How governing system of steam turbine is being done?
(pictures insert is not being allowed by wiki. i am sorry)
TOPICS OF DISCUSSION
CONCEPT OF GOVERNING SYSTEM
FEATURES OF KWU GOVERNING SYSTEM
OVERVIEW OF GOVERNING RACK
FUNCTIONING OF EHC CIRCUITS
FREE GOVERNOR MODE OPERATION
BEST PRACTICES IN GOVERNING SYSTEM
EMERGENCIES IN GOVERNING SYSTEM
WHAT IS GOVERNING SYSTEM ?
n Turbine Governing system is meant for regulation of turbine speed under no load and varying load condition.
n It helps in precise control of grid frequency under normal operation and protects the machine as well as grid during emergency situation.
KWU GOVERNING SYSTEM-FEATURES
n ELECTRO-HYDRAULIC GOVERNING SYSTEM WITH HYDRAULIC BACKUP
n OPERATION OF STOP VALVES BY STARTING & LOAD LIMITING DEVICE (HYDRAULIC)
n ROLLING, SYNCHRONIZATION & LOAD OPERATION BY HYDRAULIC / ELECTRO- HYDRAULIC SYSTEM
n ELECTRO- HYDRAULIC SPEED GOVERNOR WITH HYDRAULIC BACK UP
n SAFE SHUTDOWN BY HYDRAULIC / ELECTRO- HYDRAULIC SYSTEM
n ELECTRICAL AND HYDRAULIC PROTECTION SYSTEM ALONG WITH TEST FACILITIES
FEATURES OF EHC
n AUTO ROLLING & SYNCHRONIZATION THROUGH SPEED CONTROLLER UNDER INFLUENCE OF TSE
n CONSTANT LOAD OPERATION BY LOAD CONTR. WITH PRESSURE CONTR. AS BACKUP
n RUNBACK OPERATION THROUGH PRESSURE CONTR.
n EMERGENCY OPERATION THROUGH SPEED CONTR.
n AUTO GRID FREQUENCY CONTROL THROUGH EXTERNAL FREQUENCY INFLUENCE
n AUTO UNLOADING AT HIGH FREQUENCY THROUGH INTERNAL FREQUENCY INFLUENCE
n CONTROL DURING AUTOMATIC TURBINE TESTING,
ISOLATED GRID CONDITION & LSR OPERATION
SPEED CONTROLLER CIRCUIT
L - Raise & Lower command from UCB :
nr - Speed Reference :
nr limit - Delayed Speed Reference :
NLC - No Load Correction (Ensures required Speed controller O/P for Rolling even when Speed reference n r matches n act.)
n act - Actual Speed :
hr nc - Speed Controller O/P with DROOP of + / - 10.0 V for nr lim ~ n act = 150 RPM ( GAIN = 22
LOAD SET POINT GENERATION CIRCUIT
1 - SET POINT FOLLOW UP when Automatic Grid Control or CMC In service
(Other Raise / Lower commands get blocked)
2 -- TSE ENABLING when
A) GCB is closed AND
B) Load controller (L C) not OFF AND
C) Fast calibration signal 6 absent AND
D) I) Load controller (L C) in control
OR ii) Pressure controller with initial pressure in action
OR iii) Turbine follow mode in service
This helps to bring manually adjusted gradient and stress effect in service.
+/- 10 V gradient => +/- 25 MW / MIN for 200 MW units
OR +/- 50 MW / MIN for 500 MW units.
PRESSURE CONTROLLER CIRCUIT
EHC TRANSFER CIRCUIT
FGMO - BACKGROUND
n Unique frequency band of 49.0 Hz to 50.5 Hz, as specified by IEGC
n Scheduling & dispatch by RLDCs/SLDCs is based on day ahead demand & availability
n Frequency control by load-generation balance in every 15 mins time block
n Wide frequency variation during Grid disturbance, Unit outage, change in demand, etc.
n No primary response by generators to maintain frequency under such system contingency
n Emergencies caused due to frequency control only through importing /cutting load by system operator
n
FGMO - GRID CODES
n All generating units should have their speed governors in normal operation at all times to enable Grid frequency control by loading / unloading
n Droop characteristic for primary response should be within 3% to 6%
n Each unit shall be capable of instantaneously picking up at least 5% extra load for a minimum of 5 mins (up to 105%MCR), during fall in frequency
n No dead bands and/or time delays shall be deliberately introduced
n Facilities like load limiters, CMC, etc. shall not be used to suppress the normal governor action
IMPLEMENTATION OF FGMO
In line with clause Clause 1.6 of IEGC and CERC order dated 30-10-99, date of FGMO implementation, as decided by REBs are :-
n Western Region - 19-05-03 ( ABT - 01-07-02 )
n Southern Region - 01-08-03 ( ABT - 01-01-03 )
n Northern Region - 01-10-03 ( ABT - 01-12-02 )
n Nor-East Region - 22-12-03 ( ABT - 01-11-03 )
n Eastern Region - 02-01-04 ( ABT - 01-04-03 )
FGMO CHARACTERISTIC FOR KWU M/C
MAJOR ISSUES WITH FGMO IN 2004
Ø Wide and frequent variation of freq.
Ø Perpetual oscillations in critical parameters due to Boiler response time
Ø M/C subjected to cyclic loading and fatigue stresses
Ø Frequent HP/LP Bypass valve operation
Ø Continuous manual interventions
Ø Self-defeating feature(Unloading when freq. improving towards 50 Hz)
Ø Conflict with ABT(Offsetting freq. correction)
TRANSIENTS IN GOVERNING SYSTEM
n FAILURE OF POWER PACKS OF CONTROLLER RACKS IN EHC PANEL
n POWER SUPPLY FAILURE IN ATRS PANEL
n SIGNAL ACQUISITION PROBLEM
n FAILURE IN TURBINE SYSTEM
n ELECTRICAL SYSTEM FAILURE
n COMPONENT FAILURE IN GOVERNING RACK
n OPERATIONAL EMERGENCY
1 CONTROL RACK SUPPLY FAILURE
n M/C is on EHC. Power supply fails in Load control/Pressure control / transfer circuit rack. Starting device becomes off automatically due to EHC fault.
Observation: EHC output is minimum/zero and load minimum/ zero with EHC fault alarm. Machine on bar with ESV & IV open (Turbine not tripped).
Action: Confirm HP/LP bypass opening, isolate EHC from governing rack and parallely adjust starting device position from UCB. Reduce boiler firing to restrict rise in boiler pressure.
2) SUPPLY FAILURE IN ATRS PANEL(ATRS=Automatic Turbine Rolling & Synchronisation)
n M/C is on EHC. Power supply fails in CCA panels only.
Observation: All indication lamps in ATRS consoles will go off. EHC output and Load will become zero due loss of GCB close feedback. All ATRS drives will become inoperative.
Action: Confirm HP/LP bypass opening , isolate EHC. Reduce boiler firing. Adjust starting device position from local. Normalize power supply in CCA panels at the earliest.
3) SIGNAL ACQUISITION PROBLEM
n Loss of speed signal occurs due to Hall Probe / card failure.
Observation: Speed indication will become zero. M/C will be loaded through speed controller. Subsequently Pressure controller will come in service. AOP & JOP will take auto start & Barring Gear valve Will open on auto.
Action: Isolate EHC and adjust Starting device position. If pressure oil pressure is normal, make SLC of AOP, JOP and Barring Gear vlv OFF and stop AOP, JOP and close Barring Gear vlv.
4)FAILURE IN TURBINE SYSTEM
n Loss of speed signal occurs due to breakage of MOP shaft.
Observation: Speed indication and pressure oil pressure will come down. M/C will be loaded through speed controller and Pressure controller will come in service. Subsequently, AOP & JOP will take auto start &Barring Gear valve. will open on auto.
Action: Safe shutdown of M/C is to be ensured.
5) ELECTRICAL SYSTEM FAILURE
n M/C is on EHC with Tracking on. Starting device becomes inoperative due to Electrical module trouble/motor failure/overload.
Observation: During increase in boiler firing, Boiler pressure will increase due to load restriction by Starting device. EHC output will go to 100%.
Action: Switch off the electrical module of Starting device and increase Starting device position from local so that EHC can take control.
6) FAILURE IN GOVRRNING RACK
n EHC Plunger coil failure
n EHC Pilot valve bearing failure
Observation: EHC starts hunting
Action: Isolate EHC and take Hydraulic mode in service. Replace the failed omponent. Governing characteristic checking should be done before EHC is put in service
n Speeder Gear spring tension gets altered.
Observation: M/C may get unloaded at frequency lower than recommended value.
Action: Speeder Gear spring tension may be adjusted to increase the start of unloading.Testing for proper setting should be checked during suitable opportunity.
LOGICS
A SPEED CONTROLLER LOGICS
1 Command for slow rate at nr > 2850 RPM to facilitate easy synchronisation
2 TSE Influence ON, when min of all the upper stress margins comes into picture to control gradient of nr lim and hence, acceleration of Rolling speed. Upper stress margin = 30 deg C => 10.0 V => 600 RPM ~ (Acceleration < 108 RPM ~ causes dn / dt tripping)
B LOAD SET POINT GENERATION LOGICS
1 Stopping of nr lim when
a) GCB open AND
b) n act is < nr lim by approx. 45 RPM.
This restricts hr nc up to around 30 % during Rolling to avoid wide v/v opening.
2 Stopping speed set point control when,
a) n act > 2850 RPM AND
b) nr raised ( I.e, nr > nr lim) AND
c) I) TSE ON and faulted in GCB open condition
OR ii) Stop command from SGC in SGC ON condition.
3 Tracking in synchronized condition if
a) Frequency within limit (adjustable, say 48.5 to 51.5 Hz.) AND
b) Load controller O/P , hr PC > hr nc AND
c) I) Load controller (L C) in control
OR ii)Pressure controller in action
4 Set Point Follow Up (Fast Calibration) during
a) Tracking condition 5 ( nr = n act + 21 RPM ) OR
b) Turbine Trip ( nr = n act - 120 RPM ). Simultaneously nr lim immediately equals to nr
Condition (a) ensures certain speed controller O/P during emergency to keep machine in rolled condition along with some load.
Condition (b) ensures negative speed controller O/P during Trip condition.
LOAD CONTROLLER (L C) IN CONTROL CONDITIONS -
a) Speed OR Pressure Controller not in action AND
b) Isolated Grid condition absent AND
c) Both Load Controller OFF and Schedule OFF absent (I.e, L C ON)
LOAD CONTROLLER SCHEDULE OFF - L C can be made OFF if Speed controller is in action and hrnc > hr PC. Otherwise, with OFF command OFF lamp blinks - called Schedule OFF
C .LOAD SET POINT GENERATION LOGICS
1TSE ON AND NOT FAULTED
This helps to keep stress effect for gradient control in service.
2-- LOAD GRADIENT ON
This helps to keep manual gradient control in service
3-- STOP POWER SET POINT CONTROL when
a) TSE ON and Faulted OR
b) Stop command from SGC OR
c) Pr raised when Pressure controller is in action with CMC ON OR Limit pressure mode selected OR Boiler follow mode selected
In above conditions Pr lim stops, I.e,Set point can not be increased.
4-- FAST CALIBRATION when
a) Pressure controller is in action OR
b) Follow above (h v0) condition present
Under this condition MW error (ep) is selected and Pr lim immediately equals to Actual load (P act) without any gradient .
5 -- FREQUENCY INFLUENCE ON
This is made ON from ATRS panel to put EXTERNAL FREQUENCY EFFECT in service for
loading / unloading w.r.t. 50 Hz ( with 2.5 % to 8 % Frequency Droop)
6 TSE TEST RELEASE : TSE TEST (For checking healthiness of TSE Margins) can be done when
a) TSE Influence is OFF OR
b) Both Pr, Pr lim and hr, hr lim are balanced, I.e, Speed and Power set point controls are not in action.
D .LOAD CONTROLLER LOGICS
FOLLOW ABOVE ( h v0 ) --
a) GCB closed and load < 10 % (station load) OR
b) GCB open OR
c) Load controller OFF
Absence of these conditions help Load controller output to track above Pressure controller output when Pressure controller is in service.
FOLLOW LOW ( h vu ) - GCB CLOSED AND Speed controller in action.
This helps Load controller output to track below Speed controller output.
8 -- Either a) Initial pressure mode selected OR
b) Turbine follow mode in action OR
c) CMC Runback active
This ensures Load controller output above pressure controller output
9 -- Load controller OFF
This defeats transmission of Load Controller output to Transfer circuit.
R & L - Raise & Lower command from UCB :
nr - Speed Reference :
nr limit - Delayed Speed Reference :
NLC - No Load Correction (Ensures required Speed controller O/P for Rolling even when Speed reference n r matches n act.)
n act - Actual Speed :
hr nc - Speed Controller O/P with DROOP of + / - 10.0 V for nr lim ~ n act = 150 RPM ( GAIN = 22
LOAD SET POINT GENERATION CIRCUIT
1 - SET POINT FOLLOW UP when Automatic Grid Control or CMC In service
(Other Raise / Lower commands get blocked)
2 -- TSE ENABLING when
A) GCB is closed AND
B) Load controller (L C) not OFF AND
C) Fast calibration signal 6 absent AND
D) I) Load controller (L C) in control
OR ii) Pressure controller with initial pressure in action
OR iii) Turbine follow mode in service
This helps to bring manually adjusted gradient and stress effect in service.
+/- 10 V gradient => +/- 25 MW / MIN for 200 MW units
OR +/- 50 MW / MIN for 500 MW units.
PRESSURE CONTROLLER CIRCUIT
EHC TRANSFER CIRCUIT
FGMO - BACKGROUND
n Unique frequency band of 49.0 Hz to 50.5 Hz, as specified by IEGC
n Scheduling & dispatch by RLDCs/SLDCs is based on day ahead demand & availability
n Frequency control by load-generation balance in every 15 mins time block
n Wide frequency variation during Grid disturbance, Unit outage, change in demand, etc.
n No primary response by generators to maintain frequency under such system contingency
n Emergencies caused due to frequency control only through importing /cutting load by system operator
n
FGMO - GRID CODES
n All generating units should have their speed governors in normal operation at all times to enable Grid frequency control by loading / unloading
n Droop characteristic for primary response should be within 3% to 6%
n Each unit shall be capable of instantaneously picking up at least 5% extra load for a minimum of 5 mins (up to 105%MCR), during fall in frequency
n No dead bands and/or time delays shall be deliberately introduced
n Facilities like load limiters, CMC, etc. shall not be used to suppress the normal governor action
IMPLEMENTATION OF FGMO
In line with clause Clause 1.6 of IEGC and CERC order dated 30-10-99, date of FGMO implementation, as decided by REBs are :-
n Western Region - 19-05-03 ( ABT - 01-07-02 )
n Southern Region - 01-08-03 ( ABT - 01-01-03 )
n Northern Region - 01-10-03 ( ABT - 01-12-02 )
n Nor-East Region - 22-12-03 ( ABT - 01-11-03 )
n Eastern Region - 02-01-04 ( ABT - 01-04-03 )
FGMO CHARACTERISTIC FOR KWU M/C
MAJOR ISSUES WITH FGMO IN 2004
Ø Wide and frequent variation of freq.
Ø Perpetual oscillations in critical parameters due to Boiler response time
Ø M/C subjected to cyclic loading and fatigue stresses
Ø Frequent HP/LP Bypass valve operation
Ø Continuous manual interventions
Ø Self-defeating feature(Unloading when freq. improving towards 50 Hz)
Ø Conflict with ABT(Offsetting freq. correction)
TRANSIENTS IN GOVERNING SYSTEM
n FAILURE OF POWER PACKS OF CONTROLLER RACKS IN EHC PANEL
n POWER SUPPLY FAILURE IN ATRS PANEL
n SIGNAL ACQUISITION PROBLEM
n FAILURE IN TURBINE SYSTEM
n ELECTRICAL SYSTEM FAILURE
n COMPONENT FAILURE IN GOVERNING RACK
n OPERATIONAL EMERGENCY
1 CONTROL RACK SUPPLY FAILURE
n M/C is on EHC. Power supply fails in Load control/Pressure control / transfer circuit rack. Starting device becomes off automatically due to EHC fault.
Observation: EHC output is minimum/zero and load minimum/ zero with EHC fault alarm. Machine on bar with ESV & IV open (Turbine not tripped).
Action: Confirm HP/LP bypass opening, isolate EHC from governing rack and parallely adjust starting device position from UCB. Reduce boiler firing to restrict rise in boiler pressure.
2) SUPPLY FAILURE IN ATRS PANEL(ATRS=Automatic Turbine Rolling & Synchronisation)
n M/C is on EHC. Power supply fails in CCA panels only.
Observation: All indication lamps in ATRS consoles will go off. EHC output and Load will become zero due loss of GCB close feedback. All ATRS drives will become inoperative.
Action: Confirm HP/LP bypass opening , isolate EHC. Reduce boiler firing. Adjust starting device position from local. Normalize power supply in CCA panels at the earliest.
3) SIGNAL ACQUISITION PROBLEM
n Loss of speed signal occurs due to Hall Probe / card failure.
Observation: Speed indication will become zero. M/C will be loaded through speed controller. Subsequently Pressure controller will come in service. AOP & JOP will take auto start & Barring Gear valve Will open on auto.
Action: Isolate EHC and adjust Starting device position. If pressure oil pressure is normal, make SLC of AOP, JOP and Barring Gear vlv OFF and stop AOP, JOP and close Barring Gear vlv.
4)FAILURE IN TURBINE SYSTEM
n Loss of speed signal occurs due to breakage of MOP shaft.
Observation: Speed indication and pressure oil pressure will come down. M/C will be loaded through speed controller and Pressure controller will come in service. Subsequently, AOP & JOP will take auto start &Barring Gear valve. will open on auto.
Action: Safe shutdown of M/C is to be ensured.
5) ELECTRICAL SYSTEM FAILURE
n M/C is on EHC with Tracking on. Starting device becomes inoperative due to Electrical module trouble/motor failure/overload.
Observation: During increase in boiler firing, Boiler pressure will increase due to load restriction by Starting device. EHC output will go to 100%.
Action: Switch off the electrical module of Starting device and increase Starting device position from local so that EHC can take control.
6) FAILURE IN GOVRRNING RACK
n EHC Plunger coil failure
n EHC Pilot valve bearing failure
Observation: EHC starts hunting
Action: Isolate EHC and take Hydraulic mode in service. Replace the failed omponent. Governing characteristic checking should be done before EHC is put in service
n Speeder Gear spring tension gets altered.
Observation: M/C may get unloaded at frequency lower than recommended value.
Action: Speeder Gear spring tension may be adjusted to increase the start of unloading.Testing for proper setting should be checked during suitable opportunity.
LOGICS
A SPEED CONTROLLER LOGICS
1 Command for slow rate at nr > 2850 RPM to facilitate easy synchronisation
2 TSE Influence ON, when min of all the upper stress margins comes into picture to control gradient of nr lim and hence, acceleration of Rolling speed. Upper stress margin = 30 deg C => 10.0 V => 600 RPM ~ (Acceleration < 108 RPM ~ causes dn / dt tripping)
B LOAD SET POINT GENERATION LOGICS
1 Stopping of nr lim when
a) GCB open AND
b) n act is < nr lim by approx. 45 RPM.
This restricts hr nc up to around 30 % during Rolling to avoid wide v/v opening.
2 Stopping speed set point control when,
a) n act > 2850 RPM AND
b) nr raised ( I.e, nr > nr lim) AND
c) I) TSE ON and faulted in GCB open condition
OR ii) Stop command from SGC in SGC ON condition.
3 Tracking in synchronized condition if
a) Frequency within limit (adjustable, say 48.5 to 51.5 Hz.) AND
b) Load controller O/P , hr PC > hr nc AND
c) I) Load controller (L C) in control
OR ii)Pressure controller in action
4 Set Point Follow Up (Fast Calibration) during
a) Tracking condition 5 ( nr = n act + 21 RPM ) OR
b) Turbine Trip ( nr = n act - 120 RPM ). Simultaneously nr lim immediately equals to nr
Condition (a) ensures certain speed controller O/P during emergency to keep machine in rolled condition along with some load.
Condition (b) ensures negative speed controller O/P during Trip condition.
LOAD CONTROLLER (L C) IN CONTROL CONDITIONS -
a) Speed OR Pressure Controller not in action AND
b) Isolated Grid condition absent AND
c) Both Load Controller OFF and Schedule OFF absent (I.e, L C ON)
LOAD CONTROLLER SCHEDULE OFF - L C can be made OFF if Speed controller is in action and hrnc > hr PC. Otherwise, with OFF command OFF lamp blinks - called Schedule OFF
C .LOAD SET POINT GENERATION LOGICS
1TSE ON AND NOT FAULTED
This helps to keep stress effect for gradient control in service.
2-- LOAD GRADIENT ON
This helps to keep manual gradient control in service
3-- STOP POWER SET POINT CONTROL when
a) TSE ON and Faulted OR
b) Stop command from SGC OR
c) Pr raised when Pressure controller is in action with CMC ON OR Limit pressure mode selected OR Boiler follow mode selected
In above conditions Pr lim stops, I.e,Set point can not be increased.
4-- FAST CALIBRATION when
a) Pressure controller is in action OR
b) Follow above (h v0) condition present
Under this condition MW error (ep) is selected and Pr lim immediately equals to Actual load (P act) without any gradient .
5 -- FREQUENCY INFLUENCE ON
This is made ON from ATRS panel to put EXTERNAL FREQUENCY EFFECT in service for
loading / unloading w.r.t. 50 Hz ( with 2.5 % to 8 % Frequency Droop)
6 TSE TEST RELEASE : TSE TEST (For checking healthiness of TSE Margins) can be done when
a) TSE Influence is OFF OR
b) Both Pr, Pr lim and hr, hr lim are balanced, I.e, Speed and Power set point controls are not in action.
D .LOAD CONTROLLER LOGICS
FOLLOW ABOVE ( h v0 ) --
a) GCB closed and load < 10 % (station load) OR
b) GCB open OR
c) Load controller OFF
Absence of these conditions help Load controller output to track above Pressure controller output when Pressure controller is in service.
FOLLOW LOW ( h vu ) - GCB CLOSED AND Speed controller in action.
This helps Load controller output to track below Speed controller output.
8 -- Either a) Initial pressure mode selected OR
b) Turbine follow mode in action OR
c) CMC Runback active
This ensures Load controller output above pressure controller output
9 -- Load controller OFF
This defeats transmission of Load Controller output to Transfer circuit.
2
To hold microchips, capacitors, transistors, MOSFETs, wiring and more, naturally!
PCB means Printed Circuit Board. It's that green (Occasionally other colors) board with all the squiggly lines and technologically looking stuff on it.
A capacitor is used to store charge. It does this by the means of an electrochemical reaction. After the charging circuit is turned off, this charge - if not discharged by any means - is still present in the capacitor. High-Voltage capacitors can amass sufficient current for it to be lethal at said voltage, and they can deliver all of it at the slightest contact.
For example, a flasher circuit used in a typical photo camera can deliver lethal voltage, even when it's been charged from a 1.5V battery. The current doesn't need to be high (and is typically very low).
I've made this mistake more than once in my life, and I've had screwdrivers welded to the capacitor terminals by their charge. :D
It is worthy of note that some devices and circuits act as capacitors even when they're not designated as such! For example, a Cathode-Ray Tube (the big-ass thing in a tube TV) is a very good high-voltage capacitor itself, and can hold a charge for a long time (even weeks)!
Let C1=0.05F
& C2=0.025F, C1 & C2 are in series
Let the equivalent capacitance will be C
than 1/C = 1/C1 + 1/C2
1/C = 1/0.05 + 1/0.025 = 20 + 40 = 60F
hence C= 1/60 = 0.0166667 F
What are Rising edge triggered d type flip flops?
The D flip-flop has a D and Clock input, and a Q (and sometimes Q/) output. The D input is copied to the Q (and, inverted, Q/) output on the specified edge of Clock.
Its like a J-K flip-flop where K is driven with the inverted value of J.
ANSWER: D stands for data it it will transfer the data with a clock control input
d type flip flop is a flip flop whose output is a function of the input which appeared one pulse earlier. Also known a d type flip flop.
A multimeter combines the functions of an ammeter, voltmeter, and ohmmeter and, so, can be used to measure current, voltage, and resistance by selecting the appropriate scale/setting.
No, unless you don't watch Direct TV or have 2D to 3D Conversion TV. However, not all the 3D TVs are capable of converting 2D to 3D. Therefore, answer is Yes and No. You will be able to watch TV channels in 3D on 3D TVs like LG but not on such like a Vizio because they don't support 2D to 3D conversion. So check the spec whether there are this feature in the TV before you buy it if you want to watch TV channels like Oprah, American Idol, NFL in 3D. Plus, this conversion feature convert not only TV channels but anything on TV meaning you will be able to watch literaily any contents even downloaded movie from internet, on 3D.
I read ESPN and Discovery Channel in 3D are available for 24/7.
What is the use of 1 microfarad capacitor?
The use of the micro- prefix for capacitance, i.e. microfarads, is common because the farad is a very large unit of capacitance and we don't normally use capacitors in that range of value.
How do you find the voltage drop over a resistor?
To find the voltage drop over a resistor, you measure it with a voltmeter connected across the resistor. You also need to make sure the impedance of the voltmeter is high enough to not shift the effective resistance more than the required accuracy of the measurement.
What would you do to measure the current in a resistor?
Since the current in a resistor is the same as the current in the leads/wires on either side of the resister, I might use a clamp meter such as an Amprobe to measure current, if the current was alternating (AC). Otherwise, I would have to break one of the leads and insert an ammeter or a multimeter with an amp setting into the circuit. Afterwards the broken connection would have to be repaired.
Load on an electrical system is the power being drawn from the system. All electrical devices like fridges, heaters and light bulbs have an associated power usage capacity measured in Watts(W). Thus, we have a 60W light bulb. When these devices are all connected to an electricity network their combined power usages is load on the system.
Load can also refer to usage of say a house or factory. Often this will vary over time depending on what devices are turned on inside.
The opposite of load is generation, also measured in Watts. A power plant's generation capacity is so great it is usually measured in Mega Watts (MW) or a million watts. The generation and the load on a system have to be balanced otherwise the system becomes unstable. This can lead to load shedding and blackouts.
A: NAND implies not and to be true both input must be hi or true
<>
There are two flavors of NAND gate. The positive input/negative output NAND will have a low output if and only if both inputs are high. The negative input/positive output NAND will have a high output if and only if both inputs are low.
How do you calculate output offset voltage?
Output offset voltage is the output of an operational amplifier when the two inputs are shorted together (and often tied to ground).
>> The output offset voltage (Voo) is caused by mismatching by two input terminals. Even though all the components are integrated on the same chip, it is not possible to have two transistors in the input differential amplifier stage with exactly the same characteristics. This means that the collector currents in these two transistors are not equal, which causes a differential output voltage from the first stage. The output of first stage is amplified by following stages and possibly aggravated by more mismatching between them. Thus the output voltage caused by mismatching between two input terminals is the output offset Voo .
Difference between transistor and vacuum tube?
They are both used for similar functions, such as oscillators, amplifiers, and switches.
The vacuum tube was invented first, and has therefore been around longer than the transistor.
What is the bandwidth of half dipole antenna?
The polar pattern for a half lambda aerial is a toroidal (doughnut) shape with the aerial in the centre of the toroid when mounted in free space a half wave above the ground.
The half wave is an omni-directional aerial and produces zero gain.
What are stationary part of dc motor?
The stationary part of any motor or generator is termed the 'stator', and the rotating part is termed the 'rotor'.
The stator comprises the main frame (chassis), the magnetic circuit, and field windings.
What size resistor is needed to drop 14 volts dc to 12 volts dc?
This question cannot be answered because you did not specify the current.
Conversions of RMS voltage, peak voltage and peak-to-peak voltage. That are the used voltages. The expression "average" voltage is used for RMS voltage.
Scroll down to related links and seach for "RMS voltage, peak voltage and peak-to-peak voltage".
Answer'Average' is not the same as 'root mean square'. As the average value of a sinusoidal voltage is zero, you cannot convert it to a peak-to-peak value.
What is an electric circuit with little or no resistance?
A: As current approaches infinity on a device it is known as a current source.
Where is the highest transmission voltage in India?
the highest transmission volatage in India is 765kV ac. The highest voltage in the case of DC transmission is +/- 600 kV.
What is the purpose of transister?
The correct spelling is transistor. The definition of transistor is a portable radio that uses circuits that contain transistors instead of vacuum tubes. It is a semiconductor device that has three connections.
What is the equation used to calculate the resistance current or voltage?
S = Apparent Power
P = Real Power [Negative for supplied power, positive for absorbed power]
Q = Reactive Power [Positive for lagging or inductive loads, negative for leading or capactive loads]
Fp = Power Factor [Specified as lagging or leading for inductive or capacitive loads respectively]
V = Voltage
I = Current
* = (Conjugate)
< = 'At an angle of'
For DC cases:
|P| = P = V x I = V^2 / R = I^2 x R
For AC cases:
S = V x I* = |S| < arccos(Fp)
|S| = |V| x |I|
|P| = |S| x Fp
|Q| = sqrt(|S|^2 - |P|^2)