answersLogoWhite

0


Best Answer

1.73 (the square-root of 3) is the ratio of line voltage to phase voltage in a star (wye) three-phase connection, and is the ratio of line to phase current ratio in a delta three-phase connection supplying a balanced load. In each case, it is derived from the phasor addition of two values displaced from each other by 120 electrical degrees.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is 1.73 in load current calculation?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the formula of load calculation?

There are various formula of load calculation. Power equals current multiplied by the voltage. Power can also be computed by multiplying the resistance by the square of the current.


For voltage drop calculation you must use the current of the circuit breaker or the normal currents?

For voltage drop calculation you must use the current of the load and the distance of the load from the supply source. The circuit breaker is then used to limit the current to the rating of the wire that feeds the load.


What is the difference between rated current full load current?

rated current is the current at any given conditions......but full load current is the maximum current that the system design can hav.....it w'll b larger than that f the rated current. rated current is the current at any given conditions......but full load current is the maximum current that the system design can hav.....it w'll b larger than that f the rated current.


How do you make concrete load calculation?

get someone else to do it


How does load current varies with the load resistance?

Load current is related to load resistance by an inverse relationship. The load current increases linearly as load resistance decreases. Remember, the less resistance, the more current.


What is the percentage of the no-load current in a transformer to its full load current?

2 to 5% of full load current


The current load of a trnsformer is the current drawn by the?

Load!


The current load of a transformer is the current drawn by the?

load


What is the star delta motors current calculation?

The calculation will change daily. You will have to check with the website to find out the current calculations for your needs.


Why the waveform of no load current is not sinusoidal?

No load current is mostly inductive, hence the load current may not be a sine wave


Why no load current is 5 percent of full load current in motor?

As the no load current is the current due to core losses of the motor which is very small .in no load terminals are open circuited no current flows through it, a small current flows which is due to core


What is the current for 24VAC with load of 30VA - which fuse to put in series If you can show the calculation?

I'm assuming these are RMS values. Power is equivalent to the voltage times the current: 30VA = 24*I I = 1.25A. If the load is 30VA, you should put in a fuse larger than 1.25A. If the transformer this is coming from is rated at 30VA, and the load is below this (say typically 20 watts resistive load), you may want to undersize the fuse to insure the transformer is protected.