long travelling and cross travelling meter
The maximum current output of a CT is 5 amps. Connected to a meter this will be full scale. What ever the ratio of the CT will dictate the scale face on the meter. A 500 amp CT's output will be 5 amps at 500 amps on the buss. 250 amps on the buss, the CT will output 2.5 amp or half scale on the meter face.
K=(voltmeter range*ammeter range*power factor)/wattmeter range
5P20 CT give more accuracy than PS class CT. 5P20 cant be used in unit protection. Class PS CT is a protection class ct. It is used for differtial proction,distance (UNIT)proction.
CT (current transformer) Burden is the maximum load that the CT secondary can drive (e.g. meters or protection relays) Why do you care about burden when ordering current transformers? The burden is the termination impedance of the measuring instrument. The measuring instrument can be an analog or digital energy meter, a data logger or a recorder. All instruments that use a current transformer to measure line current must terminate the CT with a resistance (impedance in same case which means there is some inductance involved). A CT supplier should be given the burden when ordering. Technically, the total burden for a CT is the internal winding resistance, the connecting lead resistance and the measuring instrument input resistance. Some Ct's are installed a long distance from the measuring instrument and the connecting leads can have a resistance as much as 0.002 ohms per foot (both ways because the current makes a complete round trip). This resistance will cause an error if not taken into account.
By Using CT and PT, The RMS Current, RMS Voltage, True Power are measured by using Sample and Hold Circuits and converts into ADC then using Microcontroller or Microprocessor to calculate the Real values.
Lt means - long travelling ct means- cross travelling
Multiplication factor can be derived from Meter CT, Meter PT, Connected CT and Connected PT values.
mf is ratio of CT ration of meter box to CT ration written on meter. ex: CT meter box: 30/5, Meter ct ration 1/1. MF : (30/5)/(1/1)= 6
multiplying factor = Line CT Ratio / Meter CT Ratio Usually it is mentioned on Meter that MF = 1 if CT Ratio is 200/5 or MF = 2 if CT Ratio is 400/5. There can be an additional multiplication factor that would be mentioned on the meter.
is 3 phase Meter electicity to for the measurement of elektricity 3 phase.
CT metering circuit can not be used to measure voltage
The maximum current output of a CT is 5 amps. Connected to a meter this will be full scale. What ever the ratio of the CT will dictate the scale face on the meter. A 500 amp CT's output will be 5 amps at 500 amps on the buss. 250 amps on the buss, the CT will output 2.5 amp or half scale on the meter face.
A current transformer has to have the same ratio as the meter that it drives. Full scale deflection on the meter is 5 amps which equals the maximum allowed current on the phase that it is reading. A different ratio on the CT to meter would show an erroneous reading on the meter depending on the ratio of the connected CT. To keep costs down the meter is common to all three phases and is read by connecting the meter to the phase CT through a three position switch.
If, Ct value = 50 meter unit = 30 so, 50 x 30 = 1500 kwh
It is 1kg
A CT multiplier is the ratio of current trough a CT to the output of a CT. Example: A 200/5 Multiplier means that the cable passing through the CT must see 200A to provide a 5A output to the reading meter. The reading meter will then display 200A on it's display but it of course is only seeing 5A itself. Many digital meters have selectable Multipliers so you don't have to stock a wide selection of meters.
The question is incomplete, because there are no mention about CT & PT ratios. 600VA 5 can not be CT ratio.