What size wire for 220 8.3 amps?
A #14 copper conductor with an insulation factor of 90 degrees C is rated 15 amps. If it is continuously loaded it has to be de rated to 80% capacity. 15 x .8 = 12 amps. You are well within the range of a #14 wire, only drawing 8.3 amps.
Does the common and ground wires hookup together on main box?
No, the common (neutral) and ground wires should not be connected together in the main electrical panel. The common wire is used to carry current back to the electrical panel, while the ground wire is used for safety to prevent electrical shock. They serve different purposes and should remain separate.
You cannot legally work on a sealed meter base but if you have a "shutoff" at the meter base, turn off power to the breaker panel, verify that there is no power at the panel then tighten the connections inside the breaker panel.
If that doesn't solve the problem, contact a qualified electrician.
To amplify a bit, your breaker box is split into two parts each fed by one of two legs of a 230/240 VAC main supply. There will be three wires and a ground feeding the box. The white wire is neutral and Black is one side of the 230/240 VAC circuit and red is typically the other. Working on a main panel is very dangerous so calling an electrician is a great idea. If your house was fed with aluminum cable it tends to creep over time and the main screw connecting the wire to the bus bar tends to be loose. There is usually a compound use to stop oxidation when aluminum wire is used. You CANNOT just tighten this wire because it is LIVE. One of the possibilities is that some older panels may be fed from a fused disconnect box where there is a cartridge fuse on each of the two "hot" legs. The disconnect handle, when turned off, will remove power from each side of the fuses so they can be replaced.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized
IF YOU ARE NOT REALLY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
Can you use an 18 amp appliance on a 20 amp circuit?
Yes, if properly wired a 20 amp circuit is a great circuit for an 18 amp appliance.
Properly wired means you've used 12 gauge wire or larger and the circuit is protected by a 20 amp breaker or fuse and all connections are secure.
Can you have an 18 amp appliance on a 20 amp circuit?
Yes, you can have an 18 amp appliance on a 20 amp circuit. It is important to leave some room for safety margin, and a 20 amp circuit should be able to handle the 18 amp load without any issues. Make sure the wiring and circuit breaker are correctly rated for the load.
Can you use 16v 4.5 amps for 16v 1.5 amps?
First, let me clarify the question:
You want to use a 16V, 4.5 amp power supply to operate a device that uses 16V, 1.5 amps.
That's not a problem, the larger power supply simply has the capacity of 4.5 amps, meaning that you can use anything UP TO 4.5 amps.
On the other hand...
if you want to try using a device that pulls 4.5 amps, using a 1.5 amp power supply... sorry, won't work out well. That would overheat the power supply and it would fail.
What is two wire to four wire conversion?
Two wire to four wire conversion is the process of converting a communication or power system that uses two wires for transmission to a system that utilizes four wires. This conversion allows for improved signal quality, increased bandwidth, and reduced crosstalk and interference in the transmission line. It is commonly used in telecommunications, networking, and audio systems.
Can you use 12-2 with ground to wire a 2000 watt forced air heater to a 240 volt 30 amp breaker?
(LIFE SAFETY WARNING! [disclaimer]
Electricity is dangerous!
You can be injured or killed!
Improper installations can cause fire, injury and death!
Should you be doing this yourself?)
Can a 12-2 wire be connected to a 20-amp 240-volt circuit breaker to power a 240-volt heater?
There are limitations.
If there is a 120-volt fan in the heater, it will be necessary to run a 12-3 wire, so that there is a conductor for the 120 load neutral.
With a strictly 240 operation, the maximum wattage that can be served by a 20-amp circuit is 3840 watts. It is allowed to continuously operate a circuit at 80% of it's rated ampacity [4800 watts]. Continuous operation is defined as 4 hours or more continual operation.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
What size service conductors for a 225 amp 3 phase service?
For a 225 amp 3-phase service, typically you would use 3 sets of 3/0 AWG copper conductors or 250 kcmil aluminum conductors for the service entrance conductors. Make sure to consult the National Electrical Code (NEC) and local regulations for specific requirements.
Wires are not to be spliced or otherwise connected except in an approved electrical box. The box should be accessible, such as an electric outlet or switch box. If you decide to NOT use the box as an outlet or switch box, make certain that you use a blank cover.
What is soldering wire used for?
Soldering wire is used for joining metal components together by melting the solder and allowing it to flow between the parts, creating a strong bond when it solidifies. It is commonly used in electronics, plumbing, jewelry making, and other metalworking applications.
Are there electric ranges that draw 30 amps or less?
Yes, there are electric ranges available that draw 30 amps or less. These ranges are typically smaller in size and have fewer cooking elements, reducing their power consumption. It's important to check the manufacturer's specifications to ensure the range meets your electrical requirements.
What size of current does the 1.5mm wire carry?
The size of current that a 1.5mm wire can carry depends on factors like the material of the wire, temperature, and insulation. Generally, a 1.5mm wire can typically carry around 10-15 amps of current in normal household applications. For specific projects or applications, it's important to check the wire's current-carrying capacity based on the relevant specifications and standards.
Why when one of the bulbs goes out on your Christmas tree lights then they all go out?
These are old generation lights. They are connected in series with each other. This means if one of the filaments in any one of the bulbs opens the circuit current flow stops. For example if each bulb is rated at 2 volts each then a string of 60 bulbs can be on a 120 volt circuit. lamps connected in series, because each bulbs filament resistance is the same, will will drop a voltage across each bulb by the total number of bulbs in the string divided into the supply source voltage. 120 volts / 60 bulbs = 2 volts per bulb.
Newer sets of lights have a have a spring mounted in each lamp. When any lamp filament opens a spring is released and shorts out the two wires where the filament was. This allows the string of lights to remain operable. This has a drawback in that as more lights burn out the voltage becomes higher across the other bulbs. Eventually the bulbs will start burning out faster and faster as the voltage across each bulb becomes higher and higher. Use the equation above to see this fact.
Christmas string lights today use LED bulbs which last many times longer than an incandescent bulb in the string set.
Where is the only place the neutral and ground wires can be on the same buss bar?
The main electric panel is where neutral is bonded to ground. There is usually a screw or strap that connects the two so the same type panel could be used as a subpanel and have the neutral and ground unbonded in subpanel.
Do you connect both wires on a pull chain switch one to black one to white?
There should be two wires in the box, black and white and possibly a bare one depending on the age of the wiring in the house. The fixture has two screws on the base. One wire goes on each screw. If there are short wires on the fixture, black to black and white to white. If there is a bare ground wire in the house box, it attaches to the body of the fixture. If there is no ground screw on the fixture, do not worry about it.
How do you wire a dishwasher with black white and green wires?
Connect the black wire to the hot wire, the white wire to the neutral wire, and the green wire to the grounding screw or terminal on the dishwasher. Make sure to follow the manufacturer's instructions and all safety guidelines. If you are unsure, it's best to contact a licensed electrician to complete the wiring.
Using the formula for resistance of a wire (R = ρ * (L/A)), we can find the resistivity ratio (ρ_aluminum / ρ_copper) as 1.7 since the total current in both wires is the same and the lengths are different. Knowing that the resistivity of copper is 1.7 times less than that of aluminum, and given that resistivity is inversely proportional to cross-sectional area, the diameter of the copper wire will be √(1.7) = 1.3 times the diameter of the aluminum wire. Since the diameter of the aluminum wire is 2mm, the diameter of the copper wire will be 2mm * 1.3 = 2.6mm.
Your breaker panel has two separate bus bars and it is certainly best to balance your load between each bus. Typically every other breaker, as you move vertically, is an alternating bus.
While you can add up the ratings on each bus to try and balance, this will not provide the best balance in that many breakers may operate at no where near their rating. The best way is to have an electrician measure the current on each bus with a clamp-on amp meter.
While this balance is ideal, it is usually only necessary if you are having a problem with the unbalanced load, like all the lights in your house dimming when the air conditioner turns on.
On your ganged 30 amp breakers, 30 amps through either will trip that breaker.
Can you use 15 amp appliance on 20 amp socket?
Yes, the amp rating is a measurement of the highest amp load it should carry. So a 15 amp appliance will work on a 20 amp socket but you wouldn't want to use a 20 amp appliance on a 15 amp socket.
How do you flip the switches in the electrical room?
When ever a safety switch is thrown, be it to the on position or the off position, the operator must stand to one side of the switch. It is during the act of opening or closing a switch that a fault could occur. If a dead short occurs when doing this action the whole switch could explode. If the operator is standing in front of the switch their body would take the full force of the explosion.
Generally, if the electrician did it right, the BLACK wire is HOT, and the WHITE wire is NEUTRAL. Meaning that the white wire is the center tap of the main transformer, and the black wire(s) are either leg of the 240 volt output. Since the hot to center tap only takes half of the 240, it ends up being 120 volts at your outlet.
What is the purpose of ground wire?
A ground wire is used for a direct path back to the distribution panel independent of the neutral. On a split phase secondary the neutral is used by other circuits on the system and indirectly makes its way back to the distribution panel. This indirect path introduces a resistance in the neutral which could interfere with an instantaneous trip of the over current device. Using a ground wire from the grounding pin on the three blade plug allows a direct low resistance path which takes the fault current back to the distribution panel which then causes an instantaneous breaker trip due to the high current in a short circuit.
How can you convert a 110 plug to a 220 plug for a cook stove with schematics and diagram?
You'll need to run a NEW circuit, including a new breaker in the panel, a new wire which has been properly sized for the application and a new outlet box and plug.
If you have ANY questions about the procedure, you should contact a local electrician to perform the work for you.
What size rigid conduit for 200 Amp service entrance using 3 ought wire?
A 3/0 wire with an insulation factor of 90 degrees C is rated at 210 amps. The electrical code book states that 3 - 3/0 wires can be pulled into 41 mm conduit (1-1/2"). Most mast kits utilize 53 mm (2") schedule 40 conduit.