In general there is no reason why it should not be, though there may be special situations. Perhaps there is confusion with CURRENT Transformers which must not be left open circuit because of the high voltages which they will produce. it may trip the CB. although there is no faults but a high current called Inrush current is flow when the the power transfomer energized while its secondry circuit is open

User Avatar

Wiki User

15y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

13y ago

If current flows in the primary with the secondary open circuit, a large voltage will be produced on the secondary most likely causing it to burn up. The condition is very dangerous and should be avoided.so,the secondary of the current transformer should be

always close circuited.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Why should the secondary of a power transformer not to be left on an open circuit?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

How do you carry open circuit test on power transformer?

A Linear power transformer coil? use an Ohm meter and check the resistance of the coils. No resistance is an open circuit. Also check for a cross circuit from one side of the transformer to the other.


Why us the power measured during the open circuit test considered to be approximately equal to the core loss?

During open circuit test on transformer, no load is connected across the secondary side. Hence, the total power drawn by the transformer is only to induce the voltage across the secondary, i.e., core loss AND negligible amount of primary copper loss. As the primary copper losses during open circuit are negligible, it is practice to attribute the open circuit power to core loss.


What multimeter readings set to measure resistance indicate an open circuit and short circuit in the primary and secondary windings of a mains power transformer. And what readings show good?

You cannot use an ordinary multimeter to assess the difference between a normal power transformer winding and a shorted power transformer winding. You need a Q meter and/or to power it up at a reduced voltage with limited current to see what happens. Note that a shorted power transformer is capable of exploding, so you need to take appropriate safety precautions.


How do you calculate MVA rating of power transformer?

The product of the secondary rated current and the secondary rated voltage will give you the rated V.A of the transformer.


When secondary coil is open there is no current in the primary coil WHY?

I am assuming the question is about the power / distribution transformer and not the current transformer. The primary current is a function of load connected on secondary. With the open secondary, there is no load, no current, it is open circuit. Hence no primary current. However there is always some small amount of no load current in the primary winding.

Related questions

When the transformer is connected to the power source the secondary current is 0 what is the possible fault in the transformer?

A secondary current of 0 would suggest to me that the secondary circuit is open. A normally operating circuit with zero current flow would be very unusual. No load in secondary circuit. No secondary current can also be attributed to the primary power source open or an open primary winding.


What are the approximation of open circuit and short circuit test of transformer?

A short-circuit test is done to determine the power lost in the resistance of the primary and secondary windings of the transformer. It is done at full load current but with only enough voltage to give the required current with the secondary short circuited. An open-circuit test is done at full load voltage but no current is taken from the secondary, and this enables the power lost in the magnetic core of the transformer to be measured. As well a power, the tests also allow the inductances to be measured as well as the resistances, in order ot characterise the transformer fully.


Why rated current should flow in the secondary for short circuit?

The short-circuit test runs the rated current through the windings of the transformer to measure the copper-loss, or power lost in the winding resistances. Because the transformer is run at low voltage for this test, there is very little additional power loss in the iron core of the transformer.


What are the limitations of power supply?

Power limitation transformer circuit structure of power supply, including: an electromagnetic interference filter unit, a rectifying unit, a power factor correction section, a transformer having a primary input terminal and secondary input terminal, a pulse controlling unit connected with the secondary input terminal of the transformer, a primary power limitation circuit and at least one secondary power limitation circuit, an output current controlling unit and an output voltage controlling unit. The input terminal of the output current controlling unit is connected with the secondary output terminal of the transformer. The primary output terminal and secondary output terminal of the output current controlling unit are respectively serially connected with the primary and secondary power limitation circuits. The input terminal of the output voltage controlling unit is connected with the secondary output terminal of the transformer. The output terminal of the output voltage controlling unit is connected with the secondary power limitation circuit for controlling the magnitude of the voltage and current of the primary and secondary power limitation circuits so as to control the output power.


In D.C supply the transformer is not connected why?

In a DC power supply a transformer is connected. The only time there would be no transformer used would be if the DC voltage wanted was 120 VDC. The transformer in the power supply is connected to 120 VAC on the primary side and the secondary side of the transformer is connected to either a half wave or a full wave diode bridge. The voltage out of the diode bridge will be the same output voltage potential as the transformer's secondary voltage but it will be a DC (Direct Current) potential.Reading the question in another way, transformers are not connected in a DC circuit. The reason being is that the transformer operates on a collapsing magnetic field. This field induces a voltage into the secondary side of the transformer. Since the DC circuit does not operate on the principle of a collapsing field except when the circuit is opened, the transformer would not operate as a transformer should..


Why low power factor wattmeter is used for open circuit test of transformer?

For open circuit test of transformer, the secondary is open circuit and the circuit impedance is largely inductive due to the core impedance having high L as compared to R. hence the power factor is reduced, thus , we use low power factor wattmeters.


How do you carry open circuit test on power transformer?

A Linear power transformer coil? use an Ohm meter and check the resistance of the coils. No resistance is an open circuit. Also check for a cross circuit from one side of the transformer to the other.


What losses can be measured in a short circuit test of a transformer?

Winding copper losses of a transformer can be measured in a short circuit test of a transformer. Impedance voltage is given to the primary and the secondary is often shortcircuited. (some times the reverse is done of this). Full load currents are made to flow in both primary and secondary circuits. This current flow heats up the 2 windings of the transformer. Power consumed at this time gives the transformer copper losses.


What is meant by the term ideal transformer?

ideal transformer is that which has no power losses.if any transformer transfer power to secondary without power loss then that call a ideal transformer


What are the purposes of performing no load test for the transformer?

These two tests are performed on a transformer to determine (i) equivalent circuit of transformer(ii)voltage regulation of transformer(iii) efficiency of transformer. The power required for theseOpen Circuit test and Short Circuit test on transformeris equal to the power loss occurring in the transformer.


Why us the power measured during the open circuit test considered to be approximately equal to the core loss?

During open circuit test on transformer, no load is connected across the secondary side. Hence, the total power drawn by the transformer is only to induce the voltage across the secondary, i.e., core loss AND negligible amount of primary copper loss. As the primary copper losses during open circuit are negligible, it is practice to attribute the open circuit power to core loss.


What is meant by the term transform?

ideal transformer is that which has no power losses.if any transformer transfer power to secondary without power loss then that call a ideal transformer