Get an electrician to wire you up a 220v line.
Yes, with a caveat. The current ratings must be the same, and the the 110V outlet must be a dedicated circuit, i.e. nothing else on that breaker. You can safely upgrade a dedicated 110V 15A circuit to a 220V 15A circuit by re-using the same wiring. You will have to just replace the breaker and the outlet. You cannot, however, increase the current load or have a 110/220V (4-prong) outlet. Note that if you move a non-dedicated circuit up to 220 you will start a fire.
<><><>
As the existing wire size is sufficient to handle 220 volts you can use it to carry 110 volts. You will need to change the receptacle and also change from a double pole breaker to a single pole breaker at the fuse panel. Unless you know what you are doing, I would suggest you hire an electrician. A very simple job that should not be too expensive.
<><><>
I would do nothing more than trip the breaker at the fuse panel. Out of sight out of mind.
[That is not good practice! Why not provide a properly connected and protected 120 volt socket outlet near to the gas stove?]
<><><>
You'll want to perform what is known as a "burial".
Carefully remove the wires from the main service panel and tuck them away OUTSIDE the panel. Before tucking them away snip off the bare ends, put on a wire-nut, and wrap it with electrical tape. At the kitchen outlet, snip off the bare ends and put wirenut on and tape. But leave everything INSIDE the junction box.
This method allows for the unit to be hooked back up if need be.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
=== === Assuming you want to plug in say a 120V washer next to the 240V dryer, you would need to install a separate 120V 20A circuit. This is not a simple task and can kill you in several ways if you get it wrong. Please have a qualified electrician do it, if you do not understand the following discussion completely, or otherwise doubt your abilities. <><><> Any new outlet must be of a type protected by a GFCI or be wired into a GFCI-protected circuit if it is within an unfinished basement, bathroom, garage or any room that has wet or damp areas. The US National Electrical Code requires that a laundry outlet have its own separate circuit. If the laundry circuit in a garage or basement is used only for an appliance that is not easily moved (washing machine, freezer), it need not be GFCI protected, but only if there are other reachable GFCI outlets in the same room. You will need to add a 120 V 20A breaker to the breaker box (or sub-panel, if you have one with adequate feeders), run a separate 20A cable to a separate junction/work box near the 240 V outlet, and install the 120 V outlet. You are not allowed to just run a cord to your laundry from another outlet on a circuit used for other things, nor to connect the new outlet to an existing outlet. You may, however, extend an existing circuit to yet another outlet in the laundry area for purpose of ironing, fan, or other small appliances. If you plug an iron into the laundry outlet while the washer is going, you're likely to overload the 20A breaker. Under no circumstances should you attempt to "split" the 240 into a 120 outlet! The dryer circuit is protected with a 30-Amp or larger breaker (5000 watts is over 20 Amps). If anything had an overload, the ordinary 15-amp or 20-amp outlet for 120 volts and anything plugged into it could overheat and catch fire well before the 30A breaker shut off the current. A "combination" washer/dryer unit is designed with internal overload protection for the 120-volt equipment. <><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
If you do this work yourself, always turn off the power
at the breaker box/fuse panel BEFORE you attempt to do any work
AND
always use a meter or voltage indicator
to insure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
you get an adapter
Chances are there is more than 1 outlet connected to the 110volt circuit you are looking to convert. So therefore the easy answer is No. The 240volt dryer circuit must be a dedicated single circuit for the dryer only.
That is the normal electric outlet found on the walls of your home in the USA
no. the breaker is 40amps.fire hazard
If there isn't a power outlet in reach of the unit you have two options. Call an electrician to install an outlet or call a carpenter to redesign your kitchen so that there is one near (basically move the dryer). Extension cables are not recommended for permanent use in kitchens.
Metal is a conductor and the electricity will easily flow through it.
It depends on what kind of dryer you are going to put in though I recommend to put in a 110 dryer so there will be no need for a contractor as the outlet for your washer is usually rated to supply enough amps for both appliances.
Chances are there is more than 1 outlet connected to the 110volt circuit you are looking to convert. So therefore the easy answer is No. The 240volt dryer circuit must be a dedicated single circuit for the dryer only.
You cap the gas pipe and run 8/3 electric cable to the location if it's fairly close. Install it in an outlet box for range plugs. If you are not familiar with electricity, hire an electrician.
1. Drain the cooling system.2. Remove the lower radiator hose from thermostat outlet.3. Remove the thermostat outlet bolts and outlet. Remove the thermostat.4. Clean the mating surfaces of the radiator outlet and the radiator outlet pipe.To install:1. Install the thermostat.2. Install the thermostat outlet and bolts.3. Install the coolant outlet attaching bolts and tighten the thermostat outlet bolts to 10 ft. lbs. (14 Nm).4. Install the lower radiator hose to thermostat outlet.5. Fill the cooling system.6. Inspect for leaks.
You find a space in your electric panel that will hold a 30 A breaker. You run 10 gauge wire from the electric panel to where you mount the outlet. You buy a 30 A rated outlet with a receptacle that matches the cotton candy machine. Black wire goes to the brass colored screw on the outlet, white wire to silver screw and ground wire to green screw.
That is the normal electric outlet found on the walls of your home in the USA
drill hole in dashboard, install outlet in hole, and run two wires to the battery
You bet it will.
Yes
An electric cord with prungs at the end to pug into an electrical outlet
$250.00
with electric