Yes, as long as you use only one phase of the 3 phase system. If R & Y gives 460 volts, use R & Y. This not a good approach though.
It will not work at all.
The the supply stays within +/- 5% of what the motor is rated for, you can do this.
My first thought is this is probably a corner grounded delta system, but I'm confused by your voltages. If this was a 460v (L-L voltage) ungrounded or corner grounded system, the phase to ground voltage is meaningless, but the phase to phas voltage will be 460v all around the delta. If you have a 460v system and you're only seeing 230v, there's something wrong.
You can use a voltage converter to step down the 460V 3 phase motor to match the 380V 50Hz supply. Make sure the converter can handle the motor's current requirements. It's also advisable to consult with an electrician to ensure safe and proper installation.
Wiring a 9-lead motor for 460V operation involves configuring the motor leads according to the desired connection type, typically either wye (Y) or delta (Δ). For 460V, you would typically connect the leads in a delta configuration, where each of the three phases connects to two of the motor's leads. Ensure that the motor's voltage rating matches the supply voltage, and always follow the manufacturer's wiring diagram for specific lead connections. Additionally, ensure proper safety protocols are followed when working with high voltage systems.
yes can run but motor only delivers 90%rated power because v/f less by 10%
First of all, a 150 HP 460V 3-phase motor only draws around 170A, so two of them would only draw 340A, not 800. 340A at 460V equals almost 300,000 watts (or 300kw), and the generator would need to be sized a little bigger than this to start such big motors.
No, connecting a 460V machine to a 550V power supply is not advisable, as the higher voltage can damage the machine and create safety hazards. Most equipment is designed to operate within a specific voltage range, and exceeding that can lead to overheating, insulation failure, or permanent damage. It's essential to use power supplies that match the voltage requirements of the equipment to ensure safe and reliable operation. Always consult the manufacturer's specifications before making any connections.
For the same power - Watts - you need to run twice as many amps at 220V than at 440V. For the same load, it'll pull half the amps at 220V than it did on 440V
It would make no sense even if you could find a DC-AC inverter with an input voltage of 720V. The efficiency would be horrible and the bulk of the equipment would be impractical. The voltage your motor expects is 460 VRMS. This translates to a peak voltage of 650V (1300V peak-to-peak). Your battery pack, switched through an H-bridge of IGBT's using a PWM scheme could directly feed the motor. This is the best method available, but the design would not be trivial. Possibly, you could ditch the DC-AC inverter and use just a 460V variable-speed drive with 460V input and 460V output. Bypass the input rectifiers on the drive and use your batteries DC output directly to power it. It's a possibility anyway. You realize, of course, that you are dealing with voltage and power levels that can be fatal, right? Be careful.