The pilot light on a Teledyne Laars furnace is typically located near the burner assembly, often at the bottom of the unit. To access it, you may need to remove a protective cover or panel. Once located, the pilot light can usually be lit using a match or lighter after turning the gas control valve to the "pilot" position. Always refer to the specific model’s manual for detailed instructions and safety precautions.
To light the pilot on a Teledyne Laars model, first ensure the gas supply is turned on. Locate the pilot light assembly, then turn the gas control knob to the "Pilot" position. Press and hold the knob while using a long lighter or match to ignite the pilot flame. Once the pilot is lit, continue holding the knob for about 30 seconds before releasing it; the pilot should stay lit.
Possible reasons why a Teledyne Laars Phase 2 pool heater may not ignite include issues with the pilot light, gas supply, or faulty igniter. Check if the pilot light is lit, ensure there is proper gas supply to the heater, and inspect the igniter for any signs of damage or malfunction. Additionally, check for any error codes on the heater display panel that may provide further information on the issue.
Check that you are getting voltage from the thermocouple. You should see about 600 millivolts.
How do I light pilot light on furnace
I was told by Teledyne Laars that your pilot generator needs to produce at least 500mv to open the gas valve. Mine makes 350mv and will not open the valve. Hmm, I think that should be nearer to 600 mv - 700 mv.
Have you rotated the gas valve knob to "run". Have you turned up the thermostat? Is the pump running? No pump water flow - no heat -- no filtration. Is the filter clean? When was the last time you cleaned the filter? Ken
sit on it then throw it into a creepy cave
A Teledyne gas furnace pilot light may go out due to several reasons, including a draft or airflow issue that disrupts the flame, a faulty thermocouple that fails to keep the gas valve open, or dirt and debris obstructing the pilot orifice. Additionally, a malfunctioning gas supply or low gas pressure can also cause the pilot light to extinguish. Regular maintenance and inspection can help identify and address these issues.
The furnace pilot light may not light up due to issues with the gas supply, a faulty thermocouple, a dirty pilot light, or a malfunctioning ignition system. It is important to troubleshoot and address these potential issues to get the pilot light to light up and the furnace to function properly.
It could be it. The pilot generator may be weak. The Valve could be defective. The High limit or other safties could also be defective. Could be corrosion on the connection. could be a water flow broblem. could be a weak flame
Not all furnaces have pilot lights. Modern furnaces often use electronic ignition systems instead. Check your furnace's manual or contact a professional to determine if your furnace has a pilot light.
At pilot light, pilot light flows around thermocouple.