answersLogoWhite

0

📱

New Electrical Work

Electrical work ranges from the installation of new electrical components to the maintenance and repair of existing electrical infrastructure. It may also include wiring airplanes, ships and other mobile platforms.

4,938 Questions

Can you use a 150 watt light bulb in a 75 watt rated fixture?

Yes.

The rating of bulb fixtures is there to discourage people from using bulbs that create too much heat. Obviously, a 75 watt bulb will produce less heat than a 150 watt bulb so it's quite safe to use the smaller bulb.

If you overheat a lighting fixture you can cause premature failure and possibly even a fire.

My 110 washer will work my 220 dryer will work. why will it throw breaker when both are plugged in on separate breakers?

Your 110 volt washer receptacle sounds like it is not a dedicated circuit directly fed from the distribution panel as it should be. It sounds like someone has tapped off of one side of the dryer receptacle hot and neutral terminals and run them to the receptacle for the washer. If true, this would have been done in the back side of the dryer receptacles which is located in the wall. You best get it checked out because it is likely the wire feeding the washer receptacle is a #14 rated at 15 amps and is undersized for a 30 amp breaker. A #10 wire has the capacity to be connected to a 30 amp breaker which you should find the dryer's connection to be.

In an outlet which wire do you connect to the brass silver and green?

Answer for USA, Canada and countries running a 60 Hz power supply service. Looking at the duplex receptacle from the front side directly on, you should see a larger blade hole (silver) on the left, smaller (brass) blade hole on the right and a U shaped ground blade on the bottom. The white wire connects under the left (silver) coloured screw, the black wire connects under the right (brass) coloured screw and the green or bare wire under the green ground screw.

What way does the ground plug on a receptacle face?

The ground plug on a receptacle typically faces down. This allows for the ground prong on a plug to make contact with the ground pin in the receptacle, providing a safe path for excess electricity to be directed away from the device in case of a short circuit.

Minimum breaker size 60 horsepower motor?

A 60 horsepower motor typically requires a minimum breaker size of 100 Amps for normal operation. It is important to consult the motor's specifications or a licensed electrician to ensure the correct breaker size for safe and efficient operation.

100amps how many volts?

These are two different entities. Its like asking how much water will flow with pressure. With the following formula W = Amps x Volts you can see the relationship they have with each other, the end product resulting in Watts.

You have 220v wiring 2 hots 1 common from breaker box to pool wiring box Common is wired to equipment ground is that correct?

Correction - 2 hot (2 * 120) = 240 volts

common - neutral

U R 100% correct

PS: 240 motor for pool ? hmmm, learn something everyday The cable from the breaker box to the pool should be a 3 conductor. In that 3 conductor cable there should be a bare ground wire (the ground wire is not included in a cable wire count). The pool ground should be connected to that bare wire, not the white neutral. This bare ground wire is then grounded back at the breaker panel to provide a direct path to trip the breaker in case of a short circuit. Code requires a GFCI ahead of the pool load to detect ground faults. See related links below on GFCI's

What size of cable do you use for wiring sockets?

The size of branch circuits is directly related to the amperage draw of the load. The load amperage governs the size of the conductors that are used to feed the load. Also by the same token, the breaker that feeds the supply voltage is governed by the amperage draw of the load. So to answer the question, the wire sizes could be any number of different sizes depending on the amperage they have to carry.

What wire gauge should be used for 9 amp maximum?

A wire gauge of 16 AWG is typically suitable for a maximum current of 9 amps. However, you may also consider using a gauge of 14 AWG to provide some extra margin for safety and reduced voltage drop over longer distances.

If a 10 ampere fuse blows constantly it should be replaced with 15 ampere fuse?

Most definetly not. If a ten amp fuse has been used to protect a circuit, then it has been rated by guidlines to be the most that that circuit can hold. If you put a 15 amp fuse in its place, you are effectively allowing more current to flow through the cables than it is rated for, which will lead to excessive heating in cables and possible fire. If your fuse is constantly blowing, it means there is most likely something wrong with the cables, like a short circuit. This is extremely dangerous. Call a qualified electrician to fix the problem

Why do two separate breakers control the same outlets?

The only time 2 beakers are run to one outlet is if the outlet is 240V. The breakers should have handle-ties connected to them to ensure that both breakers trip in the event of an overload. Nope its not 240 either,cause it continues to other outlets the same way.and can plug 110 accesories into them. I have come accross this everywhere. In rooms without a ceiling light, one half of a duplex receptacle is a switched lighting circuit and the other is a always on receptacle.

What are some of the price qoutes on a 2800 sq ft house to rewire?

$/sq. ft.

5.27 =average

5.38 =median

16 =number of samples

0.88 =correlation, sq ft & kilobucks

half the cases are between

4.15 $/sq ft

and

6.64 $/sq ft

so 2800 x 5.27 = 14800 +/- 3000

What does a GFCI outlet look like?

If you live in a country which uses them, just look at a wall outlet in your apartment or house! But, if you live elsewhere, then take a look at the Related Questions and Related Links shown below. A single phase 120V duplex outlet (two "separate"receptacles) has a smaller prong/blade (for the black hot wire), a larger blade (for the neutral, a white wire) and of course the semi-circular or "tunnel" ground hole (for the green wire to the wall box) that makes up the outlet.

120V outlets come in two sizes for normal residential 15A & sometimes 20A. Typically you will see a 15A receptacle. You can go to a Home Depot or Lowes (or any electrical hardware store) and physically look at one closeup.

How can you tell if the ground wire is approriately bonded to the neutral and the cabinet at the service box?

Ground wire can be appropriately bonded to the neutral and cabinet at the service box by connecting the neutral and ground wires from the feeder wires to the neutral bus bar and the ground terminal located on the same cabinet at the service box. White wire (neutral) must be connected to bus bar and bare wire must be connected to ground terminal in the same cabinet.

Do you need a ground wire for 220v motor?

All electrical equipment needs to have a ground wire on it. This is the conductor that helps protect you in case of short circuits. It provides the electricity with a path to ground during the short circuit. Without this return path there is the possibility that the equipment could come up to the working voltage potential. If that happened and you touched the equipment you would become the path to ground conductor with killing results.

Now, to answer your question - The appliance will operate without the third wire, just not safely. A 220v appliance only needs two legs of 110v each to run. These legs need to be from different phases of electricity. We normally use alternating current at 60hz; so each phase changes polarity from positive to negative 60 times a second. As long as your 220v wires are connected to different buses in your service panel, one leg will always be positive and one negative (changing 60/sec). But don't do this. Add the third wire for safety. It is required by code.

What is a 220 line?

A 220 line typically refers to a 220-volt electrical supply line used for appliances or equipment that require higher power consumption. It is commonly used for larger appliances like electric dryers, ovens, and air conditioners.

How many amps is 10000 watts?

kilo... means x1000 so... 1000000 or a Million Watts, or 1to the 6 booyakasha!

You disconnected a 240 volt wall heater now connecting the wire to a receptacle Is white wire hot in that case?

The white wire in a 240 circuit may be hot depending on exactly how it was wired. There are 2 120V circuits in a 240 v circuit and if all the electrician had was a cable with black and white then he very well may have used white as the other hot wire leaving 2 hot wires and no neutral. If a separate neutral was not run for the 240 circuit then a new cable may have to be pulled from the breaker panel that has a neutral. If you have the skills with a meter, you can check. If you are going to do this work yourself make sure that you shut off the main disconnect to the electrical panel and just use a flashlight to see the work you have to do. That said, it is common practice to use a two wire to feed wall heaters. You will find that the two wires are fed from a 2 pole breaker. Keep in mind that there should not be any other heaters on the circuit, if there is the other heaters will not work. In the electrical panel the white wire has to be taken off the 2 pole breaker and terminated onto the neutral buss. The other wire on the 2 pole breaker should be taken off and put into a single pole 15 amp breaker. Now on the receptacle end white wire to the silver coloured screw and black coloured wire to the brass screw.

How do you work out how many amps a forty watt bulb uses?

To calculate the amperage of a 40-watt bulb, you need to use the formula: Amps = Watts / Volts. If the bulb operates at 120 volts (standard for US households), the amperage will be 0.33 amps (40 watts / 120 volts).

How do you wire pot lights?

To wire pot lights, first turn off the power to the circuit. Run electrical cable from the power source to the first light fixture, connecting the black wire to the black (hot) wire and the white wire to the white (neutral) wire. Continue wiring the remaining lights in the same manner, daisy chaining them together. Finally, connect the ground wires to the ground screw in each fixture and secure all connections with wire nuts before turning the power back on.

What is the max safe amps for 14 gauge wire?

The maximum safe amperage for 14 gauge wire is typically around 15 amps in most household wiring applications. Exceeding this amperage could lead to overheating of the wire and pose a fire hazard. It's important to always verify the specific requirements with the National Electrical Code or a qualified electrician for your specific application.

Where are fuses found in the house?

== == In most houses, the fuse box is usually located on the wall in the garage or basement. Typically, it's a rectangular gray metal door with switches inside. == == <><><>

The initial answer is helpful, in that MOST service panels are in the basement or garage.

The easiest way to locate your service panel is to go outside and look to see where the electric company provides power to your house. For the sake of simplicity, we will assume a detached single family home.

There will be an electric meter [flat faced glass globe]installed in a grey or aluminum metal box. It can be located by following the wires that come in overhead from the power company lines. If your service is underground because you live in a newer housing development, the meter will be on either side of the house, toward the front, or on the front wall.

When you locate the meter, the panel will usually be RIGHT behind it in the garage or basement [as suggested earlier]!

If your house is built on a poured slab, there may be a second box, a disconnect switch with a breaker or fuse. In this case, the panel for your home could be literally ANYWHERE except the bathroom, depending on how old the house is. Many older homes have an interior disconnect near the meter and a fuse panel at the top of the basement stairs or installed between the basement ceiling joists.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

Can you use 10-3 with 30 amp breakers at 90 foot to run a 225 amp max arc welder?

No, using 10-3 wire with 30 amp breakers is not suitable for running a 225 amp arc welder. The wire size and breaker amperage should be appropriately matched to the current requirements of the welder to ensure safety and prevent overheating of the wire. In this case, a larger wire size and breaker amperage would be needed to support the 225 amp maximum draw of the welder.

You have a red box and a black box they are exactly the same size the red box is heavier than the black one what does it tell you about physical properties of the boxes?

The red box likely has a different material composition than the black box, with the material in the red box likely being denser. This difference in density causes the red box to be heavier despite being the same size as the black box.

What size breaker for 10 awg wire?

For a #12 copper wire, in most areas of the US, branch circuit overcurrent protection shall not exceed 20 amps.

Check your local electrical code with any amendments to be sure! As always,

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS. If you do this work yourself, always turn off the power at the breaker box/fuse panel BEFORE you attempt to do any work AND always use a meter or voltage indicator

to insure the circuit is, in fact, de-energized.