Why short circuit is performed on high voltage side?

This is because of two reasons:

1. Primarily because SC test is performed at rated Current(as we calculate series parameters-leakage impedance-in SC test). As the rated current on hv side is much less than lv side(VI = constant), so the rated hv side current is easily achieved(compared to lv side). Vice-versa is true for Open circuit test.

2. Also because we cannot short-circuit hv side, as, if we short-circuit hv side, V of hv side essentially falls to zero and since VI(KVA power)=constant, so the hv current will be very high(compared to low rated current on hv side), and will burn the winding.

When short-circuiting lv side, the current also increases but this increase does not burn winding due to low rated V and high rated I (You can consider the example of 220/11V)on lv side. So,SC test is performed on hv side while shorting the lv side.

Also SC test can be performed on either sides for small transformer rating. The above care must be taken for big transformer(High KVA rating)..

How many hertz in household ac current?

In the United States and most western countries, the "line frequency" is 60 Hz. (formerly referred to as 60 "cycles per second"). In European and many Asian countries, the frequency is 50 Hz.

Due to the difference in line frequencies, devices with INDUCTORS (AC motors, transformers, etc.) are NOT interchangeable between 60 and 50 Hz. power sources.

The standard line VOLTAGE in the United States started out (circa 1940s) as 110 volts. Over the years, the "standard" was increased in steps of: 110, 115, and currently (no pun intended) 120 VAC.

Again, many European and Asian countries have utility power voltages in the 220 VAC range.

How do I use a clamp on amp meter?

Answer 1When electrical current flows through a wire [or any conductor[, it creates an electromagnetic field which the clamp on Amp meter is disigned to detect and quantify.

The meter loop is hinged and movable in order to open the loop to allow the loop to be placed "around" a single conductor. It is important that the loop be placed around only one conductor as if there is more than one wire conducting, then the fields from multiple wires will interfere with the meters ability to operate.

The meter will have a switch [usually rotary] to change scales, and unless you know the approximate current flowing through the circuit, you should first set the meter to the highest current scale setting, and then switch to lower current scales until the proper one is found.

Do you think Christmas lights are example of parallel or series bulbs in a circuit?

Parallel, of course. Each light has to receive the full voltage - 110 or 220 Volts, depending on the region. Also, if you disconnect one light, the others should continue working. This wouldn't be the case with a series circuit.

What is reheat factor in power plant?

The reheat factor in the steam turbine refers to the Thermodynamic effect on the turbine efficiency. Others factors includes the cumulative heat, and the steam turbine condition curve.

Why the current is equal in each resistor of a series circuit?

where else it would go through.....

the current entering the first resistor must pass through the next preceding resistors in order to reach the positive/+ve potential so as to complete the circuit.

Current flow is the actual flow of electrons so it goes from the ground (negative most point) to th emost positive point. lectrons are a negatve charged unit so they travel towards the positive point.

What is the switch on a overload?

to protect the source from overloading a switch can be opened as a circuit breaker, fuse, overload protection schemes

Three basic type of dc motor?

hair dryer, cars ,lawnmower ,generator ,computer ,pool ,cleaner ,tv ,plane ,cell phone ,fans ,heaters ,remote contrl car ,boat

For DC:

Permanent magnet brush motor; (uses fixed magnets for stator fields); toys and automotive use

Shunt field motor; (field winding has many turns of fine wire in parallel with armature) small machines;

Series field motor; (field winding has few turns of heavy wire in series with armature); high speed, high torque;

Compound field motor; (has both series and shunt fields); large machinery, general purpose workhorses;

Brushless DC motors (use electronics to switch stator windings on and off, and have permanent magnet rotors) small fans and light loads.

For single phase AC:

Split Phase induction motor (2 different windings connected to supply, cage type rotor) low torque, general purpose;

Capacitor Start induction motor; (As per split phase, but with capacitor in series with starting winding) high starting torque, general purpose;

Capacitor start, Capacitor run induction motor; (as per capacitor start, but different capacitors used for starting and running) high starting and running torque, quietest running;

Shaded pole induction motor; (run winding and copper or aluminium ring around part of iron core of stator) small, cheap motors, low torque;

Universal motor; (as per series DC motor above) high torque, high speed, poor speed stability.

For 2 or 3 phase AC (star or delta connected)

Polyphase induction motor (2 or 3 identical windings on stator, cage rotor) general purpose;

Wound rotor induction motor (2 or 3 identical windings on stator, wound rotor connected in star to 3 sliprings and external resistance unit) very high starting torque, low starting current;

Synchronous motor; (standard stator, and wound rotor connected to DC supply for 'excitation' of rotor field) constant speed, power factor correction.

What are causes of voltage drop in transformer?

An ideal transformer (one with no losses, and not a bad approximation for the real thing) has an input power equal to its output power. In simple terms, since power is the product of voltage and current, then for a given value of power, as the voltage goes up, the corresponding current will go down.

What generator produce voltage or power?

First of all power = voltage* current*power factor (a constant that varies on the characteristics of the electrical system)
so to generate power a generator has to a level of voltage and should be capable to handle the current demand of the load (viz electrical load like the bulb we use at home or the pump motor - everything connected to the generator by electrical wire put together).

Why choke coil is used in tube light?

To limit the current through the lamp when the gas ionises and conducts.

What is the total resistance of a 6-ohm resistor and a 12-ohm resistor in a parallel series?

In series like so ---6 ohms ---- 12 ohms --- , the total resistance is just 6 ohms + 12 ohms.

assuming you mean in parallel like this:

_|---6 ohms-----|

-|~|-

_|---12 ohms---|

then the resistance of this can be calculated like so:

1/6 ohms + 1/12 ohms = 1/R (where R is the resistance of the circuit as a whole)

2/12 ohms + 1/12 ohms = 1/R

3/12 ohms = 1/R

1/4 ohms = 1/R

so R = 4 ohms

A few notes, if the resistors are in parallel the total resistance will always be less than or equal to the lowest resistance in parallel (i.e 6 ohms in parallel with 12 ohms will have resistance less than 6 ohms).

Also if two resistances in parallel are the same, then the resistance is half of the resistance of both resistors (i.e. 1/2 ohms + 1/2 ohms = 1/R; 1 = 1/R, R=1 ohm which is half of 2 ohms).

This process can be extended to 2 or more resistors in parallel.

i.e if we had a 6 ohm, 6 ohm and 12 ohm resistor in parallel we could go

1/6 ohms + 1/6 ohms + 1/12 ohms = 1/R

(1/6 ohms + 1/6 ohms) + 1/12 ohms = 1/R

1/3 ohms + 1/12 ohms = 1/R

4/12ohms + 1/12 ohms = 1/R

5/12 ohms = 1/R

so R = 12/5 ohms or 2.4 ohms

How much resistance is in the circuit if it uses a current of 0.01 A?

There is insufficient information in the question to properly answer it. You need to specify, also, the voltage, in order to determine resistance from current. Please restate the question.

Ohm's Law: Resistance = voltage divided by current.

Characteristics of resistor in series and parallel connection?

Resistors in series add resistance to an electrical circuit. For instance two 1 ohm resistors in series will have 2 ohms of resistance.

Resistors in parallel divide the resistance between them. Thus two 2 ohm resistors in parallel will have 1 ohms total resistance.

resistors of different sizes work the same way. a 4 ohm and 2 ohm resistor in series have 6 ohms resistance. While in parallel they will have .75 ohm resistance.

resistance formulas:

series: Req = r1+r2+r3....+rx

parallel: Req = 1/r1 + 1/r2 + 1/r3 ..... +1/rx

The motor states it is 230V single phase to operate. Does that mean you need two 120V lines in and just a ground with no neutral?

Answer for USA, Canada and countries running a 60 Hz power supply service. The proper terminology is L1,L2,N. N is for neutral and it is this wire that is grounded. The voltage measurement from the L1 to N will give you 120 volts. Also from L2 to N will give you 120 volts and from L1 to L2 will give you 240 volts. Single pole breakers in the panel board starting at the top, alternate between L1 and L2 all the way down to the bottom. These breakers all have 120 volt outputs. If you plug a 2 pole breaker into two slots then you get a 240 volt output because L1 and L2 are adjacent to one another. <><><> If the rating plate on this motor says 230V and it has a brown wire (the 230V "hot" or live"), a blue wire (the "neutral") and a yellow/green wire (the "earth" or "ground") it was designed for use in Europe or other world areas which use a 50Hz supply. Those wires mean it requires just one "hot", running at 230V and a neutral. In 50Hz areas that neutral is connected to earth (ground) back at the breaker panel. If you are planning to use it in a 60Hz area, such as US or Canada, it would be wise to determine exactly how the ground wire is wired inside the motor. Check it by using a test meter: if it was made in the past 30 years or so the earth/ground wire should be connected only to the frame of the motor and should not be connected to the neutral wire in any way. If you are sure that is the case, then you can use the motor but only if you do not use the 60Hz supply's neutral, which is the white wire. Connect the motor's brown wire to one of the 60Hz supply's "hots" - say the red. Then connect its blue wire to the 60Hz supply's other "hot" - say the black. (It doesn't actually matter which hot goes to which.) Be sure to connect its ground wire to the 60Hz supply's ground, which is green or bare wire, and do not connect the 60Hz supply's white neutral at all. Just leave it blanked off inside an insulated connector or wire nut.

If it is an old type of 50Hz motor it might have a red (or, in newer models a brown) 230V hot wire with a black (or, in newer models a blue) neutral wire with plain green (or yellow/green) ground wire. If, using a meter, you find the motor's ground wire is linked both to the frame of the motor and to its neutral wire, that link to the neutral will have to be cut before you try to use the motor. Leave the ground wire connected only to the motor's frame. If you don't make sure that link is cut so that the neutral is no longer connected to the ground wire, you will have big problems when you hook up the motor because, back at the breaker panel, the 60Hz supply's neutral is connected to the ground, so if that link within the motor had not been removed, it would cause a short to whichever 60Hz hot (red or black) you connected to the motor's neutral wire! Note: if the motor does not have brushes running on an armature then it is a squirrel cage or similar type induction motor, which means that, running on 60Hz, it will spin at a speed 60/50 of its rated design running speed. That is 20% faster than it would spin at 50Hz, so it would be wise to check that the higher speed is suitable for the equipment you want to use the motor for. For more information see the answers to the Related Questions shown below. Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

How do you reduce elctrical harmonics?

You will need to calculate a capacitor at the output stage in order to prevent interaction with the networks connected after the output.

Explain with neat diagrams construction and working principle of a single phase transformer?

Current transformers are used to transform high currents to standardized values for control equipment as relays and meters.The primary winding in a current transformer is incorporated in the line and carries the current flowing in the network. The magnitude of the secondary current is dependent of the ratio of the transformer. A current transformer (CT) is a type of instrument transformer designed to provide a current in its secondary winding proportional to the alternating current flowing in its primary. They are commonly used in metering and protective relaying in the electrical power industry where they facilitate the safe measurement of large currents, often in the presence of high voltages. The current transformer safely isolates measurement and control circuitry from the high voltages typically present on the circuit being measured. The most common design of CT consists of a length of wire wrapped many times around a silicon steel ring passed over the circuit being measured. The CT's primary circuit therefore consists of a single 'turn' of conductor, with a secondary of many hundreds of turns. The CT acts as a constant-current series device with an apparent power burden a fraction of that of the high voltage primary circuit. Hence the primary circuit is largely unaffected by the insertion of the CT. Usage Current transformers are used extensively for measuring current and monitoring the operation of the power grid. The CT is typically described by its current ratio from primary to secondary. Often, multiple CTs are installed as a "stack" for various uses (for example, protection devices and revenue metering may use separate CTs). Similarly potential transformers are used for measuring voltage and monitoring the operation of the power grid.

How do you go from 208v to 230v?

You need a step up transformer unfortunately. Buy an Ugly's book electrical reference book. They're great and there is a transformer chart in there that will list the proper size or Kva that you will need according to your amperage need.

How is an ammeter converted to a voltmeter?

The ammeter is used in series, because you want to measure the current through a circuit. The voltmeter is used in parallel, because you want to measure the voltage across a circuit.

If you were to place the voltmeter in series, no current would flow because of the relatively high impedance of the voltmeter.

If you were to place the ammeter in parallel, you would create a short-circuit, due to the relatively low impedance of the ammeter.

Can a Dy11 vector group transformer be connected to a Yd1 vector group transformer source?

In series, yes. In parallel, nope!

Putting a Yd1 transformer in series with a Dy11 transformer would result in the output of the Dy11 transformer being identical to the input of the Yd1 transformer with the exception of the voltage magnitude - this will change depending on the winding ratio's on both transformers.

But, in regards to other properties of the voltage, the phases will in be in phase, with the voltage in-between the two transformers lagging by 30 degrees.

What is the formulae for the relationship between amps volts and resistance?

The current [I] (measured in Amps) is equal to the power [P] (measured in Watts) divided by the voltage [V] (in Volts).

I = P/V

Amps = Watts / Volts

Therefore,

P*V=I

Watts * Volts = Amps

What is the difference between squirrel cage and slip ring induction motor?

the difference is that squirl cage the rotor is short circuited while it is on operation and out of operation while the rotor of the bother one is connected to nexternal circuit to reduce the starting intial current

What is the difference between single phase and three phase voltage measurement?

Phasing, or the number of phases in an electrical system has nothing to do with the voltage. A single phase and three phase supply could have a voltage supply of any given voltage from virtually 0 to infinity. Most single phase power supplies in the US are 120/208-240 volt. Three phase power supplies are typically 120/208 to 277/480 volt.

How do you do a earth loop impedance calculation?

The earth-fault loop includes the consumer's line conductor, the consumer's protective conductor, and the earth parth external to the consumer's installation (including the low-voltage winding of the transformer, the distribution line conductors to the installation, and the earth return path.

The purpose of this test is to measure the actual value of the earth-fault loop impedance and to confirm that its value complies with the tabulated maximum values listed in BS 7671:2008 Regulations for Electrical Installations, Tables 41.2 - 41.5. The value must be low enough to enable sufficient fault current to flow to cause any overcurrent protection device to operate within the periods specified -i.e. 0.4 s for circuits supplying socket outlets and fixed equipment in bathrooms, and 5.0 s for circuits supplying fixed equipment.

The theory behind the test is as follows. With no current flowing around the loop, there are no voltage drops and, so, the transformer's full open-circuit voltage (U1) will appear between the line and protective conductors at the point where the test is conducted.

A simulated earth fault is then applied, by inserting a current-limiting resistor between the line and protective conductors. The resulting fault current (IF) is then measured, together with the voltage drop (U2) across the limiting resistor. The duration of this fault should not be allowed to exceed two cycles (40 ms at 50 Hz) to avoid damaging the circuit.

The earth-fault loop impedance is then calculated by dividing the difference between the two voltages (U2 - U1) by the resulting fault current (IF), which will give the impedance of the complete loop (including the limiting resistor), from which we must then subtract the value of the limiting resistor.

As the simulated earth fault must not exceed 2 cycles, this (theoretical) test obviously cannot be conducted with a voltmeter and an ammeter, and so it is conducted with a commercial instrument, called an earth-fault loop tester, which performs all the measurements (U1, U2, IF), makes all necessary calculations, and provides an digital readout directly in ohms -while, at the same time limiting the duration of the test to less than 40 ms.

Before conducting the test, the continuity of the protective conductors must have been confirmed. If the test was to be performed with a break in the protective conductor, then the protective conductor up to the point of that break would represent a safety hazard to anyone in contact with equipment at the time.