What is described as a device with specific resistance and is used to control current?
A current shunt is a device with a very low resistance, usually around one ohm. The exact resistance of the shunt is printed on the device for reference, and it is often slightly higher or lower than nominal, for example a 1 ohm shunt may actually have a resistance of .99986 ohms or 1.0002 ohms. A current shunt is not used to control current, however, so I do not know if this is the device you are asking about. It is used to measure current by using a precision voltmeter to measure the voltage drop across the shunt, and then using ohms law to calculate the current. Voltage (Volts) divided by Resistance (Ohms) equals Current (Amps). When the shunt is placed so that it interrupts a circuit, (placed in series), the current flowing in the circuit can be accurately measured with the shunt, without changing the values in the circuit enough to affect it. Many shunts of this type have a large heavy duty resistor that does not overheat easily. The shunt should also have a max current rating listed on it.
What kva generator to run 15Hp motor?
1HP = 746 watts
15 HP = 11190 watts = 11.19 kW
You would need a generator of at least 13kW.
UPS Distributor for 15 Years.
What winding of a current transformer carry more current?
Primary winding carry more current.
We measure the current in one single wire, so no of turns are 1, in secondary the no of turns are higher. so, obviously it has higher voltage then this wire. so, finally as per the transformer rule the secondary carry lesser current than primary.
What is the principle of operation of universal motor?
Similar to DC permanent magnet motor (which I'm assuming you understand); except the stator is not a permanent magnet but an electromagnet. There are 2 separate coils on the stator, which are connected in series with the brushes and armature:
supply ----- stator segment --- brush - armature - brush --- stator segment ----- return
Since the stator coil segments are wired in series with the armature, reversing the supply will *not* change the direction of rotation; as both magnetic fields will reverse together. (But a reversing switch affecting only the armature *will* reverse the rotation.) And since the motor will always turn in the same direction independent of the supply polarity, this means it will work equally well from DC or AC; and the supply frequency will not affect the rotation speed.
How many kva per leg on 3 phase 240v 50 amp circuit?
Assuming that the figures you supply in your question are line values, and not phase values, and each line current is identical, then you can find the total apparent power (in kV.A ) by applying the following equation:
apparent power = 1.732 VL IL
If, then, by 'per leg', you mean 'per phase', then all you need to do is to divide your answer by 3.
Incidentally, the correct symbols are 'kV.A', not 'kva', 'V' not 'v', and 'A' not 'amp'. lin
What is the minimum resistance when megohming 13.2kv transformer?
A megger would not be suitable for testing insulation resistance of a 13.2-kV transformer, as the transformer's voltage rating is significantly higher than the output voltage from a megger.
How many poles in a six thousand RPM motor?
It depends on the frequency. At 60 Hertz, with an ordinary two pole synchronous motor, you cannot have an RPM that is greater than 1800, so a six thousand RPM motor has to have a different power supply.
Why do power lines have a slack?
Overhead lines have 'sag' (not 'slack') because the conductors need to be able to expand and contract as the temperature changes. If sag isn't built into the design of the line then, when the conductors contract, they will put undue lateral strain on the supporting poles or towers. It is important that, with maximum sag, the minimum clearance distance between the line conductors and the ground below is always maintained. This safety clearance increases, of course, with line voltage. Allowing for the necessary sag part of the design-process for any overhead line, and achieving it becomes the responsibility of the linesmen when the line is eventually constructed.
How do you plot ohms law graph of potential difference versus current?
The current is represented by the horizontal (x) axis, and the potential difference is represented by the vertical (y) axis.
If the resulting graph is a straight line, then it confirms that the circuit is obeying Ohm's Law. If the resulting graph is a curve, then the circuit does not obey Ohm's Law.
The gradient at any point along of the resulting line represents the resistance of the load for that ratio of voltage to current.
How does power factor affect your power bill?
A poor power factor causes the meter to rotate more slowly than it should, so a poor power factor would reduce your bill. Electric utilities compensate for this in commercial services by billing based on power factor, or they install a meter that actually measures power factor.
AnswerEnergy meters 'read' the in-phase component of load current (therefore the load's 'true power' multiplied by time) and, so, are completely unaffected by the power factor of a load. So the power factor of a residential load will have absolutely no effect whatsoever on that residence's 'energy' (not 'power') bill.
Industrial and commercial consumers are billed for 'demand' (their rate of consumption of energy -i.e. the power) as well as energy supplied'. In addition, these consumers are usually penalised if the power factor of their load falls below an agreed value. So power factor does affect the overall bill (but not the energy bill) of industrial consumers.
What is Deregulation of power system and what are the effects of deregulation?
Restructuring the existing power system network to achieve better utilization of electrical energy with reduction of losses
B. The field coil (source page 36 of study unit 3, Appliance repair)
A short circuit between adjacent turns of the same winding will cause the turns ratio of the transformer to change. A short circuit of this nature may not cause the transformer to become disconnected, so the situation could last for a long time.
In larger utility transformers, the gases formed by the arcing between turns will collect in the Buchholz relay, situated between the transformer and its expansion tank, which will then initiate an alarm inside the substation.
Why power factor can not be unity?
Power factor can be unity. If the load is purely resistive, then the load current and supply voltage are in phase, and the load will have unity power factor.
How can you get 3 phase supply from single phase supply by using only transformers?
You cannot. By definition, the potential of each line must be displaced from each other by 120 electrical degrees, and this is only achievable from a three-phase source.
How do you calculate the over load and short circuits to use fuses?
By referring to the manufacturer's characteristic curves for the fuse. There are different curves for different types of fuse (e.g. rewirable, cartridge, etc.). Essentially, these curve will tell you how quickly the fuse will operate for any value of overload current.
Is gold used in circuit breakers?
Certainly not in the case of high-voltage circuit breakers. Probably not in low-voltage circuit breakers, as copper is a better conductor and has a higher melting point.
What is the meaning of suffix YNaOd1 in vector group of transformer?
i understand that YNaOd1 represent an auto transformer with HV winding as wye connected and loaded tertiary. Please correct me if i am wrong.
Why you use upf wattmeter for short circuit test on load test on single phase transformer?
If, by 'upf', you mean 'unity power factor', then allwattmeters measure the in-phase component of the load current, so the term is quiet unnecessary.
A short-circuit test is used to determine the (true) power loss in the transformer, which is exactly what a wattmeter measures
You are probably describing a transformer. The 'high voltage side' of a transformer is the winding with the greatest number of terms. It could be the primary or the secondary winding.
Is ohms law is applicable for transmission line?
Ohm's Law is applicable for transmission lines. It is applicable for every case of every circuit in every situation. That's what makes it a law.
The "complexity" is that 1.) resistance is not constant, it being a function of temperature and other factors, and 2.) for AC circuits, impedance makes the calculation complex.
AnswerOhm's Law is not a universal law, and applies in very few cases and, then, only to linear or ohmic devices. It certainly doesn't apply 'to every case, of every circuit, in every situation', and many physicists believe that it should not be classified as a 'law'.
If, on the other hand, you are referring to the equation, R = V/R (for d.c.) or R = V/Z (for a.c.) then, yes, these do apply to transmission lines. But you should be aware that these equations are not derived from Ohm's Law!
What is magneto optic current transformer?
moct is device measure the current by means of faraday's effect..