I have never seen a window A/C unit which runs on 1000 Watts and 1KVA is essentially 1000 watts. To run an A/C unit depending on the size you need a much bigger generator and not sized for the rated wattage of the unit but sized extra big to be able to kick the compressor motor over. Motor draw huge amounts of current when they first start typically unless you have a very late model with a VFD in it.
No, the generator is too small.
To convert kVA to horsepower (hp), you can use the formula: 1 kVA = 0.746 kW, and then 1 kW = approximately 1.341 hp. A 62.5 kVA generator can produce about 50 kW (62.5 kVA × 0.8 power factor). Therefore, the generator can provide roughly 67 hp (50 kW × 1.341 hp/kW).
The diesel consumption of a 10KVA generator typically ranges from 0.25 to 0.5 liters per hour per KVA, depending on the load and efficiency. Assuming an average consumption of 0.3 liters per hour per KVA, running a 10KVA generator for 10 hours would require approximately 30 liters of diesel (0.3 liters/KVA/hour × 10 KVA × 10 hours). It's important to check the specific generator model for accurate fuel consumption rates.
A 50 KVA generator can typically provide around 40 KW of usable power, considering efficiency and power factor. A 3 horsepower air conditioner roughly requires 2.24 KW to operate. Therefore, you could run approximately 17 air conditioners (40 KW / 2.24 KW per unit) on a 50 KVA generator, assuming ideal conditions and no other loads. However, it's essential to account for starting currents and other factors, which may reduce this number.
The difference b/w the prime generator & standby generator is that the prime generator is used for 24/7/365, while the standby generators are only used in emergency cases, if we used standby generators for more than 24 hours continuously, then it will be overheated for sure.
How much KVA generator is required to run two AC of 1.5 tone
10 AC
No, the generator is too small.
To convert kVA to horsepower (hp), you can use the formula: 1 kVA = 0.746 kW, and then 1 kW = approximately 1.341 hp. A 62.5 kVA generator can produce about 50 kW (62.5 kVA × 0.8 power factor). Therefore, the generator can provide roughly 67 hp (50 kW × 1.341 hp/kW).
To answer this question the voltage of the motor is needed.
A 15 KVA - Generator operating at 380 Volts can cater to only 22.79 Amps. It cannot cater to a 60 Amps breaker
To answer this question a voltage must be stated.
The diesel consumption of a 10KVA generator typically ranges from 0.25 to 0.5 liters per hour per KVA, depending on the load and efficiency. Assuming an average consumption of 0.3 liters per hour per KVA, running a 10KVA generator for 10 hours would require approximately 30 liters of diesel (0.3 liters/KVA/hour × 10 KVA × 10 hours). It's important to check the specific generator model for accurate fuel consumption rates.
A 50 KVA generator can typically provide around 40 KW of usable power, considering efficiency and power factor. A 3 horsepower air conditioner roughly requires 2.24 KW to operate. Therefore, you could run approximately 17 air conditioners (40 KW / 2.24 KW per unit) on a 50 KVA generator, assuming ideal conditions and no other loads. However, it's essential to account for starting currents and other factors, which may reduce this number.
3 kva genrator myt be required to run 1.5ton ac.
Well, honey, a 1 ton split AC unit typically requires around 3-4 KVA of power to run smoothly. So, you better make sure you've got a generator with at least that much juice if you want to keep cool when the power goes out. Don't skimp on the power, or you'll be sweating like a sinner in church.
1HP = 746 watts 15 HP = 11190 watts = 11.19 kW You would need a generator of at least 13kW. UPS Distributor for 15 Years.