SYNCHRONOUS GENERATOR CAPABILITY LIMITTsynchronous generator capability limiters are as follows

1.MVA or armature current limit of generator: this depends on the cooling system of generator so that temperature rise in generator is limited to safe value.depending on cooling system effectiveness and temperature limit for the insulation used in generator, MVA limit is decided.

2.MW limit: this is determined by the power output capacity of prime mover to which generator is connected.

3.rotor angle limit: this is related to stability of generator which is synchronised to the grid.ideally this could be 90 degree, but in practice this is limited to70 degree so as to have better stability margin in transient and dynamic condition.the generator falls out of synchronism in trasient condition if rotor angle is close to 90 degree.

4. rotor current limit: the field winding placed on rotor has got limited current carrying capacity, beyond which it may burn .so this limit is used.

all these limitters make capability curve of g generator within which the generators operates safely

r. k.niranjan

email id: rkniranjan@Yahoo.com

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How do you define the synchronous generator capability limiters?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Define synchronous lesion?

lado


Define generator short circuit ratio?

Checked Stephen J. Chapman's Electric Machinery Fundamentals page 287. It says: Short Circuit Ratio (SCR) for the synchronous generator is the ratio of the field current required for the rated voltage at OPEN circuit to the field current require for the rated armature current at SHORT circuit.


How does the generator constructed?

Please re define your question's terminology.


The two attributes that define a threat in OPSEC are?

The capability of an adversary coupled with intention to affect friendly operations.


Is it the same meaning of credit and loan?

No. A loan utilizes one's credit, but the loan does not define one's credit capability.


What do relationships define when one capability supports another?

purpose, effected desire and scope


How do you determine transfer function of a synchronous generator?

This is just one of the ways:Choose the variables couple in question defining the SISO form of the system. Write out the state space matrix commonly denoted as "A" of the synchronous machine. Calculate the eigenvalues of that matrix. Then calculate the residues of the matrix with respect to the selected SISO system (the chosen variables in question define the input matrix B and output matrix C). The eigenvalues are the zeros of the transfer function while the residues are the constants in the fractionally partitioned form of the transfer function.The matrices I was talking about define the linearised system in the form :dx/dt=Ax+Buy=CxFor a more thorough explanation seePower System Stability And Control By Prabha Kundur


A new capability need has surfaced to modify an existing U.S. command and control system so that it can exchange information with a system operated by a European ally.?

Define and Control Interfaces


Define the term critical field resistance?

critical resistance is the maximum resistance beyond which the generator failed to exite. it can b found form the occ of the generator.


Define Global Software Development?

Global Software Development (GSD) is "software work undertaken at geographically separated locations across national boundaries in a coordinated fashion involving real time (synchronous) and asynchronous interaction".


What do support relationships define when on capability supports another?

purpose, effected desire and scope


What can happen if a utility-sized electrical generator has an ungrounded neutral?

What you need to define is the statement "utility- sized electrical generator". It depends on what the generators output is used for as to the way it is internally wired. In some configurations there is no neutral to ground as in a Delta configuration.If the generator is configured for a Wye output and the neutral centre tap is not grounded there will be a floating voltage between the generator and the utility system ground. It is for this reason that the generator's neutral point is grounded to bring the floating voltage down to zero volts to ground.