aborbs energy from a changing magnetic field, so I'm guessing it will slow the opening and/or closing time. Try a web search: electrical contactor shading ring


What do you use magnetic for today?

well you use a magnet to lots of things... from handbags to compasses!!unistation 360 plz like


What is the Difference between a magnetic starter And a contactor?

Motor starter usually refers to the complete assembly, including enclosure, contactor, control transformer (if any), overloads, fuses (if any), etc. A contactor is really just an overgrown relay, and is just one component of a starter. That having been said, many folks use the two terms somewhat interchangably. So someone who says starter may mean contactor, and vise-versa. Go figure.


Can a 3 phase contactor be wired for single phase?

Yes, L1 of the single phase supply is terminated under terminal L1 of the three phase contactor. L2 of the single phase supply is terminated under terminal L2 of the three phase contactor. A conductor from output terminal T2 is then taken to input terminal L3. The single phase load is then connected to the contactor's output terminals T1 and T3. This incorporates all three of the overload blocks on the contactor into the control circuit. With the overloads in the control circuit, if an overload occurs the magnetic contactor's holding coil will drop out and take the load off line.