Thank You for this Great Site...*
A normal transformer should not blow the primary side breaker when it is not connected to a load on the secondary. If it does, something is wrong. Check for shorted or burned windings. Make sure that it is indeed disconnected from the load - it might still be connected to something that is also presenting a fault.
When the load current exceeds the SCR current rating, SCRs are connected in parallel to share the load current. Further the holding currents of the devices should not be so much different that at reduced load current one of the device gets turned-off because of fall of current through it blow its holding current value.
It means to have an orgasm and it usually refers to men having an orgasm.
The 5 amp fuse has many wattages that it can protect. It depends on the voltage of the circuit that the fuse is protecting. Use the following formula, Watts = Volts x Amps. For example 120 volts x 5 amps = 600 watts, 240 volts x 5 amps = 1200 watts, 480 volts x 5 amps = 2400 watts and 600 volts x 5 amps = 3000 watts.
The starting current of a motor is usually much higher than the normal current of that motor's full load condition. So for the protection purpose, in case of selecting fuse, the fuse has to be rated 2-3 times the full load of the motor so it does not blow on start. An induction motor will have a starting current of around 6 times FLC.
Blow my load.
It'll soon be time to blow out the candles.
Cover and secure the load.
Not anytime soon
A: a transformer will follow the rule of input output ratio with no load. As soon as a load is applied there will be changes in the ratio
they go hard and you blow your load.
depends on the wattage of the hair dryer. most are 1250 to 1600 watts so a 20 amp gfci circuit would be able to carry the load of a standard hair dryer.
As soon as you put a load on the bearing the noise will go away, so I would sugest that you change the bearing A.S.A.P so you don't do any more damage as soon as you put a load on the bearing the noise will go away, so I would sugest that you change the bearing A.S.A.P so you don't do any more damage
not exactly sure what is going on, one theory assuming there is no change in the load on the circuit is you are drawing close to the maximum load for the 12 v circuit. probably 10A. the fuse blows due to the heat generated by the electrical current flowing through it. so with a load of 10A it may take an hour for the fuse to get hot enough to blow. if you draw a larger current the fuse will blow quicker and a short will cause it to go instantly.
There must be a short in the system somewhere that causes the fuse to blow.
Depending on the context it is used in it could mean one of the following:Cocaine (most commonly is slang for cocaine)"Blow job"to "blow" a load - to ejaculate
It will draw over 18 amps and will blow a 15 amp fuse.