Is the maximum voltage in an ac circuit when the rms voltage is 110 volts?
It depends on the equipment. The power supplies on most devices can only handle a specific voltage and still work properly. Some, for instance some cell-phone chargers, can handle a range of voltages, say from 110 to 240, which lets them operate in both the States and the UK (where the standard home/office voltage is 230 Volts). Check the label on the back of the device; it will usually show the operating voltage required. Asking the maximum voltage for 110 equipment is valid. 110 means AC voltage that averages 110 volts as it swings above and below 0 volts. The label on a device typically will not tell you the maximum voltage it can withstand if it is plugged into a U.S. 110 volts AC outlet.
U.S. houses are wired with 2 hot wires (each 120 Volts AC but opposite of each other) and a neutral wire (0 volts). That way electrical outlets can be wired for 120 Volts AC if they use a hot wire and the neutral wire... or 240 volts AC if they use both of the hot wires.
If the neutral line goes bad then the 120 volts AC outlet floats anywhere from 0 volts to 240 volts. I have been in a house when this occurred (the neutral corroded on the transformer that fed several houses). Supplying too high a voltage burned out an air conditioner, a refrigerator, and an incandescent bulb actually burst, scattering glass close to my wife. The air conditioner threw out a lot of smoke so there was a danger of fire.
In the U.S. a typical 120 volts AC circuit often has a higher voltage. I have seen specifications and codes that put an upper allowable voltage at 120 volts AC, 137.5 volts AC, and 150 volts AC. Every electrical device has different limits but I would not subject anything built for 120 volts AC to voltages higher than 132 Volts AC unless I had specific knowledge that the device could handle the higher voltage.
Difference between 3 pole and 3 phase?
Phases in AC refer to the number of sine waves of alternating current used to generate the average voltage. In 2 phase, two opposing sine waves are overlapped to give the average voltage delivered, eg 240V in household supplies.
In 3 phase, three sine waves are overlapped to produce a more consistent average voltage.
What happens if dc supply is connected to incomer of transformer?
If a DC supply is connected to the incomer of a transformer, you effectively have a short circuit, because the DC impedance of a transformer (actually, any inductor) is quite low. You will blow something.
How demagnetize an electric motor?
A transformer winding only produces a magnetic field when current flows through it. Switch the current off, and the magnetic field disappears. You do not need to 'demagnetise' a transformer winding.
How does a circuit breaker help protect against short circuits and circuit overloads?
Quite simply, so you don't put too much current on the wires than they can handle. They also provide protection from 'ground faults', which is when the 'hot' and neutral wires touch. This causes a spike of current (because the resistance drops to near zero) and the breaker senses that too, or it should when it functions properly.
How does conservator work in transformer?
To allow room for oil expansion and contraction. The transformer is completely filled with the oil and when it heats up under load or due to ambient temperatures, the oil has to have a place to go. In the event of colder weather or if the transformer is not under heavy load the oil cools and contracts creating a slight vacuum inside the tank. The conservator acts as a reservoir of oil that can then flow back into the tank so that no air enters it.
Principle and working of synchronous motor?
Principle of synchronous motor is as given below:
"when a 3 phase winding is fed by a 3 phase supply, then a magnetic flux of constant magnitude but rotating at synchronous speed, is produced."
What are the standard voltages of 3 phase induction motor being manufactured?
The stator and rotor of a machine are not made from sold pieces of metal. They are constructed by clamping stacks of thin sheets of silicon steel, called 'laminations', together. Laminations are essential to minimise circulating currents due to voltages induced into the core/rotor when the machine is operating. These laminations are created by a stamping machine, which cuts the required shape from large sheets of thin metal.
CT ratio is the ratio of primary (input) current to secondary (output) current. A CT with a listed ratio of 4000:1 would provide 1A of output current, when the primary current was 4000A.
Why it is incorrect to say the voltage at point x is 12volts?
Voltage is the electrical potential difference between two points.
How many amps will a 55 KW motor take?
250 kW= 250,000 watts
1 horsepower=746 watts (The motor is approx. 335 horsepower. (just FYI))
The Ohm's Law formula for this is:
P(Power in watts)=I(Current in amps) x E(Voltage)
Since the voltage is unknown, I will give you different options based on input voltage.
I will assume three phase power for a motor this size.
So, back to the formula:
250,000=I x E
Let's assume voltage (E) to be 480v:
250,000=I x 480
I=520 amps
For a voltage of 208 (much less likely for this size motor):
250,000=I x 208
I=1201 amps
These are 'running' currents only. The amount of starting current will be much, much higher, but only for a brief period.
AnswerThe above answer assumes that the motor's input power is 250 kW. But this is not the case.
The power of a motor is always expressed in terms of its output power, not its input power! In North America, this is expressed in horse power, whereas everywhere else it's expressed in watts. So, to determine the current drawn by the motor, you have to start by determining its input power (input power is output power times efficiency); if you don't have a means of determining the motor's efficiency, then you cannot really find out its input power, in which case, you cannot find its current.
The armature has the stationary (not physically moving) magnetic field, which attracts the magnetic field in the rotor. Since DC does not alternate, a split ring is used to alternate the current (and resulting magnetic field), so that the rotor will spin.
Difference between overload relay and over current relay?
due to the extension of loads they are using the relays for protection.........
What is the Voltage in a overhead train wires?
you can get an idea by looking at the insulators
they must function in rain or snow
dew can collect on the insulator
they are made of porcelain with a glazed surface
3" diameter gives about 3" length of dew coated glaze and is safe at about 5000V
so if the insulator has 3 skirts its about 15,000V
10 skirts about 50,000V
the drops to the houses are low voltage and may be as little as 1/2 of glazed surface 600V or less
Is there any difference in the power consumption by a same rating motor in 1 phase or in 3 phase?
The power consumption is the same in both cases. For a high-power motor it is more efficient to feed a 3-phase motor because the amount of power wasted in the wiring that feeds the motor is less, assuming the same size of wire.
What is a emergency generator?
An emergency generator is attach to a location power supply and electricity. When the power supply or electricity shuts down unintentionally the emergency generator will send power to the things that it is attached to that is designated, until the main power is back on.
What could be the cause of overspeed in a diesel generator?
The causes of over loading in generator comes from the action of applying more load that the generator is rated for. An example using a 5000 watt generator and a connected load of 6000 watts.
Advantage and disadvantage about AC electric power with frequancy 50 HZ and 60HZ?
110 vs 230 Vac - The lower voltage is safer, but requires more current and larger wires. (BTW, the transmission loss is not worse because of 110 Vac because everything is distributed at much higher voltages, it only becomes 110 at the transformer near your home).
60 vs. 50 Hz - The higher frequency allows for the use of less iron in transformers and motors, but at the cost of more losses in the distribution system.
Why interturn test is done to transformer?
The symptoms of an interturn fault are loss of power output (blown fuse) and distortion as in audio power transformer. In power transformer there will be excessive heat as power is being comsumed. Using LCR meter to determine these 2 values of each winding 1) DCR 2)inductance. Compare the value obtained with a good one. There should be some differences in DCR and particular noted the low or no inductance in case of interturn shorting as if output winding is being shorted. The symptoms of an interturn fault are loss of power output (blown fuse) and distortion as in audio power transformer. In power transformer there will be excessive heat as power is being consumed. Using LCR meter to determine these 2 values of each winding 1) the DCR 2) the inductance. Compare the value obtained with a good one. There should be some differences in DCR and particular noted the low or no inductance in case of interturn shorting as if output winding is being shorted.
How do you calculate full load in single phase circuit?
The question has to be more specific. Full load amps, watts or voltage. Please restate your question.
Explain the need of power factor correction?
There are two types of power - real power and reactive power. Real power is power that is used, such as the power used to light a light bulb. Reacitve power is power that is held and released by a reactive element (capacitor or inductor), thus is not actually used to do any work. The reactive elements cause a phase shift between voltage and current, which manifests itself as a change in power factor.
Power companies must supply both reactive and active power. Total power is equivalent to sqrt( Reactive^2 + active^2). Not only do they need to supply the reactive power, their equipment must be sized to handle a larger total power. Reactive power is generated by installing extra equipment - capacitor banks or inductor banks - or by running generation in such a way that more reactive power is created (this will lower the power plants' real power output).
Depending on who the customer is, they may not be billed for the reactive power, thus the oversizing of equipment, and the supplying of reactive power does not generate any revenue (but costs them). If power factor is bad enough, the power company will lose money, and thus require power factor correction, or will bill on both real and reactive power usage.
It's simple economics (money)!
Why is the winding of the second phase reversed in the 3 phase synchronous motor?
That might be to make it run the right way.
What color is a computer ground wire?
Green or bare wire is used for ground conductors in US, Canada and countries which use similar wiring codes for 60Hz power supplies.
<><><> Green/yellow striped wire is used for ground conductors in Europe and other world areas which use similar wiring codes for 50Hz power supplies. IF YOU ARE NOT ALREADY SURE YOU CAN DO AN ELECTRICAL JOB
SAFELY AND COMPETENTLY
REFER THE WORK TO QUALIFIED PROFESSIONALS.
If you do this work yourself, always turn off the power
at the breaker box/fuse panel BEFORE you attempt to do any work AND
always use an electrician's test meter having metal-tipped probes
(not a simple proximity voltage indicator)
to insure the circuit is, in fact, de-energized.
Is line voltage or phase voltage mentioned on transformer nameplate?
It depends how they are connected. If they are connected between line conductors then they are measuring line voltages. If they are connected across phases then they are measuring phase voltages.
What is the use of reactor transformer in furnace?
Stabilise the arc and optimize the operation of the furnace.