In a star-delta starter, the star contactor connects the motor windings in a star configuration during the initial start-up phase. This configuration reduces the voltage and current, allowing for a softer start and minimizing inrush current. If a short circuit were to occur on the star contactor, it could lead to a direct connection of the supply to the motor windings, potentially causing overheating and damage to the motor. Therefore, protective measures such as overload relays and proper circuit design are essential to prevent such occurrences.

User Avatar

AnswerBot

3mo ago

What else can I help you with?

Continue Learning about Engineering

Are contactor points and bimetallic strip connected to the star delta starter of 3 phase induction motor?

yes


Can a 3 phase contactor be wired for single phase?

Yes, L1 of the single phase supply is terminated under terminal L1 of the three phase contactor. L2 of the single phase supply is terminated under terminal L2 of the three phase contactor. A conductor from output terminal T2 is then taken to input terminal L3. The single phase load is then connected to the contactor's output terminals T1 and T3. This incorporates all three of the overload blocks on the contactor into the control circuit. With the overloads in the control circuit, if an overload occurs the magnetic contactor's holding coil will drop out and take the load off line.


What is the Difference between a magnetic starter And a contactor?

Motor starter usually refers to the complete assembly, including enclosure, contactor, control transformer (if any), overloads, fuses (if any), etc. A contactor is really just an overgrown relay, and is just one component of a starter. That having been said, many folks use the two terms somewhat interchangably. So someone who says starter may mean contactor, and vise-versa. Go figure.


What is the easiest method of reversing the direction of rotation of a 3 phase induction motor controlled by star-delta starter?

Just swap two of the phases over. <<>> Care must be taken when swapping wires on a star delta system. Reversing the wrong set in the motor box and getting the wrong wires could accidently reverse the wrong set of windings. This would cause the star magnetic to be rotating in the correct rotation and then when it switches to delta the motor tries to reverse causing a locked rotor condition and spiking the voltage very high and hopefully tripping the overload protection. The correct place to swap the two legs is at the supply side of the star contactor.


What device may be wired into the starting circuit of a motor to improve the starting torque?

I assume a 3 phase, AC induction motor. A star delta starter or a soft starter can be used. A soft starter is better compared to a star delta starter, but it is more expensive.

Related Questions

Are contactor points and bimetallic strip connected to the star delta starter of 3 phase induction motor?

yes


How much voltage does star-Delta starter give to motor at start?

A delta starter supplies what ever the supplied voltage to the line side of the contactor is. The inrush current is usually 300% of the full load amperage of the motor. Edit to above answer: Actually the question is for a Wye-Delta Starter (Wye=Star). There are two contactors, one in Wye configuration and one with Delta. The Wye is used to start and the Delta for run. This is a reduced voltage start scheme. Though the line supply voltage remains the same, for instance 480VAC, the phase voltage at the motor will be different for the Wye: V(phase) = V(line)/1.732 In a Delta V(phase) = V(line) So the Phase Voltage during the start will be 277VAC and then when the motor is spinning, usually after a set time delay, the Wye contactor drops out and the Delta contactor kicks in so that Phase Voltage is now the full 480VAC.


How can you include phase failure relay in your star delta motor starter circuit?

The star delta motor starter circuit has to have a control voltage to energize the motor magnetic contractors. A phase failure relay monitors all three phases of the incoming supply lines. The phase failure relay also has auxiliary contacts on it. There are usually two sets of "C" form contacts. The control voltage for the starter circuit must be connected across the normally open (N.O.) contacts of one of these two sets. When the phase monitor is energized these N.O. contacts close supplying the control voltage to the circuitry of the star delta starters. If there is a phase interruption, phase reversal or phase loss, the phase failure relay will de-energize and the N.O. contacts will go back to their de-energized state. If the star delta motor starter is in use at the time, its control circuitry voltage will be lost and the delta motor magnetic contactor will open. The opening of this contactor will disconnect the motor from the failed three phase supply.


In a star-delta starter what could be the problem if the motor does not rotate in star but rotates in delta?

One of the three phase contacts in the star contactor could be burned open or just open not allowing the motor to start because of a single phase condition. The time interval between star and delta connections could be small enough that the motor heaters will not catch the single phase condition and trip. When the motor goes into delta (which is now across the line starting) all of the three phase contacts in the contactor close and the motor starts.


Can a 3 phase contactor be wired for single phase?

Yes, L1 of the single phase supply is terminated under terminal L1 of the three phase contactor. L2 of the single phase supply is terminated under terminal L2 of the three phase contactor. A conductor from output terminal T2 is then taken to input terminal L3. The single phase load is then connected to the contactor's output terminals T1 and T3. This incorporates all three of the overload blocks on the contactor into the control circuit. With the overloads in the control circuit, if an overload occurs the magnetic contactor's holding coil will drop out and take the load off line.


What is the Difference between a magnetic starter And a contactor?

Motor starter usually refers to the complete assembly, including enclosure, contactor, control transformer (if any), overloads, fuses (if any), etc. A contactor is really just an overgrown relay, and is just one component of a starter. That having been said, many folks use the two terms somewhat interchangably. So someone who says starter may mean contactor, and vise-versa. Go figure.


What supply is needed to run a 22kw 3ph motor?

question is incomplete, I think you ask how much current consumed by this motor. for starting this motor we need a star/delta starter and a three phase supply.


What is the easiest method of reversing the direction of rotation of a 3 phase induction motor controlled by star-delta starter?

Just swap two of the phases over. <<>> Care must be taken when swapping wires on a star delta system. Reversing the wrong set in the motor box and getting the wrong wires could accidently reverse the wrong set of windings. This would cause the star magnetic to be rotating in the correct rotation and then when it switches to delta the motor tries to reverse causing a locked rotor condition and spiking the voltage very high and hopefully tripping the overload protection. The correct place to swap the two legs is at the supply side of the star contactor.


What is a timer in a star delta starter?

A timer in star delta starter for a three phase motor is an electronic device designed to do the change over or transition from star connection - using which the motor suns on a reduced voltage and current and produces less torque - to the delta connection necessary for running the motor at its full power, using high voltage and current to produce a high torque. The timing interval that is set is dependent how long the motor needs to start up from standstill to normal speed. Some motors require 15 seconds for the initial startup in star connection and after that given value of time the timer signals to the star contactor to go to the open position and the main delta contactor to go to the closed position, thus forming the delta circuit.


What device may be wired into the starting circuit of a motor to improve the starting torque?

I assume a 3 phase, AC induction motor. A star delta starter or a soft starter can be used. A soft starter is better compared to a star delta starter, but it is more expensive.


How do you wire a three phase forward - reverse starter?

You start with a normal one way circuit consisting of a three phase contactor and an three phase overload in series for the forward circuit. Then you add the reverse contactor in parallel with the forward contactor but with line one and line two crossed over i.e. when the reverse contactor is made, line one of the supply will be connected to line two of the motor and line two of the supply to line one of the motor. The control circuit must also be interlocked to prevent forward and reverse being energized at the same time.


Type of starters in three phase circuit?

The three common types of starters used in a three phase circuit are DOL (Direct-On-Line) starter, star-delta starter, and soft starter. DOL starters provide full voltage to the motor upon start, which can cause high inrush current. Star-delta starters initially start the motor in a star configuration to reduce current, then switch to delta for full speed. Soft starters gradually ramp up the voltage to the motor to reduce inrush current and mechanical stress on the motor.