You listed no gauge wire. This is the required breakers.
Read the literature for the ac condensing unit, or the tag on the outside of the unit. Minimum circuit ampacity= minimum breaker, wire and fuse size. Maximum circuit ampacity= the maximum size. Your circuit breaker, wire size and disconnect fuses should all be at or between those 2 numbers.
For a TNIA 10 (Thermal Magnetic Circuit Breaker), the appropriate breaker size would depend on the specific requirements and rating of the circuit it is protecting. The breaker size should be chosen to match the maximum current rating of the circuit it is installed on to ensure proper protection against overcurrent. It is recommended to consult the manufacturer's specifications and guidelines for selecting the correct breaker size for the TNIA 10.
The wire is sized to the maximum overcurrent protection device (Max circuit breaker) ampacity. This is listed on the nameplate of the outdoor condensing unit. Size the wire to match the breaker.
fual gaug tempriter gaug speed clock revcounter all not operrating
The breaker size for a TNIA-10 wire depends on the maximum current carrying capacity of the wire, which is typically indicated on the wire's packaging or in its specifications sheet. You should select a breaker that is rated slightly higher than the wire's maximum current capacity to ensure safety and avoid overloading the wire. It is recommended to consult with a qualified electrician for specific guidance on breaker sizing for your installation.
The main breaker will have marking indicating size of electrical service, or if it is a fuse system....the fuses will have current ratings. If it is a subpanel, it might not have a main breaker. In this case you would have to look in the panel that the feed is coming from and find the size of the breaker that is feeding it. In either case you must look for the manufacturer's label that will have the maximum current the panel can handle, make sure the breaker feeding the panel doesn't exceed this rating.
The maximum amperage capacity of a 240 amp breaker is 240 amps.
The maximum current capacity of a 120 amp breaker is 120 amps.
The maximum current capacity of a 225 amp breaker is 225 amps.
The maximum amperage capacity of a 30 amp breaker is 30 amps.
The maximum current capacity of a 125 amp breaker is 125 amps.
The maximum current capacity of a 150 amp breaker is 150 amps.