Can 30 amp breaker be put in number 12 wire?
No, the National Electrical Code book (US) limits the current on a #12 AWG to 20 amps.
No, you cannot simply cap one leg of a 240-volt circuit and change the breaker to convert it into a 120-volt outlet. This requires rewiring the circuit to provide 120 volts, including changing the outlet and possibly other components to be compatible with the lower voltage. It's recommended to consult with a licensed electrician to properly convert the outlet.
Can you install 200 amp service Panel in washer Dryer closet?
It is not recommended to install a 200 amp service panel in a washer dryer closet due to potential fire hazards and code violations. The space may not have proper ventilation and clearance requirements for the electrical panel. It is best to consult with a licensed electrician to determine the safest and most compliant location for the panel.
I once put out all circuits in a Hotel In Germany by plugging something in to an outlet in my room. If you are in a Condo there is probably a panel feeding your unit. Your problem might be there instead of the panel in your unit.
What happens when you share 2 20 amp breakers with 1 neutral wire?
if it is (1) a-phase and (1) b-phase then this is the common and preferred wiring method (balanced). if you have two circuits of the same phase sharing the neutral then it is wired wrong (imbalanced). gfci and afci breakers need there own neutrals too. as far as what happens two examples:
A: (balanced system) a-phase carrying 10 amps, b-phase carrying 10 amps, neutral carries 0 amps.
B: (imbalanced system) a-phase carrying 10 amps, a-phase carrying 10 amps. neutral carries 20 amps.
hope this helps. good luck
This is not strictly true. Most residential power is supplied in a single-phase 120/240 volt format and has nothing to do with multiple phases. A single phase transformer secondary winding is center-tapped to provide two segments, each of which is 120 volts to the center tap point, which is grounded. There are then 240 volts between the outside ends of the full secondary winding. If both breakers are fed from the same ungrounded end of the winding, all of the current would pass through only one half of the secondary winding, and hence, through the neutral as well. If two breakers were installed such that they were fed from remote ungrounded ends of the secondary winding, then the only current through the grounded center-tap neutral would be the imbalanced current of the two circuits.
Why would both ground wires and neutral wires be on same buss bar?
Both the earth wire and the neutral originate from the star point of the transformer. The neutral is used to complete the circuit with one phase, while the earth wire is used to conduct any current from the exposed metal body of the equipment to earth and to the star point of the transformer. This is done to protect people and animals in the event of accidental contact with electricity.
Electricity will always follow the route of least resistance. Copper/aluminium has a much lower resistance than the human body. In the event of the live wire making contact with the earthed metal body of the equipment, the earth wire will conduct the electricity to the earth mass. Without an earth wire connected to complete the route of least resistance to earth, the human body will conduct the full load current to earth if you should touch the live metal of faulty equipment. This could result in electrocution
------------
Equipment ground-ING conductors (commonly called "ground wire" or "the ground" and is usually green or bare) and groundED conductors (commonly called the "neutral" and is usually white or gray) are required to be bonded together at the main service panel. It is common practice to put both ground and neutral conductors on the same buss bar in the main service panel which effectively bonds them together. Then, if the incoming neutral and outgoing grounding electrode conductor (that's the conductor that is connected to building ground, or ground rods, and/or water pipe ground) are connected to the same buss then everything is bonded together and grounded as required.
Ground wires and neutrals should not share a buss bar and should be isolated from each other in any sub-panel.
If all the breakers in your house added up to 765 amps how big of a generator would you need to buy?
You would size the generator to match the main breaker size rather than on the sum of all the breakers. The main breaker size depends on the specific model of the circuit breaker panel - 100 Amps is typical for a house. The main breaker protects the circuit panel's bus bars from overheating, and the bus bar size is what limits the maximum power through the panel. Power = Volts x Amps, so a 100 Amp panel at 240 Volts could be operated by a 24,000 Watt (24 kW) generator. That's a pretty big generator in household terms, so often only a subset of the circuits would be allocated to the generator. Or, you just be careful not to turn everything on when using the generator. The actual Watts used depends on what's turned on, not the generator size or total capacity of all the circuit breakers. If you turn on too much stuff with an undersized generator, the generator's overload protection will trip and cut it off. Or if you load all the circuit breakers to capacity the main breaker will trip. In addition to these basic considerations there are a considerable amount of electrical codes governing connecting a generator to your house. The major one is to have a switch that prevents connecting your generator to the utility input, which precludes you from inadvertently energizing the utility lines.
Is 15 amp breaker enough for a gas furnace?
Yes. It should be a dedicated circuit from the distribution panel. There should also be an emergence shut off switch outside of the furnace area . This switch allows you to shut the furnace down from a remote area if a malfunction occurs at the furnace.
How can you tell if a neutral bar is bonded or not to the panel?
Take a look at the junction where the ground wire and the neutral enter the panel. There you should see a green grounding screw that protruded through the neutral block and into the metal enclosure of the distribution panel.
Which is better a MTX jh600 amp or a hifonics Brutus BXI1610D amp?
Both amps are good choices for a car audio system, but the Hifonics Brutus BXI1610D amp is generally considered more powerful with a higher wattage output. If you prioritize power and performance, the Hifonics amp might be the better option for you.
Can you straight wire a sump pump to the breaker box?
Yes. Check local electric codes to see if a disconnect is required at the sump pump. One way is to wire a single 15A circuit to an outlet for sump pump. Then the disconnect is just to unplug the pump for service.
Can 12-2 600v wire handle 20 amps?
Yes, a 12-2 600v wire can handle 20 amps. This type of wire is typically rated for 20 amps in residential electrical systems, making it suitable for that current load. However, it's essential to follow local electrical codes and guidelines to ensure proper installation and safety.
Will a 800 watt generator have enough power to operate a 90 amp welder?
No, unless you can set it low and can be assured that it wont use more than say 4000watts, the welder might momentarily use more power than what you set it to, it should not wreck the welder i would imagine unless it is a fancy mig welder or something, set the welder low you should be fine but for high end use she should be firing out 8 or 9kw so keep it low if you must.
Why does Neutral amps increase after shutting off breaker?
The increase in neutral amps after shutting off the breaker could be due to a phenomenon called neutral leakage. This occurs when there is an unbalanced load on the phases, causing some current to flow through the neutral even when the breaker is off. It may also indicate a fault in the electrical system that needs to be investigated by a professional.
How to compute the size of wire with respect to the distance from circuit breaker to the load side?
Normally wire is sized by the amperage of the load. In this case the wire size is calculated by knowing the length of the run to the load and the amperage of the device to be connected. By knowing the length, the wire size has to be increased to allow for voltage drop over the distance from the supply to the load.
30 amps on a 250 volt outlet can handle how many watts?
A 30 amp circuit on a 250 volt service could handle up to 7500 watts. That's if it's actually 250 volts coming in. You should check that with your meter.
What size wires for 30 amp circuit?
If you had to ask this question here you need to learn more about your local wiring code re all the items you must use for a new household AC power range circuit.
Serious home fires can result from incorrectly installed new circuits.
So that the new installation is safe and legal - and complies with the terms of your home insurance policy - you must use the correct type and size of cable, the correct type of circuit breaker and the correct type of wall outlet.
From the local wiring code, a licensed electrician will know which size of wire to use because the answer depends both on the current to be carried (amps) and on the length of the run from the breakers on the main supply panel to the place where the outlet for the kitchen range is to be fixed.
For your own personal safety -- as well as your family and anyone else who may use the new range circuit in the future (such as if you sell your home) -- the best advice anyone can give you is call a licensed electrican to do the job. He will be able to advise you about the right wire size for the length of run, the types of breakers (main panel and GFCI), the outlet and anything else which may be necessary for your new range circuit to comply with the wiring codes in your locality (town/state), and he would install them safely for you.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
If you have a 400 Amp service using 500 MCM What size grounding electrode conductor is required?
For a 400 Amp service with 500 MCM conductors, the minimum size grounding electrode conductor required would be 3/0 AWG copper or 250 kcmil aluminum based on the NEC Table 250.66.
What gauge wire do you use for a 20 amp circuit?
The NEC table 310.16 does not go that small. If there is a code requirement in your location, you must follow it.
Otherwise, a recommendation I found suggests 11A for short in-chassis wiring, and no more than 1.5A for longer power distribution wiring.
With wire this small, your current will probably be limited more by maximum permissible voltage-drop than a safety rating.
you can only have one dimmer, the other switch needs to be not a dimmer. the green wire is ground, it connects to a bare copper wire found in the box, or to the box itself, if the box is metal. the black wire is"common" it either connects to the wire found in the box that has power in it or to the black wire that goes to the light. the 2 red wires are"travelers" they connect to the wires found in the box that go from switch to switch. if you don't know how to check which wire does what( continuity), it is possible to keep changinging the connections until the switch works. you will want to do this with a conventional switch, and install the dimmer afer you identify what wires are travelers and wich are common. you will destroy a dimmer switch by searching for the right connection. once you have identified the common wires, it will be on the black screw of a 3way switch; you can put that wire on the black wire of the dimmer. one red goes on one traveler, the other on another traveler. there might be a white wire in the box, if it is connected to other white wires and not to the switch, leave it alone. if a single white wire is connected to old switch, it may be a traveler.you will connect a red dimmer wire to this. opening the other switch location will show you if the white wire is used as a traveler.the black wire has to be either power coming in, or the wire going to the light. the reds are just connecting the 2 switches.
How many amps does a 1.7 cu.ft compact refrigerator use?
On average, a 1.7 cu.ft compact refrigerator typically uses around 1-2 amps when running. However, depending on the specific model and manufacturer, this number may vary slightly. It is recommended to check the product specifications or the label on the refrigerator for the exact amperage information.
Outlet stopped working and it is not a GFCI?
First, check the circuit breakers; make sure they are all ON.
Find out if any other outlets on the same breaker are working; it's always possible that a breaker is faulty.
If the breaker is on and everything else on the circuit is working, it could be as simple as a poor connection inside the outlet.
Also even though the outlet is not a GFCI, it may be fed from a GFCI outlet. Check near by outlets to see if any are GFCI and are tripped.
Can you run a 220 volt hi-fi amp on 240 volts?
The terms 220 volt and 240 volt are used interchangeably. The voltages coming in from the power company can vary between these numbers, and possibly higher or lower. So yes, it's fine.
Another Answer
The voltages which you quote are 'nominal' and within the allowable tolerance of a standard European nominal voltage of 230 V.
Conduit wiring is a method of electrical wiring where insulated conductors are run within metal or plastic conduits for protection. The conduits help prevent physical damage to the wiring and also provide a higher level of safety by reducing the risk of electric shock or fire hazards. This type of wiring is commonly used in industrial and commercial buildings where additional protection is necessary.