3 phase kVA = V*I*sqrt(3)
Where voltage is line to line, and current is the actual RMS current flowing in the a wire.
kW = V*I*sqrt(3)*Cos (phi), where phi is the angle between the voltage and current; Cos (phi) is also known as the power factor. kVA is the vector sum of kW (real power) and kVAR (reactive power).
As the equations above suggest, you must know the voltage to correctly calculate the current.
The same way, as you convert Appels to Carrots ........... There is a formula: KVAr = KVA / KW or cos=KW/KVA > Yes, we are treating KW, KVA, & KVAr as the 3 sides in a 90 deg TRIANGLE ! KW= vertical katede KVAr = horizontal katede KVA = hypotenuse
To convert 'kwh' to 'kvah' you first need to measure the length of time. You will then convert this amount to hours by dividing by 3,600. You will then divide this amount by the length of time.
KVA is the unit for the apparent power i.e it's the vector sum of the true power in KW and the reactive power in reactive volt-amperage. So, to get the value of the KVA for the 30KW,just divide the active power(30kw) with the power factor of that load.
To convert from KVA (kilovoltamperes) to KWH (kilowatthours) first convert to KW (kilowatts) by multiplying by power factor. Power factor is the cosine of the phase angle between voltage and current. Then multiply by the number of hours that you run the load.
Some confusion hereKW and KVA are units of power. The ampere is a unit of current. If you divide power by the voltage involved, you can determine the current involved, in amps. Power (watts) = volts x ampsA volt-amp is a watt. (A volt times an amp is a watt.)I=(KVA*1000)/(1.732*V) (Three Phase)AMP=KW/1000*V*PF--------------------------------------------------------------------------------------------------------------KW or KVA can be converted to one another but you cannot convert them to amps. You can compute amps by using this formula,KW = I x V x 1.732 x P.F/1000 (Three phase)KVA = I x V x 1.732/1000 (Three phase)
The same way, as you convert Appels to Carrots ........... There is a formula: KVAr = KVA / KW or cos=KW/KVA > Yes, we are treating KW, KVA, & KVAr as the 3 sides in a 90 deg TRIANGLE ! KW= vertical katede KVAr = horizontal katede KVA = hypotenuse
Multiply by Amps.
kva*cos(phase angle)
kVA = kW divided by (power factor). The power factor is the cosine of the angle between voltage and current.
To convert 2 kW to kVA in single phase, you need to know the power factor. If we assume a power factor of 0.8 (common for many single-phase loads), the conversion formula is kVA = kW / power factor. Therefore, for 2 kW at a power factor of 0.8, the result would be 2 kVA / 0.8 = 2.5 kVA.
To convert AC tonnage to kVA and kW, use the following formulas: For kVA: kVA = (tonnage x 3.517) For kW: kW = (tonnage x 3.517 x power factor). Remember to consider the power factor of the system when converting from tonnage to kVA and kW.
5kw = 6.25 kva becoz kva = kw/ pf if we take pf is o.8
It is less confusing if we capitalize the units as required. 1 kVA = 1 kW, as originated from power [W] = current [A] * voltage [V]. The 'k' means 'times 1000'. The statement can be re-written as 1000 VA = 1000 W.
To convert 'kwh' to 'kvah' you first need to measure the length of time. You will then convert this amount to hours by dividing by 3,600. You will then divide this amount by the length of time.
KVA is the unit for the apparent power i.e it's the vector sum of the true power in KW and the reactive power in reactive volt-amperage. So, to get the value of the KVA for the 30KW,just divide the active power(30kw) with the power factor of that load.
kva and kw are related as KVA = (KW/PF) pf:power factor
It depends on the power factor, which depends on the reactance of the load.For a typical power factor of 0.92, 150 KVAR translates to 383 KVA, which translates to 352 KW.Power factor is the cosine of the phase angle (theta) between voltage and current. KVA times cosine (theta) is KW, while KVA times sine (theta) is KVAR.