answersLogoWhite

0

📱

Electrical Engineering

Electrical engineering is a field of engineering that deals with the study and application of electricity, electronics and electromagnetism.

23,056 Questions

What does it mean when you say that lines in a home are overloaded?

lets say each outlet will take up to 15 amps.a toaster will usually be rated at 1200watts.at 120v.divide 120 into 1200 =10 amps.so if you had 2 toasters connected to the same outlet you would be using a total of 20 amps on a 15 amp circuit.this outlet would be overloaded.

How do you determine which side of a breaker is line or load?

The breaker should be legibly marked, or the line side will clip onto the bus bar, and the load side should have a termination screw of some kind for you to attach a wire to it.

Some bolt in breakers are not marked, the type you may use in a custom control cabinet and it can be confusing. When vertical mounting, always set the breaker so gravity would open the breaker. Attach the line side to the top lugs. Horizontal mounting, just make sure it is marked for the off position, use either end for load or line.

Is the typical order for a substances transformation through phases?

The typical order for a substance's transformation through phases is solid → liquid → gas. This sequence represents the heating process where a substance gains energy to break the bonds holding its particles together, eventually leading to a phase change.

When calculating kilowatts from known amps on a 3 phase circuit do you use 415 volts or the 240 line volts in the equation?

You can use either. I assume the 240 volts is the line to neutral voltage, and the 415 is the line to line voltages. They will both give you the correct answer. It is important to note these values are RMS, not 0 - peak voltages, but this may be beyond your question. The equations below are for calculated from RMS values (both voltage and current).

If you are using a L-L voltage, P = I*V*sqrt(3)

If you are using the L-N voltage, 1-phase power P = I*V (for the power in a single phase, for all three, multiply by 3), or 3phase power P = 3*I*V


You will get the same answer, since the L-N voltage is (1/sqr(3)) times the L-L voltage.

How do you make an AC motor go in forward and reverse?

If it is a three phase motor just interchange any two of the three wires. If it is a single phase motor, which is also known as a split phase induction motor, it has two sets of coils and a centrifugal start switch. The start winding is in series with the start switch. The start winding provides a rotating magnetic field in one direction enabling the motor to start. The motor can be reversed by reversing the connections of either the start winding or the run winding but not both.

Which feature has a hollow central tube?

A hollow central tube is characteristic of a hydrothermal vent, which is a fissure in the Earth's surface that releases geothermally heated water. These vents are typically found on the ocean floor near tectonic plate boundaries.

What is the running amps of a 45 kW motor?

To determine the running amps of a 45 kW motor, you would need to know the voltage at which it operates. You can use the formula: Amps = (kW x 1000) / (Volts x power factor). Once you have the voltage and power factor information, you can plug them into the formula to calculate the running amps.

How do you ground one of the phases from three phase three wire in order to make single phase?

To convert a three-phase three-wire system to single-phase, you should ground one of the phases using a grounding rod or electrode. However, please note that this method may not adhere to electrical codes and safety regulations. It is advised to consult with a qualified electrician before attempting any modifications to your electrical system.

Unit of electric resistance?

The unit of electric resistance is the ohm, represented by the symbol Ω. It measures the opposition that a material has to the flow of electric current through it. Smaller resistances allow for a larger current flow, while larger resistances restrict the current flow.

Compare between single loop circulation and double loop circulation?

In single loop circulation, blood flows through the heart and body in a single circuit, while in double loop circulation, blood flows through two separate circuits in the body: pulmonary circulation and systemic circulation. Single loop circulation is found in fish, while double loop circulation is found in humans and other mammals. Double loop circulation allows for separation of oxygenated and deoxygenated blood, leading to more efficient oxygen delivery to tissues.

What are the differences between a vacuum breaker and a SF6 gas circuit breaker breaker and a sf6 gas circuit breaker?

A vacuum breaker uses a vacuum to extinguish the arc when interrupting a circuit, while a SF6 gas circuit breaker uses sulfur hexafluoride gas. SF6 gas circuit breakers can handle higher voltages and currents compared to vacuum breakers. SF6 gas circuit breakers are also more environmentally harmful due to the greenhouse gas SF6, while vacuum breakers are considered more eco-friendly.

Application of Y-delta transformations?

delta-wye is a common type of 3-phase transformer configuration. It offers a good voltage gain and the delta transformer is useful in unstable systems for removing the third harmonics. The transformation is necessary for analyzing the circuit.

What is the difference between b type c type and d type miniature circuit breakers?

The different types are rated by how much current above its rated current will trip the breaker instantly (less than 100ms). Type B 3-5 times. Type C 5-10 times. Type D10-20 times. For example a 10amp type B breaker will instantly trip (less than 100ms) at between 30-50amps.

What is step voltage?

Step voltage refers to the difference in voltage between two points that are a short distance apart on the ground. It is a potential hazard that can occur during electrical grounding faults, such as when current flows through the ground due to a fault in an electrical system. Step voltage can pose a risk of electric shock to individuals standing near the faulted area.

Is Earth's current polarity normal or reversed?

Earth's current polarity is normal. This means that the direction of the magnetic field is aligned with what is considered the usual orientation, with the magnetic north pole roughly aligned with the geographic North Pole.

Size 134 kva cable?

A 134 kVA cable typically refers to the size of cable required for a 134 kilovolt-ampere electrical load. The size of the cable needed will depend on factors such as the length of the cable run, the voltage drop allowed, and the type of insulation and conductor material required to safely carry the current. It is recommended to consult with a qualified electrical engineer or contractor to determine the specific cable size needed for your application.

Predict whether a fuse will work successfully if it is connected in parallel with the device it is supposed to protect?

A fuse will not work successfully if it is connected in parallel with the device it is supposed to protect.

First, it will blow because it has no resistance in series with it. Second, once it blows, the device still has power applied to it. Fuses must be wired in series.

What is the resistance of a conductor that carries a current of 120 amperes when the potential difference between its ends is 240 volts?

The resistance of the conductor can be calculated using Ohm's Law: resistance (R) = voltage (V) / current (I). Plugging in the values gives: R = 240 V / 120 A = 2 ohms.

In three phase supply 415volts when i measured RY BY RB one of them shows 380volts rest two are show is below 150volts What is the reason can all of you clarify me?

It seems like there is an imbalance in the voltages between the phases, which could be due to a fault in the electrical system, such as a loose connection or a faulty transformer. This imbalance can lead to issues with the equipment connected to the system and can cause overheating or damage. It is recommended to consult with an electrician to diagnose and fix the issue.

How do you calculate the fuse rating level if the full load is 4 amp?

To calculate the fuse rating level, you typically want to choose a fuse that is slightly higher than the full-load current to avoid nuisance tripping. For a full load of 4 amps, you could choose a fuse rating of 5 or 6 amps.

What are good electricity answers websites?

Some good electricity answers websites include Energy.gov, EnergySage, and The Electric Power Research Institute (EPRI). These websites offer reliable information on various electricity-related topics such as renewable energy, energy efficiency, and the electric grid.

How do you calculate short circuit capacity of generator by using reactance of the winding?

The short circuit capacity of a generator can be calculated by dividing the generator's reactance by the sum of the generator's reactance and the total reactance of the system. This ratio will give you the short circuit capacity of the generator in relation to the total system capacity.

Trending Questions
What is the use of post insulator in sub-station? How do you build a pressurized system? What is the relation between load and resistance? Why using surcharge for cbr test? What will be the power factor if the load is non linear? How many ohms is 863 k ohm? What would make the voltage regulator smoke on a 1998 Arctic Cat 500 4x4 ATV? What is the difference between main contactor and axualiary contactor? What is relay circuit? What is the adjustable contact of a linear potentiometer is set at the mechincal center of adjustments if the total resistance is 1000 ohm? What are the electricity problems in Pakistan? Why does my star delta motor run at very high amps in delta and eventually trips on overload after changing the overload protection device.It should normally run at 25amp in delta but runs at 170 amps? Power factor is not greater than unity? What is Meaning of basic impulse level? How does the Resistance and Wattage relate to maximum voltage of a wirewound resistor? 3 inductors connected in parallel. Inductor 1 has an inductance of 0.06 H inductor 2 has an inductance of 0.05 H and inductor 3 has an inductance of 0.1 H. What is the total inductance of this circuit? What size fuse do you use on 800kva transformer? How much electrical resistance would you expect an ohmmeter to indicate if it were connected across the combination of these two series connected resistors of 3.3 kilowatt ohms and 3.3 kilowatt ohms? How do you reduce kva demand? Using ohm's law what is the formula to find the resistance in a circuit?