answersLogoWhite

0

📱

Electrical Wiring

Ask questions here about proper wiring and electrical installation here.

4,935 Questions

How many volts should be across each line on a 3 phase motor?

Three phase means just that- three phases in the windings of the motor. Therefore three leads (outputs) are used to supply power. A lot depends on the number of wires coming out of the motor. In large industrial motors, you can have 9 leads. The wiring of the motor depends on the application- the motor will either be wired in series (leads 1-4-7, 2-5-8 & 3-6-9 combination) or parallel (4-7, 5-8 & 6-9 with the first three leads connected separate).
To change the direction of the output shaft, simply reverse any two of the three leads.

How do you replace a 3 phase 5hp motor?

I assume that by two-phase, you really are talking about a supply with two hot wires and a neutral, such as 120/240 volt. This is single phase power, it just has power taps on both ends of the transformer winding, the neutral is the center tap.

I don't think it is possible to convert or rewire your motor. A large 3 phase motor must be run on a 3 phase electrical supply. It will not run and will overheat if you try to connect it to a single phase supply. The only way to make a 3 phase supply from a single phase supply is to use a converter like a motor-generator set. That would be way more expensive than getting a new motor.

How will a 3 phase rcd work with no neutral?

a traditional rcd wont work as it uses the difference between the incoming active and neutral to detect current loss it has to read 0.

In particular, an RCD alone will not detect overload conditions, phase to neutral short circuits or phase to short circuits. Over-current protection must be provided.

Application of full wave rectifier?

Transformer is used to step down the voltage. Your normal supply voltage is 230V but diodes used in rectifier can't handle that huge voltage hence this voltage needs to be reduced. This is done by transformer. Transformer brings down 230V voltage to say 10V. If you are talking about step down transformer than you should know that step down transformer produces equal voltages although opposite in polarity but equal in magnitude(ie +V and -V) across both diodes. If you don't use it the voltage across one diode may be greater than voltage across other diode. Say non-center tapped transformer produces 10V across diode D1 & -8V across diode D2. In next half cycle, -10V will be produced across d1 & +8V across D2. So in first half cycle current due to forward biased diode D1(as voltage across it is greater) will be greater than the current produced due to diode D2 in next half cycle. So rectified current waveform won't be equal.

The transformer is for isolation so the full wave rectifier can float free of the line hot & neutral wires. The power supply can then define its own ground node without "fighting" the line, this is also much safer for the user. Step-up, Step-down, or one-to-one transformer types are irrelevant to full wave rectifier but are selected by the needs of the application. There are solid state diodes that can handle several thousand volts if the application needs it and vacuum tube diodes that can go even higher.

Full wave bridge rectifiers do not use center tapped transformer secondaries, but require the isolation the transformer provides or diodes will blow out in operation!

What does normal phase mean?

The normal phase of an element is:

What form it is (liquid ,solid ,gas)

what the classification is (nonmetal ,metal ,metalloid)

Can you use two separate 120 volt circuits to make 240 volt power and run 30 amps through the circuit they are both wired with 12-2 wire?

Yes because the total load is only 18 amps. It would be more usual to allow three 9-amp circuits on a 20-amp breaker because the total current would probably not exceed 20 amps at any one time.

How many ohms will a multimeter read for an open circuit on a car?

As close to zero ohms as makes no difference.
Zero, or close to it. It should be nearly the same as if you touch the probes together.

What is proper ground wire size for 100 hp 3 phase motor?

Wire size is based on the amperage that the load requires. For an accurate answer the motor amperage is needed. That said you can get an approximate figure by this method. 1 HP = 746 watts. This formula for amperage when HP is known. HP x 746/1.73 x Voltage x %Eff x pf. Use a Efficiency % at 90 and a power factor of .85. A horse power of 5 x 746 = 3730/1.73 x 220 x 90% x .85 = 12.81 amps. Code states that motor supply conductors have to be 125% of the full load amps = 16 amps. Code also states that conductors can only be loaded to 80% on continuous load which a motor falls into. A #12 copper wire 90 degree insulation is rated at 20 amps x 80% = 16 amps. A #12 wire will do the job. It will need a 40 amp three pole breaker, 50 amp non time delay fuse or a 30 amp time delay fuse to feed the motor.

On a standard three prong AC outlet what should the AC voltage measure between hot and ground?

Any where between 220 and 240 volts are a nominal figure in the same voltage range. It is brought about by the power company, as they have a responsibility to keep voltages within a certain 10% range. The load will only notice a difference of 1% on the load current. eg. Wattage load of 2400. Amps = watts/volts. 2400/240V = 10 amps. 2400/220V = 10.9 amps.

What is the height of a 220 kv tower?

It depends on the country you're in (what codes apply), local utility standards, land being crossed (is it hilly?), type of structure/configuration of wires, and the distance between towers. At its' lowest point, the conductor could hang ~25 feet off the ground.

How you differentiate between single phase and three phase transformer?

A single-phase transformer works with a single-phase supply, while a 3-phase transformer is used with a 3-phase supply.

A single-phase transformer has 2 wires on the primary and secondary (ignoring taps) while a 3-phase tansformer has 3 or 4 wires on the primary and secondary.

What is zener break down voltage?

The point in the forward operating region of the characteristic curve where conduction starts to increase rapidly is called Knee voltage of a PN Junction Diode.

The breakdown voltage of a diode is the minimum reverse voltage to make the diode conduct in reverse.(or) Breakdown voltage is a parameter of a diode that defines the largest reverse voltage that can be applied without causing an exponential increase in the current in the diode.

-- Dinakar

What is caused by a short circuit?

A short circuit is a low resistance connection where one is unexpected. It causes a diversion of current from the intended load, and, since it is usually a higher than expected current, it often causes the protective device (fuse, circuit breaker, or relay control logic) to trip.

How do you convert a 3-phase power supply to a single phase supply?

The simplest answer is that the electric utility uses a transformer across 2 of the 3 hot leads to develop a single hot lead with an earth reference. What follows below is frequently edited by both amateurs and professionals, with mixed results. Wikipedia is a better source of more detailed information on this subject, in part because the article on three phase power has pictures.

How many wires are there in 120 volt single phase power and how are they marked?

Verify wiring layouts by making measurements, before connecting and/or energizing equipment. A 120V single phase 2 wire should have one hot wire, a 230V single phase 2 wire should be assumed to have two hot wires, and a 230V single phase 3 wire also should have two hot wires.

What is 230 volt 3 phase?

for USA, Canada and other countries running a 60 Hz supply service.

230 volt single phase refers to the two hot wires in standard house wiring but with the absence of the common return line, aka as the neutral wire.

As using only the "hot" side of phase one (120 volt) and only the "hot" side of phase two (120 volt), so that these two lines yield 240 volts in phase with each other, it is called "single phase".

This is sometime called 230 volts, "double phase" due to the two hot wires. Since both wires have the same phase, the term "double phase" is incorrect. As the two hots are balanced around the neutral point, "Split single phase" is the correct term to use.

Typical usage examples for 240 volts split single phase include: water heaters, electric clothes dryers, water pumps for wells, central and some larger window air conditioning units, air handlers, electric heating units, floor sanders, and portable arc welders.

For Europe

230 V is the standard nominal voltage for single-phase electrical services to residences in Europe. It is obtained from a wye-connected, three-phase, four-wire, 400/230-V transformer secondary, by connecting between any line conductor and the neutral conductor.

How do you build a power tube amplifier with out bias?

You cannot build a power tube amplifier without bias. At minimum, you need some kind of negative bias on the control grid, and you might need positive bias on the screen grid as well as cathode voltage on the suppressor grid.

Can a single phase generator run a 3 phase air conditioner?

Depending on who does the work it could be less expensive than getting a different air conditioner. The compressor will also need a capacitor and some rewiring. The old unit could have a 3 phase blower motor also which could run the price up even more. Although the changes can be made, the warranty at best will probably be a one year warranty and a new unit could have a 5-10 year warranty.

Why does an Electric circuit breaker have a melted wire?

Wow that is hugely dangerous and a risk of fire. They get hot because you are running a large amperage through them, melting cause it is overloaded.

For example. If you had a 20 amp breaker, and 12 gauge wire (20A), and a 15 amp recepticle. Then the most you would want to run on that recepticle is 12 amps continuously, 15 amp peak non continuous. If you replaced the recepticle with a 20 amp recepticle you could run 20 amp peak, or 16 amps continiously. You could not go with a higher amp outlet as the circuit only has 12 gauge wire, and a 20A breaker.

If you plugged something with a 30 amp draw into said outlet you would get the outlet hot.

find out how many amps you are drawing off the outlet in question, then check the gauge of the wire in the wall, and the rating of the outlet and breaker that outlet is off of. Then we could decide what to do next.

Well,Being a Electrician, my advice is if you have to ask question about that call a Electrician IMMEDIATLY!!!!It could be a number of things.A loose wire in the back of plug in,worse yet a broken wire that keeps rubbing together ,(EXTREME FIRE HAZARD)Electricity is nothing to fool with if you are not trained.BE SAFE<SMART.Turn circut breaker OFF.CALL ELECTRICIAN

Really,cmon. Residential pulling that much power off ! outlet.....look outside the box!!how old is house would be first question

How to choose rating of contactor in star delta starter?

As well as motors, contactors also have kW and Ampere ratings. Have a look on the name plate of your motor and you will see its maximum current draw (amps). Select a contactor with a current rating greater than this.

What is the formula for total current in a series circuit?

Current = (Voltage across the circuit) divided by (Total resistance of the circuit).

The current is the same at every point in the series circuit.

What is the connection procedure of star-delta connection in 3 phase motor?

Higher capacity (higher KW rating) motors take huge starting current to get over the starting torque. To avoid the high inrush of current, star delta starter is used. When started, the motor gets connected in star for few seconds and switches over to Delta and continues to run in delta. In this case motor is designed to run in Delta.

Is delta connection also called a star-star connection?

the delta has a higher voltage to ground on the B phase and is identified by the orange color for identification means so its easier to smoke equipment if not careful.hardly see delta connections anymore so old school and outdated. it just makes economic sense to use a star connection.

<<>>

On the above answer there should be no voltage to ground on a delta connection. All three phase coils are connected in series with each other and at no point in the delta are they grounded. Most of the commercial and industrial motor connections are connected delta. In installations where the motor inrush is above utility company specifications the Star- Delta connection is used. This limits the inrush current in the star configuration and then after a time delay connects the motor in a delta configuration. With delta systems the use of grounding lights are mandatory. These are used to detect if a phase grounds out. One phase and the motor can still be in operation, two grounds represent a short circuit and the system will trip.

Comment

The second answer is not altogether correct... In the USA and Canada, it is common practise for one phase of the delta-connected secondary windings of a three-phase transformer bank, to have an earthed (grounded) centre tap. With each phase providing 240 V; the centre-tapped phase then provides a combination of 240 V line-to-line together with two 120-V line-to-neutral (earth) voltages which is the standard supply method for residences in North America. The point of common connection between the two remaining phases is termed the 'high leg' of that particular transformer connection, having a potential of 208 V with respect to earth (although this is not used). To summarise, this method provides a 240-V three-phase supply, combined with a single-phase 240/120-V supply, which is useful for small businesses (e.g. garages) which might need to operate three-phase motors.

However, the second answer is perfectly true for the UK (and, possibly, elsewhere in Europe) where residences are supplied with just one voltage (230 V) -unlike North America- and delta-connected supplies are relatively unusual.

How many amps will a 10 kva transformer handle?

It depends on how many amps it was designed for. A 12.5kV/600v 10kVA 3 phase transformer can handle ~.5 amps on the primary and ~10A on the secondary. A 600/120V 10kVA 3 phase transformer can handle ~10A on the primary and ~50 on the secondary.

What are phases in electrical supply and how do they work?

'Phase' refers to a winding into which a voltage is induced in an alternator or in a transformer or motor. The voltage across a phase is known as a 'phase voltage', and the current through it is a 'phase current'.

'Three-phase', means that there are three such windings in a machine, physically displaced from each other by 120 degrees, with each phase voltage is displaced by 120 electrical degrees.

The term 'phase' is sometimes, incorrectly, used to describe the 'hot' wire in an electrical installation -the correct term, though, is 'line'.