1 MW is 1000 kW therefore 10 MW is equal to 10,000 kW.
Kw can be calculated from volts be using the formula p=(voltage)square/resistance*1000
If a load takes 50 kW at a power factor of 0.5 lagging calculate the apparent power and reactive power Answer: Apparent power = Active power / Power Factor In this case, Active power = 50 kW and power factor = 0.5 So Apparent power = 50/0.5 = 100 KVA
KVA is the vector sum of real and reactive power; put differently, KVA at a specified power factor will tell you how many KW you have: KW = KVA * pf You must provide a power factor or power factor angle (if angle, replace pf with cos (pf) in above equation) or total reactive power to calculate.
Around 80 m tower height + 40m radius
In a DC circuit Power (P) in watts is equal to Voltage (E) times Current (I). 1000 Watt = 1 kW P = EI thus I= P/E For kW then I = (P x 1000)/E Example with Power of 2 kW and Voltage of 250 V DC: I = (2000/250) = 8 Amp
p.f=kW/kV.A
condenser capacity(kw) = compressor cooling capacity (kw) + compressor input (kw) power condenser capacity(kw) = Pf + Pa
To calculate the power in kilowatts (kW) from amps (A), you also need the voltage (V). If the voltage is 120V, then 500A would equal 60 kW (since Power (kW) = Current (A) x Voltage (V) / 1000). However, without knowing the voltage, it's not possible to calculate the power in kilowatts.
Kw can be calculated from volts be using the formula p=(voltage)square/resistance*1000
If a load takes 50 kW at a power factor of 0.5 lagging calculate the apparent power and reactive power Answer: Apparent power = Active power / Power Factor In this case, Active power = 50 kW and power factor = 0.5 So Apparent power = 50/0.5 = 100 KVA
The kW rating of a transformer can be calculated by multiplying the kVA rating by the power factor. For example, if the power factor is 0.8, then the kW rating of a 100 kVA transformer would be 80 kW. You can also use the formula: kW = kVA x power factor.
To calculate kilovolt-amps (kVA) when kilowatts (kW) is known, you can use the formula: kVA = kW / power factor. The power factor is the ratio of real power (kW) to apparent power (kVA) in an electrical circuit.
Power Factor = KVA/KW. This has no unit. Its value is always 1 or less.
To calculate kWh from kW and running hours, you can use the formula: kWh = kW x hours. Simply multiply the power in kilowatts (kW) by the running time in hours to get the energy consumption in kilowatt-hours (kWh). This formula helps you determine the total amount of energy consumed by a device or system over a specific period.
The power of the engine of the Renault 10 1967 is 30.9 kW (41.4 hp)
KVA is the vector sum of real and reactive power; put differently, KVA at a specified power factor will tell you how many KW you have: KW = KVA * pf You must provide a power factor or power factor angle (if angle, replace pf with cos (pf) in above equation) or total reactive power to calculate.
what formula is used for calculate flow rate of pump vs kw