How do vegetables conduct electricity?
its cuz they r so awesomely electric if u eat an aple u can get shoked and die
---------------------------------------------------------------------------------------
The vegetable to conduct electricity it must contain free ions like in lemon, which contains free ions as it is acidic.
What KVA transformer is needed to convert 480v - 240v 13.5A load?
Ohms law says that watts are equal to volts times amps.
240v X 13.5a = 3240 va
VA / 1000 = Kva
So, your load requires 3.24 Kva. The transformer should have a rating greater than this as a safety factor, so you would choose the next larger size, in this case probably a 5 Kva transformer with a 480v primary and a 240v secondary.
Your local electrical codes may require a larger safety factor, so you would want to consult them before buying the transformer!
How do you do a megger test on a current transformer?
The megger test on a generator is usually done to check the insulation factor of a generator. The high voltage is usually used to test the insulation system of a the generator in question. It is recommended to do this test after every six months.
What is the current carrying capacity of 10 awg wire?
For cables in 'Free Air', that is, not routed through conduit, it depends on the Temperature rating of the cable; 60 deg C: 40 amps, 75 deg C: 50 amps, 90 deg C: 55 amps <><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
What is a phase shifting transformer?
This applies to three-phase transformer connections. 'Phase shift' or 'angular displacement', is defined as 'the angle by which the secondary line-to-line voltage lags the primary line-to-line voltage'.
Angular displacement depends on the type of transformer connection. The most common are:
The angular displacement for all possible combinations of three-phase transformer connections are listed in transformer vector group charts.
Angular displacement determines whether or not it would be possible to parallel different types of three-phase transformer connections. For example, from the above data, it would be impossible to parallel, for example, a delta/delta transformer with a delta/wye transformer.
How to control the starting current of motors?
the starting current of motors can be controlled by using an additional resistance in the beginning and gradually decreasing it.Motor starters do the same
An Automatic Power Factor Correction (Controller) panel is used to Save Energy by consistently maintaining higher power factor. Low Power Factor leads to poor power efficiency, thereby increasing the apparent power drawn from the distribution network. This results in overloading of Transformer, Bus bars, Switch gears, Cables and other distribution devices within the Industry or consumer area.
With an APFC the energy producer can:
What are the M L C V terminals of a watt meter?
The M terminal connects to the power supply.
The L terminal connects to the load.
The C terminal is shorted to the M terminal.
The V terminal connects to the systems neutral.
What is the voltage level of two phase machine in three phase?
From one phase to the next you should see 208 Volts.
From any phase to ground you should see 121 Volts.
AnswerYou are very unlikely to come across a two-phase machine, as two-phase a.c. systems are archaic. A two-phase system has two phase voltages that are 90 degrees out of phase with each other, and was used many years' ago. These days, you have either single phase or three phase. So it's probably safe to say that there are no two-phase motors about, these days!
How can you convert a 3 phase 208 volt pizza oven to 240 volt 1 phase?
Eliminate one wire from the 3 phase 208 volt and install a 240/250 volt 2 pole breaker . but the oven has to be rated for 240 volts check the nameplate on the oven or it will not work.
<<>>
Some three phase resistive load devices will allow the device to be used on single phase. The wiring diagrams will be on the nameplate of the device. It usually involves the repositioning of jumpers to create new connections within the device to keep the resistive coil currents equal. This is to provide equal heating throughout the oven. Other wise there would be cool spots where the third phase leg resistive coils had been taken out of the circuit.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS
When is a voltage drop calculation considered when determining the cable size?
The voltage drop in a cable is the current multiplied by the resistance. For a twin-wire cable the resistances of the two wires are added. Cable resistance for different sizes of cables can be looked up in wire tables.
More detailed answer for USA, Canada and countries running a 60 Hz supply service.
Voltage drop and cable size can be calculated by looking at tables that are available in the National Electrical Code. Some of these tables are difficult to understand and will require you to seek assistance. You can also determine the amount of voltage drop over a distance by finding the resistance of the cable for a specific temperature(given in ohms/1000ft)from the cable manufacturer or electrical wholesaler. If you know the largest amount of current that will flow in the cable, then use the formula:
Vdrop = Current X Distance(Ft) X 2 X Ohms per 1000Ft x 0.001
[Note: the 0.001 fixes an earlier error in the formula where the contributor didn't divide out 1000 ft by using R/1000ft!]
<><><>
Voltage drop is a complicated calculation done by electricians. I don't know what you're trying to run but let me just give you the rule of thumb. If you run out over 200 feet of wire for the job in hand, you should jump up a wire size in order to have sufficient voltage at the other end. For example. Let's say you are going to wire and out building for your workshop and you need only 120 volt receptacles at the shop end to run your power tools. Power tools run at the nominal voltage of 120 volts, but they operate within a range, say 108 to 128. This allows for how close your are to your distribution companies source. I don't know what your starting voltage is so that's why the rule of thumb. To your outbuilding you only need #12 to carry 20 amps for your tools and lights etc. If you have to exceed that distance, then you would jump up to #10 in order to have sufficient voltage at the other end. If you are starting at 115 volts at your house, and are running 100 feet, I would still up the wire size. You can't go wrong by going one size bigger on your wire. When in doubt, always consult a qualified electrician.
<><><>
Many electricians wire for no more than 5% voltage drop. This is usually fine since appliances and power tools are made to operate over a range of voltages. For a more expensive way to wire a house, you can try wiring for no more than 2% voltage drop. In this case, if you are running 20 amps, you need to up the wire size to #10 if you go more than 35 feet. In general, the percentage voltage drop decreases with a higher starting voltage. To see this, play around with the formula for voltage drop given in terms of resistance. The resistance of various sizes of wires can be found in the CRC handbook. Practically, this means you lose less power to voltage drop if you choose a 240 volt appliance instead of a 120 volt one. And you lose a lot with low voltage lighting running on 10 or 12 volts.
<><><>
The formula for voltage drop is Vd=KIL/CSA where Vd stands for voltage drop, K stands for the resistivity factor of the material [I think copper is around 7 and aluminum 11], I is the current in Amperes, L is the round trip length of conductor, CSA is cross-sectional area of the conductor in circular mils
You can get the CSA values from chapter 9 table 8 of the NEC
CSA for 14 is 4,110; 10 is 10,380; 8 is 16,510; 6 is 26,240
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
Can you wire a 3 phase 690 volt delta star motor to 480 volt 3 phase with out harming the motor?
Depends on the motor and the load on that motor. If the motor is loaded to its capacity, it will draw the same amount of power as it would on 690 volts - which will result in ( 690/480 = ) 144% of normal current, which will thermally damage the motor, or will trip overload protection.
In a 3 phase 480 panel what voltage should you get phase to phase?
The voltage you are referring to is a 'line-to-line' voltage ('line voltage'), as there is no such thing as a 'phase-to-phase' voltage.
480 volts. In real life, the voltage will vary slightly by up to 3% (14 V) on a properly sized circuit. Line to neutral will measure 277 volts, plus or minus 3%.
What would be the size of Cable for a 40 kw 3 phase oven?
It is not possible to answer the question without knowing the supply voltage. Conductors (wires) are sized according to current (amps), not KW. Amps = watts / volts As you can see, there is no way to determine amps (needed to size the wire), without knowing both the KW and the voltage. If this is on a test, it is a trick question. If you are really trying to size a cable for a real stove, hire a licensed electrician! Improperly sized wire can start a fire.
What is the Formula to calculate KVAR?
{| |- | capacitance of the capacitor is mentioned in KVAR. Formula : KVAR = KW*tan@ FOR tan@, First note the power factor & KW without connecting capacitor. The noted power factor is in cos@.Convert the cos@ value in tan@. for ex. If power factor is 0.6, KW = 200 cos@ = 0.6 cos-1 (0.6) = 53.1 tan (53.1) = 1.333 200*1.333 = 266.6 KVAR if you use 266 KVAR capacitor, Then the power factor improves to unity (1.000). |}
What are the advantages and disadvantages of oscillators?
The biggest disadvantages with oscillators are that they have to be stabilized with control heaters. If the oscillator is operated in a non temperature controlled environment it will drift off frequency and it is not good policy to transmit over a wider that necessary bandwidth. The frequency on either side of the offending transmitter will be affected.
One volt is the electric potential required to generate one ampere through one ohm.
One volt is the electric potential involved when one ampere generates one watt of power.
One volt is one joule per coulomb.
What is a combination of volts and amps?
Specifically, Volts and Amps would be called VA or volt amps, as in the rating of a transformer, but it is loosely referred to as Watts. In DC theory, Volts mulitplied by Amps equals Watts. In AC theory, that same equation exists but it includes power factor. If the power factor given is 1 (100%), then Volts mulitplied by Amps multiplied by Power Factor of 1 equals your Watts.
How do you wire a 12 lead motor in star delta?
This is a 3-phase, dual-voltage motor. The 12 leads represent six different windings. For the higher voltage, pairs of windings are connected in series, then the three resulting pairs are connected into a delta configuration to tie to the power source. For the lower voltage, the pairs of windings are instead connected in parallel before combining them into the delta configuration. The windings MUST be combined in the proper order AND in the correct phase for it to work. Mistakes result in great quantities of smoke being released! Each of the leads should have a label, such as T1, T2, T3, etc. It will be either an adhesive label or sometimes printed in ink right on the wire. There is no standard labeling scheme, so each manufacturer always shows the connections for each voltage on the motor nameplate. There is no real way to guess at this, if the nameplate is missing contact the manufacturer for a diagram.
What are the tools you need to buy for motor rewinding?
I want to purchase some tools for electrical motor rewinding work hence please give me list of tools available to u with price list.
E-MAil- davidph68@hotmail.com
What are the examples of electrical wirings in the house?
the cable sizes are...:
lighting=1mm-1.5mm
sockets-boiler controls=2.5mm
cooker=6mm
shower=10mm (can vary depending on the showers output)
earthing conductor of 10mm
earth bonding conductors of 6mm
25mm tailings (you're supply cables from the meter)
The sizes also depend on weather or not the cable is wired in old colours (i have only entered the new cable sizes)
circuits used are...:
ring main.
radial=only used if there are limited sockets being installed on a circuit.
lighting is just 1 cable going out and spreading to each light and switch (upstairs and downstairs lighting should be on a separate mcb)
cooker-1 cable going out of mcb.
shower-1 cable going out of mcb.
I hope this information helps as i don't fully understand what you are wanting to know from you're question. If you need any more help please let me know, or anyone else for that matter.
What should be the primisable voltage between neutral and earth in a three phase system?
It is the line to line voltage divided by 1.73.
600V / 1.73 = 347V
480V / 1.73 = 277V
380V / 1.73 = 220V
208V / 1.73 = 120V
Megger testing is done with DC or AC votage?
Earth testing results should be related to the voltage source, i.e., AC in most situations. AC reacts to resistive and reactive loads, DC to resistive loads only.
Not all earth testers, however, use AC.