Yes. In a 3-phase motor, all 3 phases have the same current.
For an 11kW 3 phase motor, you would typically need a isolator with a current rating of at least 18-20 amps per phase. It's important to also consider the starting current of the motor and select an isolator that can handle the motor's inrush current. Make sure to consult with a qualified electrician to determine the appropriate isolator size for your specific application.
To calculate the current per phase, use the formula: Current (I) = Power (P) / (Square Root(3) x Voltage (V)). For an 18kW motor at 415V, the current per phase will be: 18,000W / (1.732 x 415V) ≈ 24.5A per phase.
It is not recommended to supply a 240 volt single phase motor with only one phase until the other phase is closed. This can cause imbalanced current flow, leading to motor overheating and potential damage. It is best to provide both phases simultaneously to ensure proper operation of the motor.
To change the connection of a single-phase line to a three-phase line for a DC motor, typically you would need to use a phase converter or a variable frequency drive (VFD) to convert the power supply. This will allow you to provide the necessary three-phase power to the DC motor for it to operate efficiently and safely. It's important to consult with an electrician or engineer to ensure the proper conversion is done based on the motor specifications.
To calculate the phase current of a 10kW 3-phase motor, you can divide the total power (10kW) by the square root of 3 (approx. 1.732) and then divide that result by the line-to-line voltage. The formula is: Phase Current (Amps) = Power (W) / (√3 x Line-to-Line Voltage (V)).
yes the motor will run but will draw more current and the torque will be not constant means not smooth due to unbalanced current
Motor starting current is typically 5-7 times the rated current of the motor. (For three phase induction motors)
starting current of 3 phase 75 KW induction motor
You still need the same horsepower. The advantage of the three-phase motor is that it will draw lower current.
to start the motor and give more current to motor to run
The line current would be the same if the motor were connected in delta. The current can be based on the rule of thumb which says 7 amps must be allowed for a 1-HP single-phase motor on 240 v. A 2.2 kW motor is three times as powerful, and on a three-phase supply of the same voltage (240/415) it would draw 7 amps.
Very often a capacitor IS used in a single-phase motor. It provides a phase-shifted current to the starting winding to ensure that the motor runs in the right direction, e.g. clockwise if that is the requirement.
Cause 2 phase is applied to the motor and another phase is disconnected ... in this condition ur motor cannot run longer ,it will trip on over current or burn ur motor winding .
Yes but it will not start. Usually if you lose one phase the current will go higher on the other phases and the motor overload protection will disconnect the motor from the supply voltage.
you need the current of motor or the KW/HP rating
125 percent of full current rating of the motor
For an 11kW 3 phase motor, you would typically need a isolator with a current rating of at least 18-20 amps per phase. It's important to also consider the starting current of the motor and select an isolator that can handle the motor's inrush current. Make sure to consult with a qualified electrician to determine the appropriate isolator size for your specific application.