(volts x amps)/1000
AnswerThe 'volt ampere' (V.A) is the unit of measurement for apparent power of a load, and is the product of the supply voltage and the load current. To convert volt amperes into kilovolt amperes, divide by 1000.
to calculate kva rating of single phase transformer:
kva rating= Q =Vp * Ip * 10^-3
where,
Vp= terminal voltage of primary winding
Ip= current of primary winding
so,
Q = V * I *10^-3
=2.22 * f * phi *Kw *Aw *delta * 10 ^-3
where,
f= frequency in hertz
phi= maximum flux in weber
Kw=window space factor
Aw=window area in m2
delta= current density in A/m2
but,
phi (maximum flux) =maximum flux density * net area of core
=Bm * Ai
so,
Q=2.22 * f *Bm * Ai *Kw *Aw *delta * 10 ^-3 kva
to calculate three phase transformer,
Q= 3.33 *Bm* Kw* Aw*Ai * 10 ^-3
it's the transformer capacity power
AnswerIt's the product of the transformer's secondary rated voltage and rated current. And the correct symbol is kV.A.
http://www.federalpacific.com/university/transbasics/chapter2.html
Rating for DG set and any of electrical machines is calculated in KVA. KVA is calculated as KW/pf. One can calculate the required KVA for DG set with this formulation: (KW/pf)/load rate. For example KW=110, pf=0.8 and one loads the DG at 75%, so KVA= (110/0.8)/0.75=185 KVA.
kvar = kva*sin@
kvar = kva*sin@
kV is kilovolts, kW is kilowatts, kVA is kilovolt amps and kVAR is kilovolt-amps reactive. A common formula is kVA-squared = kW-squared + kVAR-squared.
Power Factor = KVA/KW. This has no unit. Its value is always 1 or less.
Power requirements are measured in KVA, which stands for Kilo-Volt-Amperes. To calculate the amount of power you require you would use the following formula. KVA = Volts * Amps / 1000
Amps * volts / 1000
You cannot convert them. KVA is a measure of power, while amperes are a measure of current.
kvar can be calculated as follows the a product KVA andt the sine of the angle between the KVA and KW.
1 HP = 0.9325 kVA 1 KVA = 1/0.9325 HP
Rating for DG set and any of electrical machines is calculated in KVA. KVA is calculated as KW/pf. One can calculate the required KVA for DG set with this formulation: (KW/pf)/load rate. For example KW=110, pf=0.8 and one loads the DG at 75%, so KVA= (110/0.8)/0.75=185 KVA.
kvar = kva*sin@
kvar = kva*sin@
The formula you are looking for is , A = kva x 1000/Volts.
If you multiply kVA by Power Factor (Ranges from zero to one) you get watts which is effective power.
Amperes when kva is shown. The formula is, Amps = kva x 1000/1.73 x volts.
The formula is that kW^2 + kVAR^2 equals kVA^2 or if you prefer, the kW and the kVAR are the two sides of a right angled triangle and the kVA is the hypotenuse. So here you have a 3-4-5 triangle times 140, in other words 420-560-700, and the kVAR is 420.