What is Average KWH per square foot residential consumption?
I'm finding that here in Southeast Virginia. My 1200 square foot home on average uses a little over 1200 kWh per month. That's with a wife and kid at home 24/7. The previous year they were only home for a few months and the average that year was about 1000 kWh. So I think the average could possibly be about the same as your square footage. Would also depend on climates, R-values, habits. We're fairly conservative.
What is the voltage between each lead of a 480 volt three phase delta secondary?
A 480 v three-phase system has 480 v between live lines and 277 v from each line to the neutral. This type of supply is common in North America for supplying for example small factories that need more power than a 120/208 v three-phase system can supply.
What is another name for a series -parallel circuit?
series other name current series and parallel is voltage
When conectring a step down transformer what is H1?
The H1 and H2 symbols on a transformer designates the two coil ends of the primary winding on a transformer. The symbol is the same regardless if the transformer is step up or down.
AnswerIn North America, a transformer's high-voltage windings are identified by the letter H, and the low-voltage windings by the letter X. The 'start' of a winding is allocated an odd number, and the 'finish' of a winding is allocated an even number. For example, H1-H2 represent the start and finish terminals of a high-voltage winding, and X1 - X2 represent the start and finish terminals of a low-voltage winding.
For a distribution step-down transformer, with the low-voltage terminals facing you and the high-voltage terminals on the far side of the transformer, terminal H1 is, by convention, alwayson the left-hand side of the transformer.
When terminal H1 'goes positive' (i.e. is subjected to the positive half-cycle of the AC waveform), X1 also 'goes positive'.
The identification of a transformer's terminals is important in order to determine the polarity of a transformer. Knowing a transformer's polarity is essential if two transformers are to be connected in parallel with each other.
How do you calculate the output voltage of a transformer if kva rating is known?
You can't determine the output voltage of a transformer by knowing kva. Transformers will be marked as to input and output voltages. Some will have multiple input and output voltages. The output voltage depends on the ratio of coil turns between input and output.
Why does the terminal voltage decreases as the load current increases?
A: That will happen anytime the voltage source is not able to provide the power needed for the load. If the load exceed the power available from the source the voltage will be reduced as IR drop from the source
What is the effect of the op amp in the circuit?
So long as you remain with the range of the device (power supply rails less a volt or two), the output of an op-amp will go to what ever value is required to maintain the input stages (bridge) to remain the same. So, the effect on input voltage on output of an op-amp is dependent on the feedback circuit.
How do you calculate KW from Volts?
Kw can be calculated from volts be using the formula
p=(voltage)square/resistance*1000
Does carbon have a nearly zero temperature coefficient of resistance?
Yes, carbon has a negative temperature coefficient. -0.5*10^3/C
Why permanent magnet moving coil instrument works only in dc?
A1: For ac(let fre. of 50 hz) changes its direction 100 times a second...(50 times -ive and 50 times +ive) giving no significant movement
A2: What is meant by this question? What moving coil are you referring to? Many AC motors have two coils of wire, and one definitely moves.
Why was 120V chosen as the standard voltage of homes in the US and not some other voltage?
The reason that 120v service was chosen, was economic. Originally electricity was delivered to homes, and most businesses, for a single purpose and that was lighting. Can openers, TVs, washers, dryers, electrical factory machinery, etc. came later. At the time the most cost effective form of light bulb was a carbon filament bulb that operated best (optimally) at 100v to 110v. This, adjusted for transmission voltage drop, set most supply lines at 120v.
Supplemental and Related Information:
By the time cost effective, and higher voltage, metal filament bulbs were brought to the market, most of the cities in the USA were already running 120v supply lines. Europe was just starting such systems and opted for higher voltage supply lines.
Higher voltages are used for long distance transmission and power distribution because more power can be transferred over the same size wire at a higher voltage (lower current). Power generation plants often use voltages in the hundreds of thousands, 115,000 to 165,000 of volts to move power over long distances. For lines of up to 20 miles long around a city, 2400 volts works well to reduce the voltage loss in the wires.
In North America, the electrical power lines going to residential streets and roads are operated at a primary voltage of 7200 volts. This voltage (12500/1.73 = 7225) is one leg from a three phase 12500 volt primary line. On the secondary of the transformers it is center tapped to provide 120 volts from each 240-volt leg to the center point. The center point is electrically neutral. The actual measured voltage in your house receptacle circuits will normally be 110 to 120 volts. All appliances are rated for the minimum operating voltage (110-115). This is the cause of confusion about the actual level of the supply voltages.
Different nominal voltage level and frequency standards are used in different countries. Europeans - and many other countries around the world - use 50 Hz (cycles per second) as the alternating frequency, not 60Hz as is used in North America and, again, many other countries around the world. The reason to use a higher voltage is that it is more economical because the current is less, so the wires can be smaller. On the other hand, the reason to use lower voltage in homes is safety: the lower the voltage, the safer it is.
If you have 10 amps drawing on one leg of your 240/120 service, and 10 amps on the other leg, the I2R losses are one fourth what they would be if you had 20 amps on just the one leg.
The Europeans use 415/240 (415/1.73 = 240), so their I2R losses are 1/16th of our 120 volt losses, with 20 amps drawing on just one leg.
480 V center tapped (split phase) is used in the UK only rarely, typically in rural areas to supply an isolated small group of houses that can be fed off a single phase overhead spur. Most houses and small businesses are supplied with 240 V single phase taken from a 415 V three phase local system, fed from a transformer of up to 700 KVA connected to the 11 kV distribution system. The voltage is mostly 240 V but is nominally described as 230 V with a suitably wide tolerance, to comply with European standards.
Originally, the service voltage was about 90 volts direct current, which was Edison's plan. Tesla proposed that the electrical grid be alternating current (AC) and competed with Edison for the first generating plant to be built in the State of New York at Niagara Falls. Edison proposed a DC system and Tesla an AC system. History tells us that Tesla won the competition, and because of that the industrial revolution was quickly accelerated. Had Edison won we would probably still be in the dark ages because of the inefficiency of transmitting DC current over long distances. While Edison was promoting the electrical light bulb around the country, almost every town required its own generating station because DC would lose so much in the transmission that it became unusable after only a couple of miles.
Tesla also had invented the poly phase alternating current generators that provided for the ability to generate the voltages necessary for long distance transmission. Tesla kept the voltage about the same as what Edison started but raised it to the 110 volts alternating current (VAC) because of the higher related voltages of 220 VAC and 440 VAC, which were integral to the more efficient poly phase generators.
The standard voltage available in most parts of the country (US) is now nominally 120 VAC volts +/- 10%, and can vary from 108 VAC to 132 VAC. It's usually around 117-118 VAC.
Transmission distances, the actual power needed in a neighborhood, cost, efficiency and safety issues dictate service parameters. Common distribution voltages run up to 16,000 volts. 12,000 is very common but there is still a lot of activity adding on to legacy distribution grids at lower voltages. A 2400 volt primary is very low for a distribution transformer.
In actuality power transmission is over many miles and the transmission voltage is more then 110kV. In fact interstate transmission is in the range of close to 500kV. At a substation it is reduced to 16kV for local area distribution. Transmission for the whole of the grid in North America is all tied together . Why? For economy and reliability. For example in the Summer some states do not use air conditioning but in Las Vegas, Nevada they do, so they actually buy the power from Canada in the summer because it is cost effective and reduces the need for more generation plants. Even then reserve spin power must be sustained for peak demands. Because power plants cannot produce near instant acceleration to meet new demands. In many cities and other peak demand areas, specialist peakers work to ensure that the the integrity of the grid is always maintained. 240 v is standard for the USA but only one phase is used and the transformer center tap is grounded, making it safer. Also, the main frequency of 60 Hz produced by power generation is not as stable as some people think. It varies throughout the day as loading changes but the controllers must legally ensure that it averages 60Hz over a complete day so that electric clocks using synchronous motors remain accurate.
Is lightning AC or DC voltage?
Lightning is static electricity. It's a buildup of charge, and it is facilitated by charge separation. In that light, it is DC.
If why are there transformers that step up the voltage exiting power plants?
Transmission lines have resistance. Higher voltage can "push" more current through them, thus delivering more power to the consumer.
Another AnswerThe power supplied (i.e. the rate at which energy is supplied) by an electricity transmission line is determined by the load NOT, as insinuated by the original answer, by the supply.
For a given load, the greater the supply voltage, the LOWER the resulting load current. So transformers are used at power stations to increase the transmission voltage in order to MINIMISE the current (not to 'push more current through'!).
Electricity transmission is only possible because of high voltages causing a reduction in the load current, because, otherwise, the resulting voltage drop in the line would be far too great to supply distant loads.
WebRep
currentVote
noRating
noWeight
Why induction motor current increase when load increase?
The slip is proportional to the load torque in an induction motor. This can also be seen as a reduction in speed causing extra current to be induced in the rotor to supply the increased torque.
Which metal has the highest conductivity?
At room temperature, silver has the highest electrical and thermal conductivity of all the (known) metals. Note that diamond, an allotrope of carbon, is a poor electrical conductor but is several times better as a thermal conductor than silver. Carbon is a nonmetal, of course, but it was worth mentioning as both a comparison and a curiousity.
How are the dry cells connected in series connection?
The voltage will be double that of one dry cell. The current will be that of one dry cell.
How works oil circuit breakers?
A circuit breaker is a safety device that is put in an electrical circuit. When something fails, or shorts out, the circuit breaker "senses" the excessive current and automatically opens (or breaks) the circuit.
They are used in homes, as well as some electrical devices. They are different than a fuse in that a circuit breaker can be reset. A fuse on the other hand, has to be replaced once it opens up.
I hope this helps you. for more info, here is a web page about circuit breakers:
<a href="http://www.wisegeek.com/what-is-a-circuit-breaker.htm">Ciruit breakers</a>
How can I convert A.C supply into D.C. supply?
Just buy a DC power supply that has the input supplied by 120 VAC and a DC output with required voltage and amperage.
A rectifier is an electrical device that converts alternating current (AC), which periodically reverses direction, to direct current (DC), which is in only one direction, a process known as rectification. Rectifiers have many uses including as components of power supplies and as detectors of radio signals. Rectifiers may be made of solid state diodes, vacuum tube diodes, mercury arc valves, and other components.
What is the voltage of a cell measuring?
They need to use- well the best thing/object/equipment for them to use is a voltmeter!
What is the kv phase to phase for 13.8kv?
There is no such thing as a 'phase-to-phase' voltage; the correct term is 'line-to-line' voltage. Whenever you mention a value of voltage for a three phase system, it is considered to be a line-to-line voltage unless it is stated clearly that this is phase voltage (line to neutral) voltage.
(The reason that there is no such thing as a 'phase-to-phase' voltage is because phases exist between, or 'across', line conductors or between a line conductor and a neutral.) That is a world wide practice for electrical power engineers.
Switch that regularly reverses the current in some motors?
A switch that reverses the direction of the current in a motor is called a forward reverse drum switch. It is a single phase motor that turns from clockwise to counter clockwise.
How do you reduce the copper losses in transmission lines?
Using larger amounts of copper will decrease copper loss (use bigger wire than necessary).
Which winding is characterized by a large number of turns of thin wire?
shunt field winding are made with many turn of small wire.
What is the medium voltage of circuit breaker?
low is below 600V
medium 600 to 2500V
High above 2500V
usually medium and high voltage equipment is called switchgear
the current is monitored and 3 shorts within 10 minutes will open the switch
overloads are usually 200% for over 20 minutes
but the big stuff is programable
Why do we use star to star connection in motor?
In a high voltage installation, with the same power, current drawn is small compared to those in low voltage. However it requires a thicker insulation, thus cost of insulation is significant compared to the conductor cost.
By using a star connected winding, the insulation voltage required is equal to line to neutral connection, otherwise if it is connected in delta the insulation rating has to be provided for a line to line connection.
Despite having a higher current, the total cost is still lower compared to using a higher insulation rating.