The cable to a light bulb (with a plastic bulb holder) in a house, etc, usually has just a live and neutral wire. If a brass or metal bulb holder is used, an earth wire is advised for safety reasons.
In the UK, mains power cables and wall sockets are of the three pin types, with the live (bRown wire) to the right, and the neutral (bLue wire) to the left, and the green and yellow striped wire to the earth pin.
The neutral is supposed to be grounded on all installations, single phase and three phase, according to the electrical code so no you will not get a shock if you touch the neutral wire. If the neutral wire is not grounded you might in some circumstances get a little tickle of voltage.
A neutral wire failure can cause overloaded circuits, electrical fires, and can also result in damage to electronic devices. In some cases, it can lead to electric shocks or power surges within the electrical system. It is important to address neutral wire failures promptly to avoid potential hazards.
To check if ground wires have been inadvertently terminated on the neutral bus, first, ensure all power is turned off to the panel. Then, visually inspect the connections to see if any ground wires are attached to the neutral bus instead of the ground bus. Use a multimeter to test continuity between ground and neutral; if there's continuity, it indicates a connection issue. Additionally, review the wiring diagram for the system to confirm proper connections.
If the electrical box is grounded, check with a tester, the "hot" wire will have a voltage to the the grounded box the neutral wire will not. If the box is not grounded, with the breaker supplying the voltage turned off, use a tester on the resistance scale to check for continuity between the wires and a cold water pipe or some other grounded medium. The neutral will have continuity between the wire and a ground the "hot" wire will not.
The ground wires should not be terminated on the neutral bus. They should be terminated on to the ground bus which should be located on the back wall of the distribution panel. The wires don't have to be pigtailed when inserted into the ground bus. More that one wire can go under the terminal screws if you are running out of room. Shut the panel off and remove any ground wires that are now under the neutral bus terminals and move them to the ground bus. Some panels use a lug for a ground bus. All ground wires into the lug and tighten. In a ground fault condition it is the ground wires that are connected to the ground potential that trip the breaker, not ground wires connected to neutrals. Be safe.
The neutral is supposed to be grounded on all installations, single phase and three phase, according to the electrical code so no you will not get a shock if you touch the neutral wire. If the neutral wire is not grounded you might in some circumstances get a little tickle of voltage.
Three phase allows power to be transmitted efficiently using three live wires. The voltages in the wires reach the peak of the AC cycle in turn, which allows each wire to act as the return wire for the other two, provided the currents in the wires are equal. In some cases the load currents in the three live wires are unequal, so the system is described as unbalanced, and in this case a 4th wire is added as a neutral. If the system happens to be balanced, the current in the neutral is zero. The 4-wire system allows single-phase loads to be connected between one live wire and neutral, and this type of supply is widely used throughout Europe to provide power to groups of houses. Over a sufficiently large number of houses the currents in the three phases are reasonably equal.
Three phase allows power to be transmitted efficiently using three live wires. The voltages in the wires reach the peak of the AC cycle in turn, which allows each wire to act as the return wire for the other two, provided the currents in the wires are equal. In some cases the load currents in the three live wires are unequal, so the system is described as unbalanced, and in this case a 4th wire is added as a neutral. If the system happens to be balanced, the current in the neutral is zero. The 4-wire system allows single-phase loads to be connected between one live wire and neutral, and this type of supply is widely used throughout Europe to provide power to groups of houses. Over a sufficiently large number of houses the currents in the three phases are reasonably equal.
A neutral wire failure can cause overloaded circuits, electrical fires, and can also result in damage to electronic devices. In some cases, it can lead to electric shocks or power surges within the electrical system. It is important to address neutral wire failures promptly to avoid potential hazards.
Three phase allows power to be transmitted efficiently using three live wires. The voltages in the wires reach the peak of the AC cycle in turn, which allows each wire to act as the return wire for the other two, provided the currents in the wires are equal. In some cases the load currents in the three live wires are unequal, so the system is described as unbalanced, and in this case a 4th wire is added as a neutral. If the system happens to be balanced, the current in the neutral is zero. The 4-wire system allows single-phase loads to be connected between one live wire and neutral, and this type of supply is widely used throughout Europe to provide power to groups of houses. Over a sufficiently large number of houses the currents in the three phases are reasonably equal.
Europe follows the IEC colour code that was adopted also by the UK in 2004: Single-phase: Earth: yellow and green, Neutral: blue, Live: brown. Three-phase: Earth: yellow and green, Neutral: blue, Live: brown, black, grey. In some cables the Earth wire is bare copper which should be fitted with yellow and green sleeving at its terminations.
A two-pole breaker typically connects to four wires: two hot wires, one neutral wire, and one ground wire. The two hot wires are usually connected to separate phases of a split-phase electrical system, allowing the breaker to handle 240 volts. The neutral wire is connected to the load if required, and the ground wire is for safety. In some applications, the neutral may not be used, especially in certain types of equipment.
In electrical wiring, the standard color coding often dictates that black or red wires are used for live or hot connections, white wires are neutral, and green or bare wires are for grounding. In some cases, blue and yellow may also represent additional hot wires. It's essential to follow local electrical codes and guidelines, as color codes can vary by region and application. Always ensure to power off the circuit before working with any wires for safety.
To check if ground wires have been inadvertently terminated on the neutral bus, first, ensure all power is turned off to the panel. Then, visually inspect the connections to see if any ground wires are attached to the neutral bus instead of the ground bus. Use a multimeter to test continuity between ground and neutral; if there's continuity, it indicates a connection issue. Additionally, review the wiring diagram for the system to confirm proper connections.
If the electrical box is grounded, check with a tester, the "hot" wire will have a voltage to the the grounded box the neutral wire will not. If the box is not grounded, with the breaker supplying the voltage turned off, use a tester on the resistance scale to check for continuity between the wires and a cold water pipe or some other grounded medium. The neutral will have continuity between the wire and a ground the "hot" wire will not.
Single phase is not preferred over three phase, it is the system used that the application needs to operate with. There are more single phase installations than three phase due to the fact homes operate on that system. Where as most commercial and industrial applications call for a three phase system to supply their power needs.Single-phase and three-phase are different types of power supply.Most houses and small businesses have a single-phase supply, which could be a simple live/neutral two-wire supply, or a split-phase supply with two lives and a neutral so that there is 120 v between the neutral and either live wire, but 240 v between the two live wires, which is used for loads of over 1500 watts.When necessary, properties that use more power have a three-phase supply which has three live wires and a neutral. The supply can be taken in the form of three separate single-phase supplies, or in some cases appliances such as large motors need a three-phase supply to work correctly.A three-phase supply is described by the voltage between any two of the three live wires, and the voltage from neutral to each live is 1/sqrt(3) times as much, in other words 42% less.Typical three-phase supplies are 120/208 v, 230/400 v, 240/415 v, 277/480 v and 347/600 v. The first figure is the live-neutral voltage and the second is the live-live voltage. Single-phase supplies can be taken between live and neutral or between lives.Three-phase is preferred for power transmission over longer distances, and voltages up to hundreds of kV are used. In this case the neutral is omitted because when the three currents in the live wires are equal the current in the neutral is zero.
The ground wires should not be terminated on the neutral bus. They should be terminated on to the ground bus which should be located on the back wall of the distribution panel. The wires don't have to be pigtailed when inserted into the ground bus. More that one wire can go under the terminal screws if you are running out of room. Shut the panel off and remove any ground wires that are now under the neutral bus terminals and move them to the ground bus. Some panels use a lug for a ground bus. All ground wires into the lug and tighten. In a ground fault condition it is the ground wires that are connected to the ground potential that trip the breaker, not ground wires connected to neutrals. Be safe.