answersLogoWhite

0

📱

Modification of Old Electrical Work

Electrical and building codes have changed over time and new methods proscribed for safety. Converting the old to the new leads to lots of questions.

4,592 Questions

Why is neutral and ground wires sometimes needed to be bonded in a dry type transformer?

With very few exceptions your neutral and ground are always bonded together at the service. They can be bonded together anywhere from the transformer to the first overcurrent device, usually a panel, but in the transformer is where it is usually done.

Bonding the neutral keeps your voltages from floating. Without going into very technical explanation, suffice it to say that without proper bonding you can get different voltages supplied to various circuits in the building or home. Higher voltages can cause burn out of fixtures or equipment and lower voltages can burn up motors or keep lights from providing adequate light.

Where to ground green cable when changing dryer cable from 3 to 4 prong?

The green wire should be connected to the grounding screw on the dryer chassis. This grounding ensures the safety of the appliance and protects against electrical hazards. Be sure to follow the manufacturer's instructions for proper installation.

What size wire do you need for 50 amp sub panel about 150 feet away 120 volts?

The usual allowable voltage drop is 5%, or 6 volts on a 120 v supply. For a 50 amp supply that means the total wire resistance must be (at most) 6/50 ohms, or 0.12 ohms. Because there is 300 ft of wire the resistance per ft must be 0.12/300 ohms per ft, or .0004 ohms/ft or 0.4 ohms per 1000 ft. Wire tables show that #6 AWG wire is needed, with a cross-section area of 13.3 sq mm.

<<>>

Answer for USA, Canada and countries running a 60 Hz supply service.

The code book suggest that a 3% voltage drop should be the maximum allowed. A #3 copper conductor will limit the voltage drop to3% or less when supplying 50 amps for 150 feet on a 120 volt system.

When connecting chain switch what is done with the neutral wire and white wire from ballast?

The neutral wire from the chain switch is connected to the white wire from the ballast. They should be connected together using a wire nut to ensure proper circuit completion and safe operation of the light fixture.

Can a 8 awg wire be replaced by 2 10 awg wires?

No, a single 8 AWG wire cannot be replaced by two 10 AWG wires in terms of electrical capacity and current-carrying capability. The 8 AWG wire has a larger cross-sectional area and can handle more current compared to two 10 AWG wires combined. It's important to match the wire gauge with the specific requirements of the circuit to ensure safety and proper functioning.

What could be causing your ir-12 diedrich coffee roaster to blow a breaker in your breaker box?

First, determine the current draw of the coffee roaster, then check the breaker size.

Using the formula, Watts = Amps * Volts, determine if the current draw of the coffee roaster is anywhere near the maximum current draw of the breaker. For example, if the roaster is using 14 Amps, and the circuit breaker is rated at 15 amps, that doesn't give much room for anything else on the circuit.

Add up all of the current of all devices on the circuit (the one that trips the breaker) and either move things around so that you don't have too much load on a single circuit, or you may need to bring in an electrician to run a new circuit.

If you are ABSOLUTELY certain that your appliances are nowhere near the rating of the circuit breaker, you could have a faulty breaker, in which case, bring in an electrician to replace the breaker.

Can you connect 14 gauge wire to 12 gauge wire on a 20 amp breaker if the 14 gauge is the end of the run and dedicated to lights?

yes

Another (corrected) answer.NO! The circuit breaker is there to protect the wiring from overheating. It wouldn't matter where on the circuit you decided to put the 14 gauge wire, you would need to change the breaker to 15 Amp if you did that. Using 14 gauge wire on a 20 amp circuit is a fire hazard and contrary to UBC.

Contact your local building and zoning department to verify.

What is the difference between a 30 amp and a 40 amp breaker?

A 30 amp breaker is designed to handle a maximum continuous load of 30 amps, while a 40 amp breaker can handle a maximum continuous load of 40 amps. The 40 amp breaker allows for more current to flow through before tripping, making it suitable for higher power requirements compared to the 30 amp breaker. Always consult with a qualified electrician before adjusting or replacing circuit breakers to ensure safety and compliance with electrical codes.

How do you wire a 3 wire European oven white black green to a US receptacle with 4 wires white black red and bare?

Connect the white wire from the European oven to the white wire in the US receptacle. Connect the black wire from the European oven to the black wire in the US receptacle. Connect the green wire from the European oven to the bare wire in the US receptacle. The green wire serves as the ground wire since you don't have a separate ground wire in the US receptacle.

How do you get electricity to a wall switch when getting electircity from an outlet?

Simply run a wire from that outlet to that wall switch. Be sure you use the exact same wire size that you find in that outlet. It will be AWG 12/2 or 14/2. Do not mixes wire sizes. Connect the ground to green ground screw at outlet, and white wire to silver screw, and black wire to gold screw. At the light switch connect all white wires together under a wire nut and push them back into the box. Connect the ground wire to the green ground screw on the switch. Now connect the 2 black wires you have left, power in and power out, to the 2 screws on the switch. Does not matter which wires you connect to the 2 screws.

What size wire is needed for a 200 amp sub panel that is 30 ft. from main panel?

Not an easy answer. If your breaker requires you to use the 75C rating (most do) then the absolute smallest wire that is guaranteed to pass an inspection is 3/0 copper. That treats the sub-panel as a branch circuit and uses standard ampacities.

If your sub-panel is in a single-family residence (that would be a big sub-panel for such) then you might get away with 310.15(B)(6), which would allow you to cut it back to 2/0 copper. That, however, would depend on whether the AHJ considers the sub-panel to be a service or a branch, and there are various attitudes to that depending on your inspector, your city, etc.

How do you check electrical ceiling wiring?

If you appear to have a problem with wiring in ceiling and no ceiling access, you may have to make your own access. One way in a Sheetrock ceiling would be to cut a hole that will fit a quick access panel. This way you won't have to repair and repairing the area.

How many watts is a Kenwood KAC-744 amp?

The Kenwood KAC-744 amp has a power handling capacity of 50 watts RMS per channel at 4 ohms.

Can you use a 300 watt 220-240 watts halogen bulb on 240 watt mains?

Nobody has "240 watt mains". Perhaps you meant "240-volt mains".

You would need to have a lighting or receptacle branch circuit, with over-current protection, in order to use any halogen bulb.

However, if you have a 300 W bulb, it should work nicely in a 15-A or 20-A branch circuit.

Does a bathroom require it's own dedicated 20 amp breaker?

Yes, it is recommended for bathrooms to have their own dedicated 20 amp circuit to ensure there is enough power for electrical devices such as hair dryers and heaters. This circuit should only supply outlets in the bathroom and should not be shared with other rooms.

How two wire 2 light switch up in 1 box?

Tie all the white wires together under a wire nut and push them back in the box. Tie the black incoming power wire and outgoing power wire, if there is one, together under a wire nut with a black wire pigtail. Connect this pigtail to one screw on each light switch. Connect the black wire going up to the lights to the appropriate switch you wish to use to control that light.

Can you wire a 120 volt water heater with an appliance electrical cord to plug directly into a 15 amp outlet?

Circuits cannot be loaded to more than 80% of their rating. So if the wattage rating of the heater is more than 1440 you will need a 20 amp circuit and a 20 amp outlet

Be careful what size cord you use. Most lamp cords and extension cords are not large enough to handle this heater. You must use a cord that has 14 gauge wires or larger for 15 amps and 12 gauge wire for 20 amps.

How many amps can a zero gauge wire handle?

A zero gauge wire can typically handle up to 300 amps of current. However, the exact capacity may vary depending on the specific wire material and insulation used in the wire. It is important to consult the manufacturer's specifications for the wire you are using to determine the exact ampacity.

What size of wire is required for 20 amps 220v over 100 ft?

For a 20 amp, 220V circuit over a 100 ft distance, you would ideally use a 10 gauge wire to minimize voltage drop and ensure safety. A 10 gauge wire can safely handle 20 amps of current and is appropriate for this application.

Can a 13000 btu airconditioner run on 15 amp breaker?

13,000 Btu/hr is 3,809 watts. At 120 volts that is 31 amps. At 240 volts it is still 16 amps, which is why the MINIMUM circuit you would need is 20A at 240V. This gives you the necessary "de-rating" of the circuit (80 percent) for full load bring run constantly.

In other words, you could run 20A x 240V, or 4,800 watts, on a 20A circuit, but that would be the maximum load. Electrical code requires "de-rating" by 20 percent for constant loads. Reducing 4,800 by 960 watts gives you, coincidentally, 3,840 watts, which exceeds the 3,809 of the 13,000 Btu/hr.

Note that A/C units are not 100-percent efficient, so the 13,000 Btu/hr will actually draw MORE than 3,809 watts. The unit will have a label telling you how many amps it requires.

Can you feed 200 amps to 100 amp panel?

There's more to it than just adding some larger wire. You must upgrade your meter, your weatherhead, conduit, etc. Your power company will handle the cable from the pole to your meter. After that...its up to you. 4/0 aluminum or 2/0 copper SE or USE from the meter to panel. This change has to go all the way back to the main power transformer. It's illegal to do this yourself and the power company will not turn your power back on of you do. Call an electrician.

How do you replace a 15 amp breaker in the circuit box?

The breaker will have a black wire connected to it. Turn off the main breaker and then disconnect that black wire from the breaker. The breaker will snap into the main bar. Remove the breaker and install the new one. Reconnect the black wire to the breaker and then install the cover and turn the main breaker back on.

Does a 3-wire prong range cord have a built in ground?

Yes, a 3-wire prong range cord typically includes a built-in ground wire. The ground wire is important for safety to prevent electrical shocks and fires. It is recommended to always ensure that the range cord is properly installed and grounded according to manufacturer's instructions.

How do you wire a light switch that has a black common screw and two gold screws one on each side of light switch and a green screw?

That is called a three way switch. It's used in conjunction with another 3 way switch in another area and they both control a light or set of lights. The black is power and the other two are called travelers that wire to the the other 2 gold screws on the other switch.

A three way switch can be used as a single pole switch by using the black screw and one of the brass screws. You will have to test the circuit to orient the switch so up is on and down is off, if that is what you desire, because it is not obvious on a three way switch.

The green screw is simply your equipment ground. You place your green or bare conductor there.

How do you remove a light fixture but leave the wires behind?

First make sure there is no power to the fixture while you are working on it. After you remove the fixture you need to put one of those screw on plastic caps securely on each wire separately before turning the power back on. Do not touch them together or try to put them both in the same screw cap because you may start a fire.