answersLogoWhite

0

📱

Electrical Wiring

Ask questions here about proper wiring and electrical installation here.

4,935 Questions

What happens when a 200 volt equipment is plugged into a voltage supply of 220 volts?

For more information see the answers to the Related questions shown below.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

What will be the size of cable for 75 HP 220 Volts 3 phase motor?

75 HP = 55 KW

55 = 31/2 x 0.220 x I x cos φ = 31/2 x 0.220 x 0.8 x I

I = 55/(31/2 x 0.220 x 0.8) = 180,42 A

3 x 70 mm2 is the size of cable for 75 HP 220 Volts 3 phase motor

Compare and contrast the flow of the water in a pipe and the flow of electrons in a wire?

The bigger the pipe the less resistance to water flow which is analogous to the electrons in current flow. As you make the pipe narrower the resistance to water flow would increase (Less water would flow). Hence higher resistance means lower current in both water and electrical example.

If you had a big vat filled with water and a spigot at the bottom you could turn on and off, you could simulate voltage and current.

The water in the vat represents the potential voltage or stored electron charge. With the spigot off the voltage is constant and the current (flow) is zero. If you open the spigot a small amount you get a trickle of water flowing since the resistance is very high. This will make the water (potential) last longer like a battery that has a small load. As the spigot is opened more, more current flows and the quicker the potential will be reduced to zero.

Can you get a 3 phase supply from single phase and how?

No, you cannot get a three phase supply directly from a single phase supply.

Nowadays electronic inverter units can be bought that will do the job. For very low power loads the cost of such invertors is quite reasonable but for high power loads they are very expensive.

For high-power industrial uses the most economical solution is to have a 3-phase service installed by the local electric power utility company.

What are the advantages of three phase induction motors over the other motors?

A Single phase induction motor includes a main winding, an auxiliary winding, a run capacitor, & a subsidiary star device. The auxiliary winding is configured such that the number of turns of the aauxiliary winding through which a current flows, varies according to the operating mode of motor. When the motor starts, the number of turns of the auxiliary winding through which a current flows is reduced there by increasing the start efficiency of the motor. when the motor runs in normal mode, the number of turns of auxiliary winding through which a current flows is increasing there by increasing the operations efficiency of motor

What is the clearance required between phase bus bars in 440 volt system?

Your question should read, 'How much clearance is needed between LINES.... (not 'phases')?' The answer will depend on local authority regulations. The clearances in air tolerated by REC companies in the UK is 90 mm line to line and 127mm phase to earth. Even though there is a greater potential difference between line to line, the gap is less. I think it's to do with public safety if it flashes to earth.

How do you use a megger tester?

There are basically two types of meggers, an electronic one and the old-fashioned hand-cranked type. On the whole megger testing is non-destructive.

What happens is a DC voltage is applied to the device or winding under test. It is basically an insulation test to see if the insulation has been injured in any way to cause a short circuit when normal power is applied to it.

On some meggers there are 3 ranges 300V, 750V, and 1000 volts. Applying the proper voltage is essential to avoid damaging the device you are testing.

Working voltages up to 240 volts should use the 300 range. Working voltages up to 600 volts use the 750 volt range and working voltages above 600 use the 1000 volt range.

If you used the 1000 volt range on a device that had a working voltage of only say 24 volts, you could damage the insulation of the device just by testing it! So meggering a device is only non-destructive if you use the tester as its instructions tell you to.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

How can you run a three phase motor on a single phase supply?

for countries in Europe and other world areas running a 50 Hz supply service. UK household AC power mains voltage is now 230V (previously it was 240V) 50 Hz. From a 415 volt 3-phase incoming supply you will get this voltage between any ONE line and the Neutral.

Between any two lines you will get 415V. DO NOT WIRE IT LIKE THIS!

So, if you wire the motor to any ONE line (and ONLY ONE) and Neutral you'll get the correct voltage.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

+++

My advice would be to buy a proper transformer which can be connected to a 415V 3ph input and give 230V 1ph output at a current rating suitable for the motor and its purpose. I assume the questioner's installation is in a commercial premises because domestic supplies in the UK are 230V 1ph only - running a 3ph motor off that requires a suitable inverter.

What are the examples of single and two phase system?

In its simplest form, a single-phase a.c. system comprises two conductors: a line ('hot') conductor and a neutral conductor. In North America, however, it is usual for a single-phase residential supply to have three conductors: the two 'hot' conductors are connected across opposite ends of a single-phase transformer winding, while the neutral conductor is connected to the centre (tap) of that winding. This provides a combination of 240 V and 120 V, and is known as a 'split phase' single-phase system.

A two-phase a.c. system is very rare, these days, and you are unlikely to come across one. It is an archaic system that has long since been replaced by the three-phase system. Essentially, this system was provided by an a.c. generator whose armature windings were physically displaced from each other by 90 degrees, thus providing two phase voltages that are 90 electrical degrees apart. Usually, a two-phase system was a three-wire system, providing two line conductors and a neutral. The resulting line voltage (measured between the two lines) would then be 1.42 times either of the phase voltages (measured between one of the lines and the neutral).

What is the electrical symbol for a GFCI receptacle?

== == == == It's a receptacle symbol, usually with "GFCI", "G", or "GFI" written under it. To find out exactly which symbol is used on your prints, look at the electrical legend, which is normally page E-1, E-001, etc.

What is the voltage between each lead of a 480 volt three phase delta secondary?

A 480 v three-phase system has 480 v between live lines and 277 v from each line to the neutral. This type of supply is common in North America for supplying for example small factories that need more power than a 120/208 v three-phase system can supply.

Why is the power off on on breaker when it is not flipped off?

Turning the breaker on allows the power to flow through to the outlets, lights, and appliances on that circuit, so yes power goes to and through a turned on breaker. If the breaker is off, but the main power is on, power still get to the breaker, usually from the bus bar that runs down the middle of the back of the breaker box.

What is the kv phase to phase for 13.8kv?

There is no such thing as a 'phase-to-phase' voltage; the correct term is 'line-to-line' voltage. Whenever you mention a value of voltage for a three phase system, it is considered to be a line-to-line voltage unless it is stated clearly that this is phase voltage (line to neutral) voltage.

(The reason that there is no such thing as a 'phase-to-phase' voltage is because phases exist between, or 'across', line conductors or between a line conductor and a neutral.) That is a world wide practice for electrical power engineers.

Why do we use star to star connection in motor?

In a high voltage installation, with the same power, current drawn is small compared to those in low voltage. However it requires a thicker insulation, thus cost of insulation is significant compared to the conductor cost.

By using a star connected winding, the insulation voltage required is equal to line to neutral connection, otherwise if it is connected in delta the insulation rating has to be provided for a line to line connection.

Despite having a higher current, the total cost is still lower compared to using a higher insulation rating.

How do you calculate the voltage drop for 238 KW 3 phase 415 V and length of circuit is 20 meters?

You need also to know the resistance of the cable. First you establish what the current of the load is. Then from that you calculate the wire size. From a wire size chart you find the wire resistance. Then use the formula I (squared) x R.

Your building has a 3 phase 240v and you want to convert it to be 110v?

Best to get quotes from two or three licensed electricians for the installation of the necessary extra fuses, breakers, etc., testing and commissioning (= handing over to customer to use) of a 120V panel for as many circuits as you want. Though the question does not specifically ask about DIY ("Doing It Yourself"), if you are not a licensed electrical technician you should not even think of doing this kind of work as a DIY project because 3 phase 240V power supplies can kill you if you don't know exactly what you are doing. Depending on your local wiring codes and regulations, it may be illegal to attempt to do such work if you are an unlicensed person.

Do you need a circuit breaker in a house?

1 for every 13 outlets, lights etc plus one for each major appliance ( heavy duty ) The minimum *required* number of circuit breakers will be dictated by your local building codes, so there is no one answer that will fit all. If you are planning on building or remodeling a house and are just interested in a back of the envelope estimate, keep in mind that up to a point, more circuits, and thus circuit breakers, are better than fewer. At a minimum, I would use a dedicated circuit for each of: - the furnace - the air conditioner - the refrigerator - the stand alone freezer - the basement lights (or the lights for where ever the breaker box is located) - the sump pump (if you have one) - the water pump (if you have one) - the garage door opener By using a dedicated circuit for each, you minimize the chance of a malfunctioning device or frayed extension cord causing the shut down a critical house hold system. From there it's a matter of how many rooms and outlets. For a family room with an entertainment center, computer equipment, etc., two circuits for the outlets and one for any overhead lights would not be unreasonable. On the other hand you might have two bedrooms share the same circuit for wall outlets and another shared circuit for the ceiling lights. If each room has its own air conditioner, the ideal situation is to locate an outlet by the window which is a circuit dedicated just for that air conditioner. As an aside, ground fault detectors are a must for the kitchen and bathroom, but use self contained ground fault outlets rather than a ground fault circuit breaker for these areas. Ground fault circuit breakers are best for outdoor circuits, like outdoor lighting, swimming pools, etc. While the building codes may dictate a minimum number of circuits needed, based on the size of the house, there is nothing to stop you from having more. What you will need to do however, is make sure you do not exceed the capacity of your electrical service. For that the services of a licensed electrician are highly recommended.

What is the formula for calculating DC votage from a 3 phase rectifier bridge using AC voltage across one phase?

A 3-phase rectifier bridge can be used with a single phase supply, it just means that four of the diodes are not connected. The peak voltage (if a reservoir capacitor is used) is sqrt(2) times the rms supply voltage and the average voltage using inductor smoothing is 0.9 times the rms voltage.

How do you calculate cable size for given load?

Generally speaking, you would find conductor ampacity (the amount of current it can handle continuously) in Table 310.16 of the NEC (National Electrical Code). The numbers in the table are good as long as you don't go over the stated number of conductors at the top of the table and the 86 degree Celsius ambient temperature. If anything changes, use the adjustment factors for conduit fill and ambient temp.

However, with all the possible other applicable sections of the NEC, it really depends on the type of load and howand where the cable is fixed because its operating temperature will depend on whether it is enclosed in a duct, is buried underground or is outside in the open air.

For a typical load, not knowing anything else about it, I would multiply the load (in amps) by 1.25 and find a wire with at least that ampacity.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

How do you Connect 3 phase water heater to single phase?

Most 3-phase welders cannot be made to function on single-phase power. If your welder is an inverter type, such as a Miller Dynasty or Lincoln Invertec, then it may have a single-phase mode with reduced current output. You would have to download the manual for your particular welder. If it is an older transformer (big and very heavy), then you're probably out of options here.

What will be the cable size for 300 A if the 3 phase voltage is 220 volts?

At least 50mm but with all the de-rating factors it might be 70mm that's if its 2 cable single phase non armoured clipped direct. Check out the tables dopey!!!!

FYI 50 mm = 2 inches, 70 mm = 2.75 inches these are not wire sizes, sound more like cable outside diameters.

Correct answer

The wire size is dependant on the insulation factor on the wire. A few common insulations and corresponding wire sizes for 150 amps are - Size 0 R90 good for 155 amps, also with insulations of RW 75, TWH, TW75, good for 150 amps. Size 000 TW good for 165 amps.

Can you please explain what RMS value is?

RMS stands for Root Mean Square. It is a method of averaging where you take the squares of a bunch of samples, average them with an ordinary mean, and then take the square root. This gives greater weight to larger values. In the case of an ordinary sine wave, the RMS value is 0.707 times the peak value, 0.707 being 1/2 the square root of 2, and the peak value being one half the peak-to-peak value. For example, in the US, a "standard" 117VAC line voltage is actually an RMS voltage that corresponds to a peak voltage of 166VAC.

RMS is a necessary unit because, often, the waveform is not sinusoidal, it is sawtooth, such as in a power supply. Using an ordinary VOM, calibrated for a sinusoidal AC scale in such a case, will give an inaccurate reading of ripple voltage. Most modern DMM's have a true-RMS mode which will work correctly by using sampling and analysis technology.

RMS is also a necessary unit because RMS is a better indication of how much power a signal can impart to a load.

Another answer

RMS stands for Root Mean Square value.

In electrical technology, where alternating current (AC) is used, RMS Voltage and RMS Current (Amps) must be used to calculate the average power supplied or consumed. See the link below on how to find the RMS.

In fluid flow technology related to gases, velocity is calculated as an RMS value because it can be used to find the average velocity of an ideal gas.

Yet Another Answer

Because a AC current is continuously varying in both magnitude and direction, it's necessary to measure it in a meaningful way. The rms-value of an AC current is equivalent to the value of DC current necessary to do exactly the same amount of work. For example, a sinusoidal AC current which peaks at 100 A has an rms-value of 70.7 A, and does exactly the same amount of work as a DC current of 70.7 A.

What is the starting sequence of a star-delta starter?

This is the schematic for the starter. K1T is a timer. Initially KM1 and KM3 are closed to start the motor. Then KM2 is closed and KM1 is opened to run the motor This is the equivalent ladder logic using relays and timers.

What is the difference between neutral and earth wire in the distribution system?

Both conductors are at ground potential. They are connected together with a bonding jumper at the panel. The primary difference is the neutral is used as the return current path for single-phase loads, and the ground is the return path for fault current only. So, unless the hot conductor accidentally comes in contact with, say, a grounded equipment cabinet, there would be no current flow on the ground wire. The neutral wire carries current any time the single-phase load is in operation. With a three-phase balanced load, no neutral is necessary or required, yet electrical codes still require a ground wire for safety.