To answer this question, wire size is rated in the amount of amperage that it can legally carry. Fuse sizing is based on the amperage that the wire carries.

The formula to find amperage when the HP is known is I = HP x 746/1.73 x E x %eff x pf.

A standard motor's efficiency between 5 to 100 HP is .84 to .91.

A standard motor's power factor between 10 to 100 HP is .86 to .92.

Amps = 30 x 746 = 55950 = 55950/ 1.73 x 415 x .87 x .87 = 55950/550 = 101 amps.

The electrical code states that a motor conductor has to be rated at 125% of the motors full load amperage. 101 x 125% = 126 amps

A #2 copper conductor with an insulation factor of 90 degrees C is rated at 130 amps.

Fusing for this motor will be, non time delay fuse 300 amps, time delay fuse 175 amps or a circuit breaker rated at 250 amps.

User Avatar

Wiki User

11y ago

What else can I help you with?

Related Questions

Can you run a 415v 3 phase motor on 480 3phase?

It would not be immediately dangerous but there is a possibility of overheating with the 9% overvoltage so it isn't a good idea unless the motor is lightly loaded and watched very carefully. The safe voltage range should be marked on the motor.


Power a 415volt motor with 480volts?

in low voltage connection in wye (star conncetion) 415v high voltage connection in delta 480v


How much current per phase will a 18KW motor draw on 415 v?

To calculate the current per phase, use the formula: Current (I) = Power (P) / (Square Root(3) x Voltage (V)). For an 18kW motor at 415V, the current per phase will be: 18,000W / (1.732 x 415V) ≈ 24.5A per phase.


Can you use a 415v motor in a 240 v socket?

No you can't use a 415v motor in a 240 v socket.


What is the full load amps of a 3 phase 415v 14.7kw motor?

0.073 assuming 0.85 power factor


Can you convert 415v 3 phase to 230v single phase?

415V 3 phase is the line to line voltage. The line to neutral of this supply is 230V single phase. Therefore you use one of the phases and the neutral.


What is the calculation formula for rewinding a 415v 3 phase single speed motor to 2 speed operation?

5 hp moto 1500 rpm 3 phase winding calculation


Can a 415V 3-phase 50 Hz motor run on 380V 3 phase 60 Hz?

Yes, it will run drawing little more extra current in similar conditions. The motor is expected to be running in lesser rpm as well.


What you basically want is will each phase take 26 Amps current for 15HP 3 phase 415VAC motor?

Yes, for a 15HP 3-phase 415V AC motor, each phase will draw approximately 26 Amps of current when running under normal operating conditions. This results in a total current draw of 26 Amps per phase for the motor.


I have a three phase device on a 415v 50 Hz supply drawing about 100 amps. If I put that device on a 380v 60 Hz supply how will the frequency difference effect the motor?

That is a big motor, 70-80 HP and you should check with an electrician. It depends on what type of motor it is and what type of load it is driving.


Can a 415v 50hz motor run on 380v 50hz?

no


What is the value of 3 phase voltage in India?

In India its 415V, 50Hz.