Best Answer

Short answer: get a licensed Gas Fitter to do the job.

Long answer: as a 34-year HVAC veteran service technician, here's how I would do it.


1. Confirm that the valve is definitely At Fault by confirming that the gas is on, and that there is "the applied voltage" (typically 24 volts) to the valve, and that the valve will not operate. A gas valve is usually rather expensive.
2. Shut off the gas and electricity to the furnace.
3. Identify all wires connected to the valve, either by drawing a diagram with each lead identified, or by taking photos. Then disconnect the wiring.
4. If there is pilot tubing attached to the valve, disconnect it. Be aware that it can be difficult to properly install pilot lines, and if you cross-thread the fitting, you will have to replace the entire gas valve, again.
5. If there is a gas relief line from the valve to the pilot assembly, disconnect it. In all likelihood, your new valve will not have a connection for a relief line, so you can just leave it disconnected. (The relief line is a relic from the days of "diaphragm gas valves," which used gas pressure to operate the valve itself.)
6. Using 2 pipe wrenches, disconnect the gas piping from the existing valve.
7. If there is room to spin the valve in place in the furnace, disconnect it there. Otherwise, it will be necessary to remove the valve, manifold, and burner assembly to get the valve out.
8. Clean all pipe threads using a wire brush. Apply dope or gas-rated Teflon tape in the approved fashion (set back 2 threads from the end of the pipe, overlapping by 1/2).
9. Tighten all gas connections using 2 wrenches. Reconnect the pilot tubing (if present). Reconnect the wiring per your diagram or photos.
10. Attach a manometer and tubing in order to read and calibrate manifold pressure.
11. Turn on the gas and leak test the connections using a combustible gas leak detector, soap, and/or meter dial test.
12. Turn on the gas valve itself (it is usually shipped in the OFF position). If it is a "standing pilot" valve, light the pilot according to the instructions.
13. Turn on the furnace electrical power, and set the thermostat to call for heat.
14. When main flame lights, confirm manifold pressure. It should not exceed the pressure listed on the furnace nameplate (often 3.5" W.C.), but may under-fire by up to 10%, if desired.
15. Shut down the furnace and remove the manometer and tubing. Reseal the pressure tap.
16. Turn the furnace back on and check all gas connections downstream of the gas valve (using a combustible gas leak detector and/or soap).
A note: when using a combustible gas leak detector, it is not unusual to pick up a small amount of gas at the outlet of a valve (ie, at the burner ports), when the heat is shut off. It's been my experience that somewhere between 10%-25% of all gas valves do not seal off completely.


The HVAC Veteran

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How do you replace the gas valve in your furnace?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Can you buy and repace the diaphragm in your furnace gas valve?

No, you should replace the valve.


How do you identify an electric furnace from a gas furnace?

an electric furnace runs off of 208/230 Volts while a typical gas furnace runs off of 120 also a gas furnace will have a valve for the gas relay where the gas enters the furnace.


What gas valve will replace a b12826-14 for a goodman furnace?

gemini 36g22 y type 202 goodman b12826-28


York furnace pilot light is on replaced thermo stat and thermo couple still wont come on?

Bad thermo,replace. The thermo senses that the pilot is lit and opens gas valve,also could be bad or blocked gas valve.


What is the reason for a furnace to go through all the systems of operations and the ignitor sparks but no gas?

Typically, it is going to be the gas valve. The system sends a 24 volt signal to the gas valve and it opens. I you are getting 24 vols to the gas valve and no gas, it will be the valve.


How do you fix a furnace main gas valve that is stuck in open position and main burner burns all the time replaced thermostat and new wire without change?

the without change part is the most difficult part of the answer. Change the valve. Mine was less than $100. You have a runaway gas valve-the other contributor is right-replace the gas valve asap.


How do you convert a furnace to propane or natural gas?

Change out the gas flow orifice size to propane and adjust the gas valve.


Why is it necessary to have a pilot safety shutoff on a gas furnace?

so when the pilot goes out the gas valve is shut off


Why does the home gas furnace blow cold air?

Perhaps the pilot light is out and the gas has been turned off at the valve.


How do you remove concrete from a gas valve?

Your kidding me right; replace the valve.


Can you use a gas valve from a 64000 btuh lp furnace into a 124000 btuh ng furnace?

That's less than half the btu's required what do you think!


How do you know if the thermo coupling on your gas furnace is bad?

The thermocouple tells the gas valve to supply gas to the burners. If the thermocouple is bad then the furnace will not work or the pilot will not stay lit. A properly working one will have a reading of at least 12 milliamps.