14/3 copper with ground on a 25 amp breaker
Before I get chastised for recommending that 14 gauge wire be protected with a 25 amp breaker, which would be in violation of standard wiring requirements, Sec. 240.4(G) of the NEC tells us that the standard wiring requirements, i.e. 15 amps on 14 gauge wire, does not apply to motors. Table 430.52 tells us that an inverse-time circuit breaker (that's a standard type breaker) can be set to 250% of the FLC of the motor and 430.22 tells us that the branch circuit conductors are sized at 125% of FLC.
The question does not say that 10 amps is the FLC. The nameplate rating of a motor is not the FLC. FLC is determined by using the tables in Sect. 430. The name plate rating is used only for sizing current overloads, called "heaters". For my answer I have assumed 10 amps is the FLC.
There are no three phase 120 volt systems.
you need the current of motor or the KW/HP rating
The motor would draw about 24 kVA which is 35 amps. For this you would need 10 mm2 cable.
Assuming it is a 400 V three-phase motor, the phase current is 11 amps, or more if the power factor is less than 1.0 (or the supply voltage is different). If it is a 400 V motor the cable should be capable of carrying 16 amps, so a 2.5 mm-sq 4-core cable is needed.
The 12 lead motor is a very versatile motor and can be connected in numerous ways. It is a dual speed motor and can be wired as star delta. If you are interested, start a Discussion Page and I will see if I can help you.
We can convert a 3 phase ac motor into generator by changing phase sequence of the ac input cable of that motor
how to connect power capacitor with 3 phase motor
Sir, what is the cable size for 1.5kw 3phase induction motor 400v?
There are no three phase 120 volt systems.
you need the current of motor or the KW/HP rating
The systems are one in the same. Yes.
On a three wire supply system if you connect the two 110V wires together and they are across the phase they will short out and trip the breaker. If the two 110V wires are supplied from across the phase and connected to a motor then the motor will run. If the 110V wires are on the same phase nothing will happen.
The capacitor is used to create a second phase from the single phase power source and it is the interaction between these two phases that causes the motor to turn.
See Discuss Question below.
NO however id uyou use thirtyeen you can gt high (y)
use a rotor phaser or simply connect a 3 phase motor and check dirrection
It is very simple. Just interchange any two phase wires. i.e. Y and B ( or ) R and B ( or ) R and Y for example Stop the supply. keep R phase wire as it is and disconnect B phase wire and Y phase wire. Connect B phase wire to the Y phase motor stud and Y phase wire to the B phase motor stud. Now give the supply, now motor revolves in opposite direction to the earlier.