answersLogoWhite

0

📱

New Electrical Work

Electrical work ranges from the installation of new electrical components to the maintenance and repair of existing electrical infrastructure. It may also include wiring airplanes, ships and other mobile platforms.

4,938 Questions

Is the neutral bus bonded to the equipment ground in a subpanel?

Definitely not. The neutral wires must be put on the neutral buss and that is the only place that they are to be terminated in a distribution panel. In a distribution panel there is no ground buss, it is just the metal enclosure that is used. The ground wire is only used to return a system fault back to the distribution panel to trip that circuits breaker.

<><><>

Distribution panels typically have two "busses"-- one for ground and one for neutral. These are terminal strips where the ground and neutral wires are connected. In some panels, these busses are electrically connected or "bonded." In other panels they are isolated. Most panels come with an optional "bonding screw" that can be installed or removed depending on whether the busses need to be connected. NEC is very specific on when these busses are to be connected. Ground and neutral busses should only be bonded at the main panel where the service enters the building. Other distribution panels will have separate ground and neutral busses and they should be isolated electrically--connecting these is a commonly seen mistake.

I believe the question refers to the case where the two busses are properly bonded together, so are electrically equivalent. Then is it acceptable to have some ground wires on the neutral bus and vice-versa. Electrically it will work, but code or electrical inspectors may deem it to be confusing or sloppy practice and reject the installation.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

What determines the size of a main breaker distribution panel?

You'll need to know what the total current demand is for the circuit, then select the circuit breaker that will take the load without tripping, i.e. its rating will have to be equal to or larger than the demand. There are other factors to consider, but for domestic installations (in the UK) you'd normally install 'B' Type MCBs. If this answer hasn't clarified things, then you need to seek the services of a professional electrician.

What can you use 10 gauge wire for?

ten gauge wire is used for high current circuits. in home wiring, 12 gauge wire is normally used. 12 gauge wire can carry a maximum of 20 amps. 10 gauge wire on the other hand, is larger and can carry more current. the maximum current capacity of a 10 gauge wire is around 30 amps. one would use this for a stove, hvac or other power hungry device's.

What size wire is needed for 200 amp panel?

If you have a 120/240v service for a home, and you have 4 wires, That is, 2 hots, a neutral and a ground. The National Electrical Code requires a #6 AWG copper equipment ground wire, or a #4 AWG aluminum wire. In addition the wire that connects to the ground rod (that is, the grounding electrode conductor) should be a # AWG copper or #2 AWG aluminum when you are using a 2/0 or 3/0 hot wire. If it is the sole connection to the ground rod, the grounding electrode conductor may be reduced in size to a #6 AWG copper. Keep in mind that your local electrical codes, and other factors unknown, such as, mobile home or commercial applications, may require a more stringent application. Your safety and the safety of others depends on a properly sized and installed grounding system, and should only be installed by an electrician who has a record of experience with this type of installation.

<<>>

The CEC states that a #6 bare copper conductor is to be used for the connection between the ground rod or plate and the neutral connection block of the distribution panel for a 200 amp service.

How do you know what wire is ground on 200 amp service?

On a 200 amp or any size service the ground wire is easily identified. Look in the distribution panel for the neutral bus bar. This is where the service neutral (white wire) is connected to the distribution panel. There you will see a bare copper wire connected to the same neutral bar. This is the ground wire that is connected to the ground rods out side of the house.

What size wire for 110 volt 20 amp circuit 700ft?

I would recommend no smaller than #8awg copper. This is derived by 8awg copper ampacity of 40 amps multiplied by 80% load rating to get 32 amps. Then calculating for voltage drop over this distance shows a drop of 5.9 volts or 2.5% which is negligible so not accounted for. So like i said no smaller than #8awg copper.

Is it ok to exchange a 20 amp breaker with a 40 amp breaker?

No. The 20 amp breaker is probably protecting a #12 wire. Connecting a 40 amp breaker to the 20 amp #12 wire would seriously overload the #12 wire. This means that if the load increased to a full 40 amps the insulation on the smaller size wire would most likely melt off and the wire could short out.

Do you have to change from 60 amp to 100 amp service?

The answer is likely NO. I assume you're talking about a 60 amp subpanel. To upgrade to a 100 amp, the wire size will need to be increased. (replaced with the correct size) This is not a job for amateurs but should be done by a qualified electrician. The typical size wire employed for a 60 amp supply is # 6 awg, whereas the minimum wire size for 100 amp is # 3 awg (which is larger).

Can you use a 20 amp fuse and wire rated for it in a 15 amp outlet?

You can use the wire rated for 20 amps on a 15 amp receptacle but you can not use a 20 amp fuse on any device rated at 15 amps.

This is a tricky part of the code about receptacle outlets, You can use a 15 amp duplex outlet on a 20 amp circuit. (duplex outlet two devices can plug in) If it is a single outlet then the outlet must be rated 20 amp. NEC table210.21(B)(3).

============

A 15 amp duplex receptacle can be wired to a 20 amp rated circuit. This means the breaker OR fuse protecting the circuit can be rated 20 amps if the wire is also rated at 20 amps (12 AWG). --Sparkfighter

What size breaker would you need for a 600 watt light?

A 120 volt, 600 watt light draws approximately 5 amps. In the US, electrical codes specify that continuous load current should not be more than 80% of the breaker rating, so a 10A breaker would be the minimum size standard breaker.

However, if this is a practical situation (as opposed to a basic arithmetic problem), it would be very unusual to put in a 10A circuit. Most residential lighting circuits are designed to carry 15A, even if that is not the immediate requirement. The occupant could decide to increase the load in the future.

Can neutral and ground wires be bonded downstream of electrical box?

Bonding of the neutral or grounded conductor to the earth ground or grounding conductor means that they are mechanically and electrically connected. That is, they have full continuity between each other. In most residential panels, the neutral bar, (where you screw down all of the neutral (white) wires) and the ground bar where you screw down all of the bare copper ground wires are on opposite sides of the panel. They are typically connected mechanically and electrically or bonded with a "crossover" bar which bolts in connecting the two bars. Bonding the neutral and ground is required by the NEC (National Electrical Code) on all panels which have a main disconnect. For example, if you have a typical 200 amp residential panel and it has a main 200 amp breaker or "main disconnect", then the neutral and grounds are to be bonded. If you have a main disconnect panel and the neutral and ground are not bonded, then you should bond them by running an insulated wire between them to connect them. That wire needs to be no less in size than the size of the incoming supply neutral wire in the panel. If you are at all confused, post again and be very specific about your question and someone may be able to answer you.

What will happen if neutral and ground wire is shorted?

Nothing will happen if the neutral and ground wire is shorted. The electrical code makes it mandatory that the neutral and ground are brought together at a common point within the distribution panel. On a 120/240 volt distribution system the ground wire is terminated at the point where the service neutral terminated in the distribution panel. It is usually a double lug the neutral wire connecting into one hole and the ground wire connecting into the other hole. Through this lug assembly there is a machine screw that is inserted through the lug assembly and it screws into the metallic enclosure of the distribution panel. This action bonds the metal enclosure, neutral wire and ground wire bringing the point to a common potential of zero.

How many 160 watt solar panals do you need for a 220 amp home?

Not sure what you mean by a 220 Amp home unless somehow you measured the amperage. More than likely you are saying that your home has 220 volts available which is normal.

A ballpark average whole house wattage is in the range of 30,000 watts or 30 KW. That would equal 188 panels.

Hope you have a big roof facing south.

ANOTHER PERSPECTIVE As you can see from the above numbers, it would be a considerable expense to purchase photovoltaic's based on such a high electrical current usage. The maximum current your home can use would be 220 Amps, which would result in a maximum of 48,400 watts. But the reality is, you have probably NEVER used that much; it's just that the home was designed to be able to use that much if necessary.

To calculate your ACTUAL electrical needs you'd need to find out your maximum KWH usage, and you should be able to get that by taking periodic readings from your electrical meter. Add a comfortable factor and plan to use storage batteries to provide for the big surges and for when there is little or no sun.

That's when it becomes helpful to have someone design the system for/with you.

Understand too that you can reduce your daily KWH usage by using different technologies inside your home; convert to LED bulbs and you can save quite a bit over tungsten incandescent. Convert to a gas range (from electric) and you can save again. Same with a gas dryer, and believe it or not, there are alternatives for AC that can save quite a bit.

Reduce your electrical needs as much as you can before you try to go "all solar", and you won't have to purchase as many panels.

What is the maximum height allowed in CA for the circuit breakers New panels the meter sits physically lower than the heighest breaker and as such the top breaker if the meter is 6 tall is even?

In California, the National Electrical Code (NEC) typically requires a minimum of 6 feet and 7 feet clearance in front of and above electrical panels, respectively, for safety and accessibility. However, local regulations and building codes may have specific requirements that vary. It is best to consult with a licensed electrician or the local building department for precise guidelines in your area.

What size aluminum wire for 100 amp 240 volt underground service 200 feet from transformer?

It depends upon whether you mean 240 volts at the first end or the second end.

Assuming 240 volts at the source, and allowing no more than a 3 percent voltage drop over the 200-foot circuit, at 100 percent load of 100 amps, you would need a #1 copper conductor. You would only have 233 volts at the far end at full load.

Note that if the ampacity of conductors supplying your connection point is not sufficient, the "supplied voltage" on your new extension could be substantially diminished under load. For instance, if you are already 100 feet from the original 240 volts, your extension would have an effective circuit distance of 300 feet, requiring #2/0 conductors.

How can calculate the max amps of wire?

To calculate the maximum amps for a wire, you will need to consider factors such as the wire gauge (thickness), the material of the wire, and the ambient temperature. You can use a wire ampacity chart or an online calculator to determine the maximum amperage the wire can safely carry without overheating. It is important to follow the guidelines to prevent electrical hazards.

What is the current rating of 350 MCM al wire for direct burial?

The current rating of 350 MCM aluminum wire for direct burial will depend on the specific environment and installation conditions. It is recommended to consult the National Electrical Code (NEC) or a qualified electrician for precise calculations and to ensure safety and code compliance.

How many sub panels can you have off an 100 amp 2 phase residential service?

The key is that you still only have 100 Amps to work with. You could have multiple small panels if needed for convenience, but the total capacity for constant load should not exceed 80% of maximum or 80 Amps. Also make sure neutral and ground only bonded together at main panel.

What size wire is needed for carrying 100 amps under ground?

For carrying 100 amps underground, typically a 2-gauge copper wire or a 1/0-gauge aluminum wire would be suitable. It's important to consult with a licensed electrician to ensure the correct wire size based on distance, voltage drop, and local electrical codes.

What size wire do you need for 100 amp feeder single phase running 350' away?

For a 100 amp feeder running 350' away, it is recommended to use 3/0 AWG aluminum wire for a single-phase system to minimize voltage drop. This size wire can efficiently carry the current and maintain proper voltage levels over that distance. It's always best to consult with a qualified electrician or refer to local electrical codes to ensure compliance and safety.

What gauge wire for 10 amps 12 volts dc?

If you're looking for a wire to cover all the areas use 10 guage. Very heavy but will handle most normal vehicle requirements except for extreme areas such as starter/battery cables (1 - 6 guage), and some stereo main amp feeds. You won't need 10 guage in a lot of applications (overkill) but it will cover most areas as I said. 16 guage is good for a lot of vehicle applications (lighting etc..). Check out the area of repair/installation and depending on the amperage needed you select you wiring. Below is a link to a chart you may find usefull. http://www.kayjayco.com/techPractical.htm

How do I wire from a 220 volt 30 amp breaker to a 50 amp receptacle for a Lincoln AC225 welder using ten gauge wire do I wire it the same as I would for 50 amps using two hots ground and neutral?

No, you should not wire a 50 amp receptacle using 10 gauge wire intended for a 30 amp circuit. The wire size should match the amperage rating of the breaker and receptacle to avoid overheating and potential fire hazards. In this case, you should upgrade the wire size to match the 50 amp requirement.

How do you calculate the main fuse for electrical wiring?

Fuse sizing is calculated by the size of the conductor. The conductor is calculated by the amperage to the load.

The above answer is partially right, however in calculating fuse sizes for say a motor load of 10 hp on 208 volts 3 phase. The table in 430.250 list this motor as pulling 30.8 amps. Conductor size would be 30.8 times 1.25 or 38.5 amps. This value would lead you to wire table 310.15(B)(16) and a conductor size of number 8THWN. This conductor is listed for 50 ampacity, however due to the starting current of the motor. A fuse could be sized at 30.8 times 1.75 or 53.9 amps. The next standard size would be 60 amps. the fuse size is above what the conductor is rated for, but because of motor overload protection the conductor is protected. If breakers were used instead of fuses, a breaker would be sized at 30.8 times 2.5 or 77 amps or 80 amp next standard size.

How many amps in 1600 watts?

To know Amps you need to know the voltage and power factor. For a pure resistive load and a normal house voltage of 120 VAC then you just divide wattage by voltage to get Amps. Power factor is a maximum of one for resistive load and decreases with various inductive loads that cause current and voltage to be out of phase.

Example 1: 1600 watts / 120 volts = 13.3 amps

Example 2: 15 amp outlet x 120 volts = 1800 watts

Best guess in your case is 13.3 Amps at 120 Volts assuming a load like an electric heater or incandescent bulbs.