10 hp and above motor power rating....

User Avatar

Wiki User

13y ago

What else can I help you with?

Continue Learning about Electrical Engineering

What device requires an electric power supply?

A motor


Open Transition Switching in star delta starter?

The transition from star connection to delta connection requires that the current flow through the motor is interrupted. This is termed "Open Transition Switching" and with an induction motor operating at partial speed (or full load speed), there is a large current and torque transient produced at the point of reconnection. This transient is far worse than any produced by the DOL starter and can cause severe damage to equipment and the supply.


Why is a star-delta starter used?

A "star-delta" starter- also known as a "Y-delta" or "wye-delta" starter - is used to reduce the voltage on the motor windings to only 1/.'/'3 [one divided by root 3] times the incoming line voltage, to help reduce mechanical stress and in-rush current at start-up.More detailWhenever you start a big heavy electric motor, you need to start it slowly to prevent the rotor overheating and drawing an enormous current. When the windings of a 3-phase motor are connected in STAR the voltage is reduced to a fraction equal to one over root three (1 / 1.732) times the normal running voltage that is used when it is connected in DELTA, resulting in a reduction of nearly one half the normal current.Once the motor picks up speed, the connection is changed to DELTA so that the motor runs at full speed and torque from then on. It's a bit like using the gears of an automobile.For more information please see the answers to the Related Questions shown below.


What supply is needed to run a 22kw 3ph motor?

question is incomplete, I think you ask how much current consumed by this motor. for starting this motor we need a star/delta starter and a three phase supply.


What is the difference of a star or delta connection on motor terminals?

230/400 V These motors can be connected in star to a mains of 400 V between the phases (see figure 1). figure 1 Star connection 400/695 V These motors should be connected in delta to a mains of 400 V between the phases (see figure 2).

Related Questions

What is the reason if you are running an electric motor with a star delta starter but whenever it is switched to delta at the same instant its circuit breaker trips?

Check your Delta connections first if the phases is corresponding, and check your Circuit Breaker if it sufficiently rated.


What is the advantage of a Star Delta Motor Starter?

The inrush current to the starting motor is lower due to the the motor coils being in series across the line creating a higher impeadence. When the starter connects to delta connection the motor is already turning and it does not have to go through the locked rotor phase. This system is being phased out now with the use of electronic soft starts and by-pass contactors.To start a motor direct on line (DOL) in delta requires approximately 6 to 8 times the full load current of the motor and delivers full torque. Delta places 415v across each of the windings on the motor. A Star-Delta starter starts the motor in Star which places 240v across each winding on the motor. This results in a lower starting current and also a lower starting torque.


What will happen if induction motor is in star-star connected?

If a motor is connected in a star configuration it will operate at a slower speed. This is the working process that a star delta starter operates on. At first through the starter the motor starts in the star connection. When the motor gets up to its highest speed in that connection it times a timer out , the star starter drops out and the delta starter pulls in and then connects the motor in the delta connection. This allows more voltage to be applied to the motor and it then speeds up to its nameplate rated RPM.


What device may be wired into the starting circuit of a motor to improve the starting torque?

I assume a 3 phase, AC induction motor. A star delta starter or a soft starter can be used. A soft starter is better compared to a star delta starter, but it is more expensive.


How much KW range can be use star-delta starter?

The use of a star delta starter is for motor control only and not resistive heating loads. This type of starter is used to dampen the inrush current by using a lower voltage to start the motor.


When star-delta starter timer will disconnnect?

its is very simple whem motor shifted on delta then timer will disconnect


What is motor housing?

The outer casing of an electric motor, as in a starter, wiper motor etc.


What is a motor housing?

The outer casing of an electric motor, as in a starter, wiper motor etc.


Why using on motor star delta starter?

because at the starting the induction motor drawn a heavy current thats why we use starter to increase the starting resistance of the induction motor!


What component used to start a modern induction motor?

Star delta starter


What will cause a star delta panel to trip in delta?

On a star delta starter a motor overload or a motor going to ground and cause a short circuit will cause the overload protection to trip. These overloads have to be reset before the motor can be restarted.


Type of starters in three phase circuit?

The three common types of starters used in a three phase circuit are DOL (Direct-On-Line) starter, star-delta starter, and soft starter. DOL starters provide full voltage to the motor upon start, which can cause high inrush current. Star-delta starters initially start the motor in a star configuration to reduce current, then switch to delta for full speed. Soft starters gradually ramp up the voltage to the motor to reduce inrush current and mechanical stress on the motor.