answersLogoWhite

0

📱

Electrical Wiring

Ask questions here about proper wiring and electrical installation here.

4,935 Questions

What is the basic difference between electronics and electrical?

I'm not an electrician and someone else can surely give you a better answer than this, but here goes: * Electricity- is the reason why electronics has a function to used by man. -support our appliances.

* Electronics are the things that need electricity to run on. Electronics are things like stereos, graphic equalizers, car stereo amplifiers, the guts of a GPS device, etc., ... it can also refer to the stuff inside these devices like wires, circuit boards, capacitors, resistors, RAM, circuits, etc. Example:

Here's an anology: Imagine one of those old grain mills next to a creek that's powered by the running water. The water would be like the electricity and the gears, wheels, and presses inside would be the electronics.

How do you measure the circulating current in 3 phase parallel system?

The clamp on amp meter has to go around both of the parallel conductors to get an accurate reading of the line current. If you are using a current transformer, both wires have to go through the centre hole in the transformer.

Advantage of having a star - delta connected motor starter?

Whichever way it is connected, no matter whether it is in a star configuration or in a delta configuration, a 3-phase motor's start-up current can be more than 4 times its normal running current.

If the star configuration is used when first switching-on power to a 3-phase motor, a much smaller "start-up surge" is forced onto the power lines than if it were switched-on directly in the delta configuration.

So "using star for start-up" achieves very worthwhile purchase cost savings because smaller circuit breakers and thinner 3-phase line wire sizes can be installed to supply power to the motor.

However, leaving it running in star has a major disadvantage: the motor can never deliver as much power and torque as when it is running in delta.

For that reason a 3-phase motor was usually started in star mode and then - after reaching a steady speed - switched over to run in delta mode to achieve its maximum power output.

The explanation for this is easier to understand if you draw a sketch of the wirings and their connections, but unfortunately we cannot use diagrams when giving an answer here! Anyway, if you draw the circuit diagram for the windings connected in a "star" or "Y" configuration, it should look like a three-pointed star, with a phase input power line attached to each point of the star.

Thus, when a 3-phase motor's three windings are connected in a star configuration, the current from each individual phase power input line goes directly into one winding and is then series-connected to both of the other two windings via the star's "center-point".

If you draw the circuit diagram for a delta configuration, it should look like a triangle with a phase power input line attached to each point of the triangle.

Thus, when a 3-phase motor's three windings are connected in a delta configuration, each winding is effectively connected directly to two phase supply lines. The third phase supply line is also connected to that winding, but indirectly via the other two windings. They are connected in series to one another, and that series pair is connected in parallel across the first winding, to form the "delta".

The much lower starting current is the main reason why a three-phase motor was usually started in star mode and then - after gaining a steady speed - was switched over to run in delta mode to achieve its maximum power output.

Update: Electronic motor-control systems, which offer soft-starts in DELTA configuration, are now replacing the use of manual or semi-automatic star-delta starters.

Technical explanation

When the windings of a 3-phase motor are connected in STAR:

  • the voltage applied to each winding is reduced to only (1 /.'/'3) [1 divided by root three] of the voltage applied to the winding when it is connected directly across two incoming power service lines in DELTA.
  • the current per winding is reduced to only (1 /.'/'3) [1 divided by root three] of the normal running current taken when it is connected in DELTA.
  • so, because of the Power Law V [in volts] x I [in amps] = P [in watts],

    the total output power when the motor is connected in STAR is:

    PS = [VL x (1/.'/'3)] x [ID x (1/.'/'3 )] = PD x (1/3) [one third of the power in DELTA]

    where:

    VL is the line-to-line voltage of the incoming 3-phase power service

    ID is the line current drawn in DELTA

    PS is the total power the motor can produce when running in STAR

    PD is the total power it can produce when running in DELTA.

  • a further disadvantage when the motor is connected in STAR is that its total output torque is only 1/3 of the total torque it can produce when running in DELTA.

For more information please see the answers to the Related Questions shown below.

How do you wire a three phase motor if none of the wires are idetified?

If it is a three lead 3-phase motor, it is easy: connect the incoming three leads randomly to the three leads on the motor (one to one) so that there are a total of three splices. The motor will run but possibly in reverse If it runs in reverse, switch any two of the three splices ---- If the motor has more than three leads, and they are not marked, it is much more difficult. You will have to have a working knowledge of how to test the leads and compare the results with the information given on the nameplate

If an industrial customer of an electrical power company connects a large single phase load to a three phase power line then every user on that power line will have unbalanced power explain why?

A 'balanced' three-phase load, by definition, is one in which the load connected in each phase (either line-to-line or line-to-neutral) is identical in all respects. A single load, clearly, doesn't comply with this definition.

What is constantan wire used for?

In essence it is used in applications where it is important that the resistance of a length of contantan wire doesn't change with temperature. As a student the only time I've ever needed this feature is in experiments involving measuring resistance.

A use for constantan wire is in DC Current Shunts. This is a precision low value resistance placed in series with the load in a direct current circuit that is carrying high current. By measuring voltage drop across the shunt, we can measure the current. In this application it is important that the resistance of the shunt does not vary with temperature (the shunt will heat up under full load) otherwise the accuracy of the current reading is compromised. Typically the resistance of the shunt is set to give 60 millivolt voltage drop across it at full current.

Are single phase 208v and single phase 230v equivalent?

No, not really. 208V is derived from two phases of a 208/120 three phase power system, while 230V (or 240) is a single-phase power system already. Motors and other loads are usually notrated for both voltages, and could be damaged if fed the wrong one. Of course, other devices are rated for both. If so, it will be listed on the nameplate.

Is a three phase high leg delta better than a wye for a motor?

There is really no advantage, the only purpose of having the variety is for motor manufacturer companies to be able to sell their product to customers if the building's electrical service is of a Delta of Wye configuration.

How does a pressure to current converter works?

An electrical circuit is an example of an electrical pressure to electrical current convertor.

What are the advantages of three phase to single phase electric power distribution systems?

This Answer is the same as the for the Question 'Why is power for a country's mains grid usually generated as 3-phase electricity not single phase?'

Single phase power has a sine wave voltage that crosses zero before reversing its polarity. In the region near the zero-crossing there is not much power. At zero there is none at all. So single phase loads often need some trickery to deliver output in this area. Often it is just the inertia of the motor or appliance.

Three phase power is always delivering power on one of its phases, and is thus preferred for machines, motors and appliances that use lots of power.

Three phase power generation is preferred if the application needs very high power, or nees relatively small power output but with with weight restrictions - as in automobiles, where the power is generated in a 3-phase alternator and then converted to DC using rectifiers!

Use of DC (Direct Current) is the next step up for smooth high-power devices but requires rectification, regulation and smoothing to be useful.

Another problem with DC is that, for efficient long distance transmission, it cannot be simply converted to much higher voltages than the voltage at which it was generated at the power station.

Similarly DC cannot - simply by using transformers - be converted down to safer, much lower AC mains voltages for use by consumers.

Conversion of DC to AC requires the use of expensive high-power electronic "power inverter" systems and the opposite - the conversion of high-power AC to DC - requires the use of very big power rectifiers.

AC (Alternating Current) is used for high power generation and distribution because it can easily be transformed, using transformers, to achieve very efficient power transmission over very long distances and can then be transformed down to low voltages for distribution to consumers.

Two phase, and higher multi-phases are also used, but very rarely, for a few very specialised applications.

<><><>

A three phase system provides constant torque, whereas single phase does not.

With three phase you will get more power per kilogram of metal to generate electrical energy.

Answer

For a given load, a three-phase supply uses less copper than a single-phase system. In other words, it's more economical!

Why would you use a three phase transformer in place of a single phase transformer?

the necesscity of two three phase transformers operating in parallel are as follows...

  • if the one transformer fails to give supply,then another transformer can be used in parallel and hance,continuity of supply can be maintained.
  • one transformer can be easily take out from the supply for repair & maintanance.
  • if the load on the substation increases beyond the rated values of transformer, then another transformer can be used to share rhe load of the substation.

What is the purpose of a transistor in a circuit?

A transistor has three leads, called the base, the collector, and the emitter. The voltage of the base (in relation to the ground) determines whether and how much current flows from the collector to the emitter. An NPN transistor can be off, meaning that there is no (or very little) voltage from the base; partly on, meaning that there is some voltage from the base; or saturated, meaning that it is receiving full voltage from the base. A saturated transistor allows the current to flow from the collector to the emitter unopposed; a partly on transistor provides some resistance; and a transistor that is off provides full resistance. A PNP transistor is similar to an NPN transistor except it performs the opposite function: when it is saturated, the current is fully resisted; when there is no voltage from the base, the current is not at all resisted; and when it is partly on there is some resistance.

In sum, a transistor controls the flow between the collector and the emitter based upon the voltage of the base. this is carbage. a transistor is basicaly two diodes back to back base being common TO BOTH DIODES because of inpurity doping on purpose at the depletion region the transistor will control the current flow on the other diode. Once it reaches saturation both diodes conduct therefore current can flow in BOTH DIRECTIONS ACROSS IT.

What is the effect of voltage reduction on three phase induction motor?

Voltage reduction usually results in an increase in load current which, ultimately, will cause the machine's overcurrent protection to operate and disconnect the motor. This overcurrent may also result in increased voltage drops along the supply lines that can exacerbate the situation as well as affecting other consumers that share the same supply.

How does a single phase transformer work?

a single phase motor has 2 parts. a stator and rotor.

the supply is fed to the stator windings.as a result of that,a magnetic field is developed on the stator windings which runs at synchronous speed. this magnetic field is induced on the rotor's windings which produces a torque on it and it starts rotating.this is how a single phase motor rotates.

that is partially right

but the ac supply has two half cycles +ve and -ve

due to which there is magnetic field developed which is alternating in nature due to which the net torque developed in the rotor becomes zero and there is no rotation

so to avoid this there is an arrangement of capacitor in the stator to make the rotating magnetic field unidirectional and with a constant magnetic field

after that the answer above is right

What size wire for 3 phase 60 hp motor?

If you had to ask this question here you need to learn more about your local wiring code re all the items you must use for this new motor circuit.

So that the new installation is safe and legal - and complies with the terms of your home or business insurance policy - you must use the correct type and size of cable, the correct type of circuit breaker and the correct type of wall outlet.

Serious home fires can result from incorrectly-installed new circuits.

Another answer

NEC table 430.248 lists this motor as drawing 17 amps, !7 x 1.25 =21.5 amps. Number 10 copper wire.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS

What does a step up transformer increase?

Power is normally transmitted at high voltage through step up/step down transformers to minimize the power losses in the transmission lines (this is one reason anyway). Since power loss is equivalent to the resistance of the conductor times the current squared, stepping up the voltage by a factor of two cuts the transmission losses by a factor of (2^2 = ) 4.

Why do the current readings differ for increasing and decreasing values of the incandescent lamp wattages?

While Voltage and Resistance typically remain constant in incandescent lamps: P (Power in Watts) = I (Current in Amperes) times E (Electrostatic energy in Volts [AC and DC]).

P=I*E - when P (Watts) goes up so does I (Amps).

How do you check a ground fault interrupter?

There is only 2 forms of Ground fault protection. A breaker or a recptacle (stadard plugs and outlets). Both are obvious to the naked eye. A recptacle will have a test and reset button that will turn it on and off. This is a sensor that constantly monitors the diffence of potential between the HOT wire and the grounded conductor . If this gets to and unacceptable limit It will trip. The breaker will have a test and reset button next to the switch. The complicated part is that 1 GFI outlet can protect multiple outlets. When it is hooked up it has an option to Downstream other outlets. Theese outlets are then monitored by the same sensor in parralel with the first. The best way is to push the test button and check for outlets that shut of with the GFI. Code requires a GFI protected outlets to have a sticker on it stating that fact. A breaker wll protect the entire circiut from ground faults provided it is hooked up correctly.

If resistance is constant and voltage increases what happens to current?

You have it backwards, the resistance controls the current not the current controls the resistance. I = E/R . Your question should read, "If the voltage is constant and the resistance in the circuit is increased what happens to the current?" Say the voltage is 120 volts and the resistance is 30 ohms, I = 120/30 = 4 amps. Now we double the resistance to 60 ohms, then I = 120/60 = 2 amps. So now you can see if you increase the resistance the current drops.

How do you convert or rewire a 3 phase motor to a single phase?

Of course, but it will change all parameters (HP, torque etc.) The problem is someone would have to redesign of that motor, size of coils in field winding according to new voltage, speed and HP ratings. Basically, is not worth it.

What is the purpose of a LED in a circuit?

An LED, or light emiting diode, can have many functions. Commonly used as a solid state light emitter, LEDs of nearly any color of light are available, including ultraviolet and infrared.

A less obvious use of a light emitting diode is to detect light. A LED makes a very efficent and narrow band light detector. It will produce electric current in response to light that is about the same wavelength (and therefore color) as when it is used as an emitter.

Another use of an LED is to make a fairly stable voltage reference; A red LED when forward biased will have a steady voltage drop of about 1.8 volts, an orange LED produces a voltage drop of about 2.0 volts, and about 3.5 volts for blue and white emitting LEDs.

LEDs can be used as modulated light emitters to transmit speech, music and digital information. A good example is a television remote control which digitally pulses a infrared LED to change channels, control volume, and so on.

LEDs are used in solid state switches when optically coupled to a photodiode or photo resistor. LED flashlights are very common, and some small light bulb replacements are available, with larger bulb replacements soon to come. Some links are provided below:

How can you connect a 120 volt motor to run with 240 volt?

Answer for USA, Canada and countries running a 60 Hz supply service.

Use one leg of the 240v and the neutral wire. Most electric dryers run the motor this way. The heating element is 240v but the motor is 120v.

NO, THAT IS DANGEROUS ADVICE because a 240 volt service has a circuit breaker which is sized for the current draw of a large 240 volt appliance, so it would have a rated amperage that is too high to protect a 120 volt motor running on its own.

Only 240 volt appliances such as dryers, air conditioners, etc. are safe to use on 240 volt circuits.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

What are the advantages and disadvantages of single phase and three phase in the electrical supply system?

In Australia most power is generated in 3 phase the split down to single phase wen it reaches individual residences 3 phase power is more efficient to produce.

most single phase motors have switching gear and capacitors to help kick a motor on when it starts because single phase power doesn't have enough power to turn over a motor. 3 phase motors are generally simpler and require no starting gear ( normally cheaper to build)

Most workshops have 3 phase machinery for the extra power it prvides

Some motors can be 2 phase (rare) as well.

Why does one line of 3 phase 480v show 0 volts and the other 2 have 480?

My first thought is this is probably a corner grounded delta system, but I'm confused by your voltages. If this was a 460v (L-L voltage) ungrounded or corner grounded system, the phase to ground voltage is meaningless, but the phase to phas voltage will be 460v all around the delta. If you have a 460v system and you're only seeing 230v, there's something wrong.