answersLogoWhite

0


Best Answer

An Earth Leakage Circuit Breaker - ELCB for short - was the first name given to what is now called a Ground Fault Circuit Interrupter (GFCI) .

The early, original, type of ELCB was designed only to detect a current flowing in the safety "ground" or "earth" wire.

Why was that important?

If there is no fault anywhere in a circuit supplying single-phase alternating power to a unit such as an electrical appliance, machine or other equipment, the current flowing to the unit at any instant in the "hot" or "live" wire should exactly match the current flowing away from the unit in the neutral wire. Similarly, there should be no current flowing in the unit's safety "ground" or "earth" wire.

It is a basic fact of electrical engineering design that all current flowing to an electrical appliance, machine or other equipment from the power generation station via its supply circuit's "hot" or "live" wire should only return to the power station via that same circuit's "neutral" wire.

So, as a result of that basic fact, if any current isflowing in the ground wire, it must be caused by a fault condition and the supply of current to the circuit needs to be stopped urgently.

Many years ago, before today's electronic RCDs or GFCIs were designed, much simpler electro-mechanical relays called Earth Leakage Circuit Breakers (ELCBs) were invented so that, if any such ground current exceeding just a few milliamps was detected, they would "trip" - meaning "operate" - to break the current supply to the circuits for which they were installed to protect.

The original type of ELCB did not check for any difference in current flowing in the live and neutral wires, which is another indication of a very serious fault condition - even if no current can be detected flowing in the ground wire - because the "missing current" may actually be flowing to ground via someone's body!

When RCDs were invented, most manufacturers of GFCIs adopted the same technology because it offers so much more protection to users than the original GFCI could ever give.

In the US and Canada such devices are still commonly known as "GFCIs" or "GFIs" even though they have the additional "residual current detector" functionality, whilst in Europe and elsewhere the more accurate name of "Residual Current Detector" or RCD has been widely adopted for general use instead of using the name of the much simpler GFCI device.

Another answer [Note: this is actually a description of a GFCI, not of an ELCB.]

An ELCB works by comparing the input current in the "hot" line feeding a load and the return current in the "neutral" line coming back from that load.

If the return current is less than the input current by a quite small amount - usually only about 30mA or less (mA = milliamps, which are thousandths of an amp) - it means there must be a leakage current.

That very small difference between the input and return currents is what the ELCB is designed to detect and cause it to trip so as to break the flow of current to the load.As the name itself indicates, an Earth Leakage Circuit Breaker device always checks for any leakage of current. The leakage may be either to the "earth" or "ground" wire or to something else such as the user of the equipment that is being protected by the ELCB device.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

13y ago

No, only circuit breakers and fuses can provide protection from general short circuit fault conditons.

An ELCB is connected into the ground wire of an appliance. The designed use of an ELCB is specifically to detect if there is a flow of current more than a certain minimum value (a few milliamps).

Such a flow of current means there is a fault somewhere that is causing live electricity to reach any grounded metal parts - which should never be "hot" - either inside the appliance or on its outside, such as its casing.

If that fault condition occurs the ELCB operates to break the flow of current coming from the power service to the appliance, thus helping to prevent people from getting electric shocks from it.

GFCIs - also known as RCDs in Europe and elsewhere - are usually installed nowadays to do a similar job because ELCBs can only monitor the ground wire of an appliance but GFCIs are designed to monitor both the hot and the neutral wires in the cord supplying power to an appliance.

A GFCI is a much better and safer protection device because it is designed to detect any difference more than a certain minimum value - a few milliamps - between the amount of current flowing in the neutral wire compared to the amount flowing in the hot wire.

If such a fault condition occurs, which means some current (the "difference current") must be leaking away somewhere else - which could be through a person who is using the appliance - the GFCI operates to break the flow of current from the power service to the appliance, thus helping to prevent people from getting electric shocks from it.

For more information see the answers to the Related Questions shown below.

This answer is:
User Avatar

User Avatar

Wiki User

13y ago

An Earth Leakage Circuit Breaker was the first name given to what is now called a Ground Fault Circuit Interrupter (GFCI) . The original type of ELCB or GFCI was designed only to detect a current flowing in the safety "ground" or "earth" wire.

If there is no fault anywhere in a circuit supplying single-phase alternating power to a unit such as an electrical appliance, machine or other equipment, the current flowing to the unit at any instant in the "hot" or "live" wire should exactly match the current flowing away from the unit in the neutral wire. Similarly, there should be no current flowing in the unit's safety "ground" or "earth" wire.

It is a basic fact of electrical engineering design that all current flowing to an electrical appliance, machine or other equipment from the power generation station via its supply circuit's "hot" or "live" wire should only return to the power station via that same circuit's "neutral" wire.

So, as a result of that basic fact, if any current isflowing in the ground wire, it must be caused by a fault condition and the supply of current to the circuit needs to be stopped urgently. Many years ago, before today's electronic RCDs or GFCIs were designed, much simpler electro-mechanical relays called Earth Leakage Circuit Breakers (ELCBs) were invented so that, if any such ground current exceeding just a few milliamps was detected, they would "trip" - meaning "operate" - to break the current supply to the circuits for which they were installed to protect.

The original type of ELCB or GFCI did not check for any difference in current flowing in the live and neutral wires, which is another indication of a very serious fault condition - even if no current can be detected flowing in the ground wire - because the "missing current" may actually be flowing to ground via someone's body!

When RCDs were invented, most manufacturers of GFCIs adopted the same technology because it offers so much more protection to users than the original GFCI could ever give.

In the US and Canada such devices are still commonly known as "GFCIs" or "GFIs" even though they have the additional "residual current detector" functionality, whilst in Europe and elsewhere the more accurate name of "Residual Current Detector" or RCD has been widely adopted for general use instead of using the name of the much simpler GFCI device.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How does an earth-leakage circuit breaker or ELCB work?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

How can a circuit breaker be made to work after it has opened?

put your dick in it


What is different Circuit Breker And Isolater?

I think that the questioner is asking what is the difference between an isolator and a circuit breaker.A circuit breaker is a switching device designed to interrupt a fault current.An isolator is not intended to break a live circuit but, rather, to provide a visible separation between a circuit component and live conductors.For example, isolators (or 'disconnectors' in US parlance) are located on either side of a high-voltage circuit breaker. If the circuit breaker requires maintenance, then the procedure is to:a. trip the circuit breaker.b. open the isolators on each side of the circuit breaker, so there is a visible gap between the circuit breaker and the 'hot' conductors.c. apply temporary earths (grounds) between each isolator and the circuit breaker.d. complete a 'permit to work' card.e. begin work.


Where isolators are placed in substation?

An isolator is a non load-breaking switch, and is provides a visible means of isolating a component, such as a circuit breaker, transformer, etc., from the high-voltage lines, whenever it is necessary to perform maintenance of that component. Normally, isolators come in pairs, with one on each side of the component to be isolated. Isolators are only opened afterthe load current has been broken using a circuit breaker, and must be closed before the circuit breaker is reclosed.To work on, say, a h.v. circuit breaker, the breaker must be tripped, the isolators on either side must be opened and locked off, temporary earths attached to either side of the circuit breake- to-work card, detailing the maintenance work, must be issued to the crew by the supervising engineer.


What is the difference between disconnect switch and circuit breaker?

A circuit breaker is an automatically-operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and, by interrupting continuity, to immediately discontinue electrical flow.The term switchgear, used in association with the electric power system, or grid, refers to the combination of electrical disconnects, fuses and/or circuit breakers used to isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream.


How would one wire up an earth leakage circuit breaker on the secondary side of an isolating transformer?

Isolation transformers are used to protect people working on transformerless equipment, where there is a 50-50 chance that the equipment's metalwork is at mains active voltage (110/240 V). Plugging in to the transformer "floats" the equipment, so that the metalwork can be safely connected to ground, and remove any voltage on it. An ELCB relies on detecting the imbalance between active current and neutral current that occurs when you touch a wire of metalwork that's at mains potential. But, on the secondary of the isolation transformer, you decide which is active and neutral. It is possible to wire the ELCB into circuit on the secondary side of the transformer, just as you would for a normal installation. Be aware that you must now connect one of the transformer secondary wires to gound for the ELCB to work (at least, that's the case here in Australia), so you are back into the 50-50 chance of live metalwork, unless you fit a reversing switch that lets you ensure that the metalwork is connected to neutral. But you need to understand that an ELCB only protects you from active-to-ground shocks, it DOES NOT protect you from active-to-neutral shocks, and there is no current equipment that can. I STRONGLY SUGGEST that you consult with a licensed electrical contractor to work out what you are trying to achieve. Electricity gives you one chance.

Related questions

How do you work air circuit breaker?

There are various to check if your air circuit breaker working. You can use various tools that are available to test your air circuit breaker. A clamping ammeter is ideal for this purpose.


Can you use any other brand of circuit breaker in conjunction with a Challenger circuit breaker?

A Murray or similar breaker would work but most inspectors want the brand breaker to match the brand panel.


How can a circuit breaker be made to work after it has opened?

put your dick in it


Need of isolator on both side of circuit breaker?

Before anyone is allowed to work on a high-voltage circuit breaker, it must be tripped, electrically isolated, earthed (grounded), barriers/warning notices put in place, and a permit to work document issued by an engineer to the senior member of the maintenance crew. 'Isolation' means a physical (and visible) break in the conductors between the circuit breaker and any potential source of supply -and this is provided by placing isolator switches on each side of the circuit breaker. Without these isolators, the circuit breaker would remain energized, even though the circuit has been broken by the circuit breaker.


Why do you use isolator on both side of circuit breaker?

Opening a circuit breaker merely interrupts the current flowing through that circuit. It doesn't remove the voltage from the circuit breaker. Isolators (called 'disconnects' in North America) place a visible gap between the circuit breaker and energised conductors, allowing work to be performed on the circuit breaker safely. The full procedure involves: 1. Tripping the circuit breaker (CB). 2. Opening both isolators. 3. Applying temporary earth (ground) connections on either side of the CB. 4. Placing barriers and warning signs around the CB. 5. Issuing a permit to work card to the maintenance supervisor.


What is an electrical isolator?

Something that doesn't let electricity throughAnswerAn isolator (UK terminology) or disconnector (US terminology) is a switch used to isolate a section of a circuit from any energised conductors, by presenting a visible break in the circuit. Isolators are not designed to break load currents (unless fitted with optional arc-breaking feature) or to break fault currents. In high-voltage systems, isolators are used in conjunction with circuit breakers -with the isolators opened after a circuit breaker has opened the circuit, and closed before the circuit breaker closes the circuit. For example, before one can perform maintenance work on, say, a high-voltage circuit breaker, the following sequence must be followed:the circuit breaker is opened, breaking the circuit.isolators located on either side of the circuit breaker are opened, presenting a visible break between the isolator and energised lines.temporary earth (ground) connections are applied to each side of the circuit breaker.barriers and warning signs are erected around the circuit breaker to define the permitted work area.a permit to work card, listing the work to be performed, and any potential hazards, is issued to the personnel who are to maintain the circuit breaker.


Can a circuit breaker be tripped by using 20 amp sockets instead of 15 amp sockets?

A circuit breaker protects the wires that the devices are connected to. If the devices that are connected to the circuit are 20 amps the wire size should be #12 wire fed from a 20 amp breaker. This breaker should not trip unless the circuit is overloaded or a fault occurs on the circuit. If the devices that are connected to the circuit are15 amps the wire size should be #14 wire fed from a15 amp breaker. This breaker should not trip unless the circuit is overloaded or a fault occurs on the circuit. Putting 20 amp sockets on this 15 amp circuit will work but the circuit is limited to the amount of load that can be plugged in. You will not get the full capacity of the 20 socket because the breaker will trip at 15 amps.


Marine engine no electric power circuit breaker will not reset or work when jumped why?

Your engine is kaput.


What is different Circuit Breker And Isolater?

I think that the questioner is asking what is the difference between an isolator and a circuit breaker.A circuit breaker is a switching device designed to interrupt a fault current.An isolator is not intended to break a live circuit but, rather, to provide a visible separation between a circuit component and live conductors.For example, isolators (or 'disconnectors' in US parlance) are located on either side of a high-voltage circuit breaker. If the circuit breaker requires maintenance, then the procedure is to:a. trip the circuit breaker.b. open the isolators on each side of the circuit breaker, so there is a visible gap between the circuit breaker and the 'hot' conductors.c. apply temporary earths (grounds) between each isolator and the circuit breaker.d. complete a 'permit to work' card.e. begin work.


Where is the fuse for the headlights on a 1993 Chevy Caprice Classic LS?

There is no fuse. Headlights work on a circuit breaker.


How to bypass single phase circuit breaker?

You should never try to bypass any protection devices. This is just asking for trouble down the road. The circuit breaker is there to protect the wiring to the device that is powered from that breaker. If the load is too large and keeps tripping the breaker install a larger breaker with new wiring sized to the breaker to accommodate the higher load current. Again do not bypass circuit breakers as you will have no short circuit or overload protection.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliancesalways use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


Where isolators are placed in substation?

An isolator is a non load-breaking switch, and is provides a visible means of isolating a component, such as a circuit breaker, transformer, etc., from the high-voltage lines, whenever it is necessary to perform maintenance of that component. Normally, isolators come in pairs, with one on each side of the component to be isolated. Isolators are only opened afterthe load current has been broken using a circuit breaker, and must be closed before the circuit breaker is reclosed.To work on, say, a h.v. circuit breaker, the breaker must be tripped, the isolators on either side must be opened and locked off, temporary earths attached to either side of the circuit breake- to-work card, detailing the maintenance work, must be issued to the crew by the supervising engineer.