You do not ohm a transformer, in fact you do not ohm anything. Please restate your question.
with an meg ohm meter
1 volt
The side of the transformer that has the ohm CT which translates into a winding on the transformer that has a center tap . This side of the transformer was likely attached directly to the audio output transistors set up in push pull configuration. This is what the center tap is for. This side of the transformer would have a higher impedance and is directly driven by the power supply to provide amplification The transformer also isolates the amplifier voltage from the other side which is of low impedance. This may be in the range of 8 to to 16 ohms which would be directly tied to a speaker.
1st make sure the power is turned offDisconnect one lead on primary side of transformer and using an ohm meter check for continuity. You will probably get a low ohm reading if you get no reading the windings are broken and transformer is no good2nd test using ohm meter again check for winding to ground you should get no reading. If you get a ohm value the transformer is shorted to groundRepeat these tests on secondary sideWith power on and fuse removed with a voltage meter check for power on secondary sideIf it is okay turn off power and install fuseIf fuse blows again check for shorts in circuitRemember to be careful when power is turned on
A 10 ohm reactive load would produce a larger shift of theta in the primary of a transformer compared to a 10 ohm resistive load. This is because a reactive load introduces a phase difference between the voltage and current, resulting in a larger reactive power component in the primary winding. In contrast, a resistive load maintains a phase angle of zero, leading to a smaller shift in the overall current phase. Thus, the presence of reactance in the load increases the complexity of the magnetic coupling in the transformer, causing a greater phase shift.
Sir I am Imran khan in nepal my problem is 6000KVA Step down Transformer is not charging. Transformer Pri- 33000V /105A Sec- 6900V / 502Atransformer all test (open & short circuit ) good . but problem is HT(IR)= value this time IR value 50M ohmBefore 3days HT(IR) = value is 7000M ohm suddenly start Transformer result is Transformer not charging & HT(IR) value is down 50M ohm.
A: Ohms law apply to any and to all components if there is current flowing.AnswerFor Ohm's Law to apply, the ratio of voltage to current must remain constant for variations in voltage. This is only true for a limited range of conductors and devices which are termed 'linear' or 'ohmic'. If the ratio of voltage to current changes for variations in voltage, then the conductor or device is 'non-linear' or 'non-ohmic', and Ohm's Law does NOT apply. An example of a non-ohmic conductor is tungsten (e.g. a lamp filament) and an example of a non-linear device is a diode -there are many more.As to whether a transformer obeys Ohm's Law, the answer is not straightforward. When the transformer is not supplying a load, the primary current is determined by the voltage and impedance of the primary windings and, say, doubling the voltage will double the primary current -so you could say that it is obeying Ohm's Law. However, when the transformer is supplying load, the primary current is determined by the secondary current and not just by variations in the supply voltage, so is clearly not obeying Ohm's Law.
The dipole side is always 50 ohm. The other side depends on the signal source impedance requirement, like 8 ohms for audio.
You would not connect a current transformer to a 230 v supply. To get 5.6 v 12 mA you could get a 230 to 6 volt transformer, then drop the supply from 6 to 5.6 using a 33-ohm resistor.
iT IS ISMILAR TO THE GROUND RESITOR CALCULATION FOR TRANSFOMER THE TYPICAL EXAMPLE WAS ANSWERED EARLIER FOR TRANSFORMER DT.19-06-2009 Neutral of transformer can be grounded solidly earthed OR with Neutral Grounded with Resistance. Typical shunt calculations fro 5 MAV 11/6.6 kv transformer neutral are as :_ Transformer rating = 5 MVA Voltage ratio = 11/6.6 KV Vector Group = Dyn11 (6.6 KV ground through Resistor) During Earth fault voltage between Neutral & Earth = 6.6/√3 = 3.81 KV Earth Fault current will be limited to = 5 x 10³ /(√3 x 6.6) = 437.38Amp. N.G.R. value in ohm = V / I = (3.81 x 10³) / 437.38 = 8.71 Ohm Value of N.G.R. is 437.38 Amp, 8.71 Ohm., 10 Sec NGR are inserted On Higher voltage to restrict earth fault current BY SRI
The " Ohm " is. 1 ohm is the resistance across which 1 volt of EMF appears when the current through it is 1 Ampere.
To test primary and secondary resistance in a transformer, you can use a digital multimeter. For primary resistance, disconnect the transformer from the circuit, set the multimeter to the resistance (ohm) setting, and measure across the primary winding terminals. For secondary resistance, perform the same procedure across the secondary winding terminals. Ensure the transformer is completely de-energized and isolated from any power source before testing.