1.73 (the square-root of 3) is the ratio of line voltage to phase voltage in a star (wye) three-phase connection, and is the ratio of line to phase current ratio in a delta three-phase connection supplying a balanced load. In each case, it is derived from the phasor addition of two values displaced from each other by 120 electrical degrees.
For voltage drop calculation you must use the current of the load and the distance of the load from the supply source. The circuit breaker is then used to limit the current to the rating of the wire that feeds the load.
get someone else to do it
2 to 5% of full load current
Load!
When the value of the load resistance in a transformer is changed, it will affect the current flowing through the circuit. Increasing the load resistance will decrease the current, while decreasing the load resistance will increase the current. This change in current will in turn affect the voltage across the load and the efficiency of the transformer.
There are various formula of load calculation. Power equals current multiplied by the voltage. Power can also be computed by multiplying the resistance by the square of the current.
For voltage drop calculation you must use the current of the load and the distance of the load from the supply source. The circuit breaker is then used to limit the current to the rating of the wire that feeds the load.
rated current is the current at any given conditions......but full load current is the maximum current that the system design can hav.....it w'll b larger than that f the rated current. rated current is the current at any given conditions......but full load current is the maximum current that the system design can hav.....it w'll b larger than that f the rated current.
get someone else to do it
Load current is related to load resistance by an inverse relationship. The load current increases linearly as load resistance decreases. Remember, the less resistance, the more current.
2 to 5% of full load current
Load!
load
The calculation will change daily. You will have to check with the website to find out the current calculations for your needs.
No load current is mostly inductive, hence the load current may not be a sine wave
As the no load current is the current due to core losses of the motor which is very small .in no load terminals are open circuited no current flows through it, a small current flows which is due to core
I'm assuming these are RMS values. Power is equivalent to the voltage times the current: 30VA = 24*I I = 1.25A. If the load is 30VA, you should put in a fuse larger than 1.25A. If the transformer this is coming from is rated at 30VA, and the load is below this (say typically 20 watts resistive load), you may want to undersize the fuse to insure the transformer is protected.